Connection

  • Routing: outgoing ROUTING_INDICATION frames of concurrent senders (TelegramQueue, Management) are serialized by the flow control so each one keeps the pause after the previously sent frame and the ROUTING_BUSY wait time, instead of being sent in a burst - KNX v01.01.02 - Communication Medium KNX IP 03.02.06 - §2.1.
  • Routing: the number of received ROUTING_BUSY frames N - used for the random wait time extension and the slowduration - counts every frame received more than 10 ms after the previous one, including the first one - KNX v01.05.02 - Routing 03.08.05 - §2.3.5. Before, the first frame was never counted.
  • Tunnelling / Device Management: send a CONNECTIONSTATE_REQUEST heartbeat every 30 seconds instead of every 70 seconds. KNX v01.06.02 - Core 03.08.02 - §5.4 asks for one every 60 seconds; ETS 6 sends one every 30 seconds, which halves the time until a dead connection is noticed. CONNECTION_ALIVE_TIME was removed from xknx.io.const.
  • IP Secure: send the SESSION_STATUS keepalive after 15 seconds of inactivity instead of 50 seconds, like ETS does, leaving a wide margin to the 60 second session timeout.
  • Routing: close the multicast socket when configuring or binding it fails instead of leaking it.
  • Accept unwrapped TunnellingRequest and DisconnectRequest frames in a KNX IP Secure session from servers that send them this way, until a wrapped TunnellingRequest is received. Since 4.0.0 they were discarded, so no telegram and no L_Data.con arrived from such servers. One warning per session is logged. All other unwrapped frames stay discarded. TunnellingRequests of another communication channel are dropped by every tunnel type.
  • Fix concurrent CEMIHandler.send_telegram() calls being confirmed by another request's L_Data.con. Only one L_Data.req is outstanding at a time now; the next request is sent once the previous one is confirmed or timed out - KNX v01.02.03 - Transport Layer 03.03.04 - §3.6. Previously, e.g. two P2PConnections to different devices or a broadcast next to a group write could return as confirmed before their own confirmation arrived.
  • Harden KNXnet/IP frame parsing: malformed DIBs, headers and bodies raise CouldNotParseKNXIP instead of hanging the event loop or closing the TCP connection. The TCP transport skips an unparsable frame by its total length and keeps processing the stream.
  • cEMI: empty or truncated frames raise CouldNotParseCEMI instead of IndexError.

Management

  • Add xknx.profile.PropertyDataType - KNX v01.04.01 - Standardized Identifier Tables 03.07.03 - §4.1 Table 6, the Property Datatypes of Interface Object Properties. Its size property gives the size in octets per element, or None where the PDT alone doesn't fix it. PropertyDescriptionResponse gets writable, pdt, read_level and write_level properties for the single fields of its type_ and access octets (KNX v02.01.01 - Application Layer 03.03.07 - §3.4.3.1), named like the fields of PropertyExtDescriptionResponse. type_ and access keep holding the whole octets. Together they tell the element size of a Property before reading it, e.g. whether a device's Group Object Association Table (PID_TABLE) holds 2 or 4 octets per entry.
  • Add connectionless point-to-point communication - KNX v01.02.03 - Transport Layer 03.03.04 - §1.5, telegrams sent as T_Data_Individual without a transport connection. async with xknx.management.connectionless(address) as connectionless: provides a P2PConnectionless with send(), receive() and request(), like Broadcast and BroadcastContext for one device. While it is open, the T_Data_Individual telegrams the device sends are handed to it - they were dropped as unhandled before, so a response to a connectionless request could not be received. receive(expected, timeout) yields every telegram of the device carrying expected until timeout elapses, for procedures that need more than the first response. request() returns the first telegram carrying the payload's RESPONSE_TYPE and skips any other, and raises ManagementConnectionTimeout if none arrives within timeout (keyword, default 6 seconds). Concurrent request() calls are sent one after the other, as nothing in a response tells which request it answers. A connection() to the same device may be open at the same time.

