Skip to content

GridSim 2.1.073 RC-4

Latest

Choose a tag to compare

@github-actions github-actions released this 20 Nov 15:47
Immutable release. Only release title and notes can be modified.

Release candidate RC-4 of GridSim 2.1 (versions 2.1.072 to 2.1.073), built on the 2.1.072 post-RC-3 fixes. Windows x64,
Linux x64 and macOS arm64, self-contained, no .NET install needed. Every RC-3 command, flag, default and exit code is
unchanged, and so is its output except as listed under Changed (first of all the BREAKING CHANGEs: one at rounding level, one to solves that did not converge);
the new work is in new commands and new library entry points. Requirements, verification and known limits: RC4.md.

Added

  • Study cases: study-case runs one immutable master with dated variations, named operation scenarios and a groups
    sidecar (gridsim-groups/1: area, zone, owner, feeder and free groups, bound to the case by SHA-256 and to elements by
    stable identity) as one ordered, resumable batch, with a group-summary mode. case-diff and result-diff compare two
    cases or two result documents by identity, reporting each change with its old value, new value and unit.
  • Analysis verbs: sensitivity (OTDF, PSDF, tap, dV/dQ and dV/dP, control effectiveness), qv-curve, pv-contingency,
    dc-contingency and fault-level-n1. AC sensitivities are refused as OUT OF SCOPE for cases with tap changers, DC
    links, FACTS devices, static var compensators, induction machines or flow-controlling transformers.
  • Seeded random foundation (gridsim-rng/1): a counter-based generator keyed by seed, domain and stream, Gaussian
    deviates, a Sobol sequence of up to 64 dimensions and a thread-count-invariant reduction. Every stochastic result is
    bit-repeatable from its seed; there is no default seed.
  • probabilistic: probabilistic load flow (DC or AC, correlated inputs) and static generation adequacy (LOLP, LOLE, EENS)
    by Monte Carlo, quasi-Monte Carlo or convolution, each result stating its sampling error.
  • reliability-network: reliability and restoration on the real network, binding failure data to groups, isolating
    faults with placed devices and switches, and reporting load-point indices, SAIFI, SAIDI, CAIDI, ASAI, ENS and AENS with
    AC-verified restoration paths, by enumeration or seeded Monte Carlo.
  • line-constants: overhead line constants from conductor geometry (perfect earth or the exact earth-return integral,
    Kron reduction, transposition, sequence constants, optional per-unit values).
  • rpc: a resident endpoint (gridsim-rpc/1, JSON lines on standard input and output, or TCP on loopback) that holds
    loaded cases by handle and runs any verb exactly as the command line does. The Python package gains gridsim.Session.
    The endpoint has no authentication; it is a local tool and refuses a non-loopback listener unless --allow-non-loopback
    is given.
  • Short-circuit duty: g74 (ENA ER G74 style, with decay of machine contributions), ansi-sc (ANSI/IEEE C37.010 style
    E/X breaker duty), sc-61363 (ship systems), sc-dc (DC auxiliary systems) and series and simultaneous fault models in
    Core. iec60909 is unchanged. Items that depend on paid standard text are labelled AWAITING STANDARD TEXT in the output.
  • Protection: a gridsim-devices/1 file places relays (ANSI 50, 51), fuses, reclosers and breakers on branches, with IEC
    60255-151 and IEEE C37.112 curve families or tabulated curves. New verbs devices-check, fault-line, sc-trace and
    protection-audit (pair margins, sensitivity, instantaneous overreach, breaker rating margins).
  • Declarative dynamic models: user controllers as gridsim-model/1 block diagrams, validated and compiled by
    user-model list and user-model check, and bindable to a machine in a dynamics study. Each shipped library model that the
    block catalogue can express matches its coded model bit for bit; the others (AcExciter, Esst4b, IEEEG1 with rate
    limits, HydroGovernor) are not expressible.
  • Small-signal analysis of the full model: modal-full linearises machines, exciters, governors and stabilisers, with
    dense and Arnoldi eigen-solvers, residual-checked eigenpairs, participation, damping and frequency. Controllers the
    block catalogue cannot express are reported NOT LINEARISED.
  • dynamics-study adaptive integration: an optional adaptive member runs every row a second time with a
    variable-step Dormand-Prince kernel, locating events exactly and bracketing critical clearing times without a step grid.
    Overcurrent relays and fuses act inside the run, and a recloser acts for its first shot only. The adaptive rows use the reduced electromechanical swing
    model, and the fixed-step rows and status are unchanged.
  • Node-breaker topology: a native substation model with a topology processor, switching scenarios and
    substation-state; cgmes-export (CGMES 2.4.15 and 3.0 EQ, TP, SSH, SV), cgmes-conform (a named subset of the profile
    rules (eleven checks), not a conformity certificate) and cgmes-study --archive; and dgs-import for ASCII PowerFactory DGS
    files, built from public descriptions, with unconfirmed attribute mappings refused unless --accept-unconfirmed.
  • dist3ph-mesh: meshed unbalanced load flow in an explicit phase frame (named wires, full primitive impedance matrices,
    wye, delta and line-line loads, solid, impedance and shared-grid earthing, split-phase services, SWER), three-phase
    transformer banks, step-voltage regulators with line-drop compensation and quasi-static series. The shipped IEEE
    4-node cases and the IEEE 123-node feeder run through the Core solver. dist3ph is unchanged.
  • emt3: three-phase electromagnetic transients on a new nodal solver, with lines from line constants (constant or
    frequency dependent), faults, breakers, surge arresters, saturable inductors and transformers, and a named status
    instead of a last value when Newton fails. Core entry points add power electronics (valves, two-level bridge, PWM,
    average-value converter, dq controller), synchronous and induction machines, MMC and VSC HVDC stations, LCC bridges, a
    partitioned parallel run bit-identical at any thread count, and an RMS-EMT co-simulation interface. emt and emt-line
    are unchanged.
  • emt3 documents (gridsim-emt3/1, now with a JSON schema file and an example document) take optional machines
    (synchronous and induction machines: no-load or phasor start, torque and field-voltage steps, induction start speed and
    shaft load), dc_buses and converters (the average-value converter and the two-level bridge with sine PWM, open-loop
    modulation or the dq current controller behind a filter) and hvdc (VSC stations with two-level average, MMC
    arm-average or MMC sub-module converters, LCC bridges of 6 or 12 pulses, and Bergeron DC lines) keys, all through the
    existing Core classes. New output kinds: speed, torque, rotor-angle, field-current, dc-voltage-positive,
    dc-voltage-negative and dc-current; the result gains machines and converters tables. A document without these
    keys gives identical output. Partitioned runs are not offered through the document (CLI reference).
  • Workbench on the Avalonia app (Ctrl+Shift+B, and File > Workbench...) and the web client (/workbench/{case}): model
    browser, plot kit (time-current, R-X, harmonic spectrum, eigenvalue plane, Bode, QV, PV, time series), reports and a
    single-line diagram with an undoable editor whose every edit passes the case loader. Open reads v2 cases, PSS/E RAW,
    UCTE and CGMES through the readers the app and the command line use; Add generator, Add load and Add branch take
    typed, validated entries. report renders any result through a gridsim-report-template/1 template.
  • Script console panels: File > Script console... in the Avalonia app and /console in the web app run
    GridSim.Scripting statements line by line, with history, check-only and run-file modes and the session recorded as
    .gss and .run.json. On the web the console loads catalogue cases only, under the licence and private-model rules,
    refuses EXPORT, enforces tick, size, output and time limits, needs the Analyst role for SOLVE POWERFLOW (as
    POST /api/solve does) and the Operator role for other state-changing statements. Manual chapters 8, 9 and 35.
  • --json and --csv through the shared result writer on ten study verbs: probabilistic, reliability-network,
    flicker, filter-design, harmonic-assess, connection-assess, study-case, case-diff, result-diff and
    report (their own --out is unchanged; also in the Python wrapper and rpc).
  • corrective-sequence: the plan names the elements still over their limit after redispatch
    (CorrectiveRedispatch.UnrelievedAfter), only when there are any; otherwise the output is unchanged.
  • GPU backends report where each Newton linear solve ran: after the convergence line a GPU: line gives the solves on
    the device and on the CPU (given up to the CPU LU, or run on the host), and the gpucheck probe lines end with the
    same counts; the run metadata carries them as gpuSolves. Counting only, no arithmetic change; the CPU backend's
    output is unchanged.
  • UK power quality: harmonic-assess (ENA ER G5 Issue 5 stages), flicker (ENA ER P28 Issue 2) and filter-design
    (single-tuned, high-pass and C-type filters). A missing background is reported INCOMPLETE, never a pass; the
    IEC 61000-4-15 filter coefficients are AWAITING STANDARD TEXT.
  • cable-size (IEC 60364-5-52 and BS 7671 design rule) and connection-assess (VDE-AR-N 4105, 4110, 4120, 4130 and BDEW
    rule sets). No standard table or limit is shipped: a quantity without its table is OUT OF SCOPE and every limit is
    AWAITING STANDARD TEXT until the owner supplies a rule file with provenance.
  • Scripting: the GridSim.Scripting library (references GridSim.Core only) and the gridsim-script console. Grammar
    version 1 is a verb-first, line-oriented language in .gss files, frozen for all of 2.x: LOAD CASE, SOLVE POWERFLOW,
    TRIP, CLOSE and SET on generators, lines and loads, FAULT and CLEAR FAULT, REPORT, EXPORT RESULT, PRINT,
    SELECT ENGINE, STEP SIM and AT; FOR EACH <noun> [WHERE ...] over the elements of a case in model order;
    IF / ELSE / END on state, results and time; named values (LET, SET name =) with unit-checked arithmetic (MW + MVAR is refused at validation); and named procedures (PROC, CALL) that may not recurse, directly or indirectly. There
    is no WHILE and no unbounded loop, so every script terminates. Five engines can be stepped: LIVE (now with trips and
    closes of lines and generators and set-point changes reaching its network), FREQUENCY LUMPED, PROTECTION FREQUENCY, RMS CLASSICAL (classical
    multi-machine) and EMT SINGLE_PHASE, plus RMS SUBTRANSIENT and RMS GOVERNED (six-state machines, with governors and exciters, from a gridsim-dynamics/2 file) and EMT THREE_PHASE (each requires its model word; PROTECTION FREQUENCY refuses cases with voltage or loading stages); the last four run over a whole time range and are stepped by deterministic re-run from t = 0,
    with a bit-for-bit check of the part already shown, and each takes a typed WITH settings clause. Names are checked
    against the loaded case and every number carries a unit (MW, MVAR, MVA, PU, KV, HZ, MS, S, DEG); an
    error names its line and column and leaves the session as it was. A step must be a whole multiple of the integration step
    and events land on step boundaries in script order. Every console session is recorded as a .gss file, and every run
    writes a record (gridsim-script-run/1) with the GridSim and grammar versions, the SHA-256 of the script (and of its
    canonical form), the model and every output, the solver and engine settings, the step and event sequence, every IF
    decision, every loop and the named values. The same script gives the same record and bytes. Manual chapter 35.
  • LiveSim.ReplaceNetwork(GridModel): replaces the network the live loop re-solves, between steps, for a topology or
    dispatch change on the same case. Nothing calls it except the scripting layer; a loop that never calls it, or calls it with
    the network it has, gives the same bits as before (LiveSimReplaceNetworkTests).
  • fault-series (one or two conductors open in a branch's series element) and fault-simultaneous (solid shunt faults at
    several buses at once): two verbs over the sequence networks fault --type uses, with --json and --csv. Core adds
    FaultAnalysis.SequencePorts and FaultAnalysis.SeriesBreak (the transfer impedances and the break Thevenin impedances;
    SeriesFault and SimultaneousFault are unchanged). Purely additive: the existing short-circuit, IEC 60909, sequence and
    dist3ph test classes give identical results before and after. Not offered: a shunt and a series fault together, and a break
    whose zero-sequence network is not earthed on both sides (an infinite zero-sequence impedance). Manual chapters 12 and 19.
  • dist3ph-mesh takes regulators (wye, open delta and closed delta, fixed taps or a line-drop-compensator tap search),
    banks (three-phase transformer banks) and capacitors (shunt banks, switched by a step's capacitors member), and a
    --hold-taps switch. A case without them is read and solved as before. Manual chapters 7 and 19.
  • substation-state reads a CGMES exchange (a .zip or a folder of EQ, TP, SSH and SV files) as a node-breaker model through
    Core's CgmesSubstationReader, with the SSH switch states as the starting states, and takes --base-mva for such an input.
    A .json input is read and projected as before. Manual chapter 19.
  • convert takes a CIM / CGMES input (a .xml document, a .zip exchange or a folder of profile files) through the importers
    the desktop app uses, and proves the conversion as for any input. Other inputs are unchanged. Manual chapter 19.
  • dist3ph-mesh --from-dist3ph <feeder.json> lifts a dist3ph feeder, transformers and regulators included, into the phase frame
    through Core's MultiPhaseFeederAdapter (--switch-z-pu gives a closed switch its impedance). Mesh case files and every other
    option are unchanged. Manual chapters 7 and 19.
  • dist3ph-mesh case files take split_phase_sources and centre_tap_transformers (Core's 120/240 V split-phase builders) and a
    swer member (a single-wire earth-return feeder, with its line given as an impedance or from conductor data). A case without
    them is read and solved as before. Manual chapters 7 and 19.
  • substation-state --sequence <steps.json> runs Core's SwitchingScenario (ordered open and close steps) from the starting state and
    reports every step. Without the flag the verb is unchanged. Manual chapter 19.
  • Network models: the 36 national and regional network models (GridSim-Models, ODbL 1.0, each labelled
    UnvalidatedAtScale) are linked as the optional models submodule. Fetch them with
    git submodule update --init models or clone with --recurse-submodules; open a case as
    gridsim pf models/<case>. They are not bundled data and are not in the release archives, so the licence bus limit
    applies: the eight cases above 1,500 buses need a licence (issued free of charge at present, on request).

Changed

  • BREAKING CHANGE: results and determinism digests are NOT bit-identical to 2.1.071 or 2.1.072. The difference is
    at rounding level: max |dVm| 9.7e-13 pu and max |dVa| 1.9e-11 deg on 66 MATPOWER cases (dynamic and EMT trajectories
    within about 2e-10 normwise), with identical convergence and iteration counts, and dense and sparse Newton remain
    bit-identical to each other. Any stored digests or bit-exact comparisons against those releases will fail and must be
    regenerated. Two numerical changes cause this: the sparse LU column ordering is now exact minimum degree
    (MinimumDegreeOrdering) instead of reverse Cuthill-McKee (one shared switch moves every LU user), and the Newton
    power flow voltage floor (NewtonShell.VmFloorPu) is lowered from 0.2 to 0.01 pu. This breaches the strict
    bit-for-bit contract but will not materially change your results; they remain at the floating-point rounding floor.
    The determinism digests and numeric pins in this repository were re-baselined accordingly.
  • case2848rte now converges (it has a bus at 0.0215 pu, below the old 0.2 floor).
  • BREAKING CHANGE: a Newton power flow (dense or sparse) that does not converge is now retried automatically, so the
    outcome of a solve that used to fail can change. The magnitude: every solve that converged before gives bit-identical
    results (the retry is never reached), checked on 15 MATPOWER and PGLib cases dense and sparse up to case9241pegase.
    The retry repeats the same Newton iteration with the same options and voltage magnitudes, starting the bus angles
    from the DC power flow; it needs one slack bus and a DC model that forms a single island. A converged retry is
    reported unless a branch carries more than 90 deg (net of any phase shift), which is not a usable operating point;
    otherwise the original non-converged result is reported unchanged. PowerFlowResult.NewtonRetry and
    NewtonRetryNote say whether the retry ran and how it ended, and pf and export print the note.
    case13659pegase now converges from flat start (10 iterations; it used to stop at a mismatch of 63.157 pu).
    The retry runs only when the failed solve stalled or diverged: its final mismatch is above 1e-3 of its mismatch at
    the start (NewtonShell.RetryStallFactor). A solve stopped by MaxIterations while still converging is not
    retried and is reported MaxIterations exactly as before, so the iteration cap is never exceeded by a second
    attempt. PowerFlowOptions.RetryFromDcStart (default true, also in the solverProfile kind and the script run
    record) turns the retry off.
  • Large sparse solves are 4 to 7 times faster, measured on an EPYC 7763 server (case_ACTIVSg2000 306 -> 46 ms,
    case3375wp 560 -> 83 ms). The cloud benchmark results for RC-3 and for this change are in
    docs/developer/benchmarks/server-results/hyperstack-2026-11/.
  • GPU paths are documented as deterministic run to run but not bit-identical to the CPU contract (different algorithms
    and reduction order), with the measured envelope; they are held to solver tolerance, not to the CPU cross-check gate.
    gpucheck now calls workstation NVIDIA parts (Quadro, RTX A-series, RTX Ada and RTX PRO) workstation GPUs in its FP64
    note instead of consumer GPUs.
  • Licensing text: GridSim is source-available and requires a licence; at present licences are issued free of charge,
    and a request receives a Network Operator (DNO) licence. The contact address in the licence, the documentation and
    every licence message is mark@gridsimdigitaltwin.co.uk.
  • Wording: program output, help and user-facing strings no longer claim that an engine, path or model is validated (the
    RMS footer, the experimental help and the experimental-models view say "checked against" or "standard").
  • emt3: an output name must be lower-case snake_case (it becomes a trace column and a summary key); any other name, and
    time_s, is refused as bad input (exit 1) naming the output, instead of failing after the run. Output kinds are
    hyphenated words. Output for valid documents is unchanged.
  • ProvenanceTag is unchanged; imports that follow public format descriptions carry the separate output-only
    ImportProvenanceTag.FormatFromPublicDescription.
  • The writer-verb registries (C# and Python) list the new verbs; existing entries are unchanged.
  • Machine-independent paths: the Unity viewer launcher (unity/GridSimViz/Launch-GridSimViz.ps1) takes the editor
    from -Editor or GRIDSIM_UNITY_EDITOR, its scratch folder from -Scratch, GRIDSIM_VIZ_SCRATCH or the system
    temporary folder, and an optional default world file from GRIDSIM_VIZ_WORLD; the benchmark chart scripts read
    their run folders from GRIDSIM_BENCH_ROOT (and GRIDSIM_BENCH_REHEARSAL_ROOT).
  • Tests: the intl/iberia row of the home phasor-card spread test was removed (it pinned a non-converged iterate); the
    Iberia network data still ships.
  • Tests: the Newton retry is covered on case9 (never entered on a converging solve; a retry that also fails; a case
    the retry cannot run on), on a stalled 8-bus chain (converging on the retry to the same root, dense and sparse
    bit-identical), on case9, case14 and case118 capped one step short of convergence (never retried, bit-identical to the
    retry switched off), on RetryFromDcStart = false, and on case13659pegase when its file is supplied
    (GRIDSIM_CASE13659PEGASE). The earlier case9 test that expected a 3-iteration cap to converge on the retry was
    replaced: it contradicted the iteration-cap test on identical inputs.
  • Documentation: benchmark results are reorganised under one landing page (docs/developer/benchmarks/index.md) with one folder
    per run and a dated history; the RC4 large-case results are added.

Removed

  • The Unity viewer (unity/GridSimViz, its launcher script and README) is no longer in the repository; it was never
    a release artefact. gridsim export still writes gridviz.json for any external visualiser.

Fixed

  • Workbench: opening a case applies the same licence and bus-limit check as the app and the command line.
  • Workbench: studies and Colour by result run off the UI thread, one at a time, and an error is shown in the status line
    instead of reaching the crash handler; a run always returns to the caller before it completes.
  • Workbench: after a single-line diagram edit the project is rebuilt on the edited network (studies kept, stale results
    cleared), so tables, studies, reports and the diagram describe the same network.
  • Web workbench: a private model the viewer may not open shows a NOT AVAILABLE card.
  • Web console: a LOAD CASE of a model the licence does not cover is reported as a refusal, not as an error, when a
    whole script is run (the typed console already did so).
  • substation-state goes through the licence gate like every other case-loading verb.
  • Builds are stamped from v2 release tags only, not from the RC-2 checkpoint tag.
  • On a GPU backend the GPU: line is printed after a non-convergence message, which keeps that message next to its exit
    code 3.
  • MATPOWER import: a generator row with PMIN above PMAX (as in the PGLib-OPF __api cases) loads as written with a
    warning note instead of refusing the whole case; a power flow does not use those OPF limits. QMIN above QMAX loads
    with a warning on an out-of-service unit and is still refused on an in-service one, whose reactive limits the power
    flow uses. Studies that use the active-power range refuse a crossed one themselves: DC-OPF, AC-OPF, corrective
    redispatch, unit commitment and the security and transfer studies as before, and now also the distributed slack
    and governor / inertia outage sharing in contingency screening.

Not in RC-4, by design: PSS/E v35 node-breaker records (incomplete), coupled harmonic power flow, harmonic state
estimation and the RoCoF filter (experimental), DNP3 and GOOSE, partitioned emt3 runs and grid-forming and
grid-following inverters (they need new numerics), PROTECTION FULL in scripting, web studies beyond POST /solve, and
any LLM integration.

Known limits: the new work is tested on small analytical, constructed and synthetic cases. Items that need paid standard
text are labelled AWAITING STANDARD TEXT, and DGS acceptance on real PowerFactory exports and the ENTSO-E conformity
bundle are awaiting files. No commercial-tool comparison has been made and no parity is claimed. Bugs to
mark@gridsimdigitaltwin.co.uk.