DPT

  • Add DPT 15.000 (DPTAccessData, value_type "access_data")
  • Add DPT 26.001 (DPTSceneInfo, value_type "scene_info")
  • Add DPT 27.001 (DPTCombinedInfoOnOff, value_type "combined_info_on_off")
  • Add DPT 217.001 (DPTVersion, value_type "version") with KNXVersion
  • Add DPT 222.100 (DPTRoomTemperatureSetpoints3, value_type "room_temperature_setpoints_3") and DPT 222.101 (DPTRoomTemperatureSetpointShifts3, value_type "room_temperature_setpoint_shifts_3")
  • Add DPT 225.001 (DPTScalingSpeed, value_type "scaling_speed") and DPT 225.002 (DPTScalingStepTime, value_type "scaling_step_time")
  • Add DPT 240.800 (DPTCombinedPosition, value_type "combined_position")
  • Add DPT 241.800 (DPTStatusSAB, value_type "status_sab")
  • Add DPT 21.001, 21.002, 21.100-21.106, 21.601, 21.1000-21.1002, 21.1010, 21.1200 and 21.1201 8-bit sets (DPTStatusGen, DPTDeviceControl, DPTForceSign, ...) - KNX v02.02.01 - Datapoint Types 03.07.02 - §3.22, §4.4, §6.4.1, §8.2, §9.6, §9.7.
  • Add DPT 22.100 DPTStatusDHWC, 22.101 DPTStatusRHCC, 22.1000 DPTMedia and 22.1010 DPTChannelActivation16 16-bit sets, 25.1000 DPTDoubleNibble and 30.1010 DPTChannelActivation24 - KNX v02.02.01 - Datapoint Types 03.07.02 - §4.5.1, §4.5.2, §8.3.1, §8.3.2, §8.4, §8.5.1.
  • Add DPT 206.100 DPTHVACModeNext, 206.102 DPTDHWModeNext, 206.104 DPTOccModeNext and 206.105 DPTBuildingModeNext with the new enums DHWMode (20.103), OccupancyMode (20.003) and BuildingMode (20.002) in xknx.dpt.dpt_20 - KNX v02.02.01 - Datapoint Types 03.07.02 - §4.12.
  • Add DPT 207.100 DPTStatusBUC, 207.101 DPTLockSign, 207.102 DPTValueDemBOC, 207.104 DPTActPosDemAbs, 207.105 DPTStatusAct and 207.600 DPTStatusLightingActuator - KNX v02.02.01 - Datapoint Types 03.07.02 - §4.13, §6.5.1.
  • Add DPT 219.001 DPTAlarmInfo, 229.001 DPTMeteringValue and 230.1000 DPTMBusAddress - KNX v02.02.01 - Datapoint Types 03.07.02 - §3.29, §3.45.1, §8.6. The enums they use are in xknx.dpt.dpt_20: Priority (20.004), ApplicationArea (20.006), ErrorClassSystem (20.011), ErrorClassHVAC (20.012) and MeteringDeviceType (20.114).
  • Add DPT 234.001 DPTLanguageCodeAlpha2ASCII, 234.002 DPTRegionCodeAlpha2ASCII, 236.001 DPTPrioritisedModeControl, 237.600 DPTDALIControlGearDiagnostic, 238.001 DPTSceneConfig and 238.600 DPTDALIDiagnostics - KNX v02.02.01 - Datapoint Types 03.07.02 - §3.47, §3.49, §6.7.1, §3.50.1, §6.8.1.
  • Add the DALI emergency converter DPTs 244.600 DPTConverterStatus, 245.600 DPTConverterTestResult, 246.600 DPTBatteryInfo, 247.600 DPTConverterTestInfo, 248.600 DPTConverterInfoFix and 272.600 DPTConverterInfo - KNX v02.02.01 - Datapoint Types 03.07.02 - §6.11-§6.15, §6.22.
  • Add DPT 255.001 DPTGeographicalLocation and the forecasts for 2-octet float values 273.001-273.007 (DPTForecastTemperature, DPTForecastWindSpeed, DPTForecastRelativeHumidity, DPTForecastAbsoluteHumidity, DPTForecastCO2, DPTForecastAirPollutants, DPTForecastSunIntensity) - KNX v02.02.01 - Datapoint Types 03.07.02 - §3.52.1, §10.1.
  • Add DPT 275.100 (DPTRoomTemperatureSetpoints4, value_type "room_temperature_setpoints_4") and DPT 275.101 (DPTRoomTemperatureSetpointShifts4, value_type "room_temperature_setpoint_shifts_4") - KNX v01.03.01 - HVAC S-Mode FBs 07.19.20 - §9.4. Their values RoomTemperatureSetpoints4 and RoomTemperatureSetpointShifts4 carry the comfort, standby, economy and building_protection setpoints in °C, or setpoint shifts in K, of the RTSM (Room Temperature Setpoint Manager) and related HVAC function blocks as float, or None for the invalid data value 0x7FFF.
  • Add DPT 5.100 (DPTFanStage, value_type "fan_stage") - KNX v01.03.01 - HVAC S-Mode FBs 07.19.20 - §9.5. A discrete fan stage 0...255, 0 is off.
  • Add DPT 20.107 (DPTChangeoverMode, value_type "changeover_mode") with the enum ChangeoverMode in xknx.dpt.dpt_20 - KNX v02.02.01 - Datapoint Types 03.07.02 - §4.3.
  • Add DPT 20.116 (DPTEnableHCStage, value_type "enable_hc_stage") with the enum EnableHCStage in xknx.dpt.dpt_20 - KNX v01.03.01 - HVAC S-Mode FBs 07.19.20 - §9.6.
  • Add DPT 21.107 (DPTCombinedStatusRTSM, value_type "combined_status_rtsm") - KNX v01.03.01 - HVAC S-Mode FBs 07.19.20 - §9.1. Its value CombinedStatusRTSM carries the window, presence, comfort push button, comfort prolongation User and HVAC Mode User status of an RTSM (Room Temperature Setpoint Manager). §9.1 makes it mandatory one year after publication, and disallows the "Eberle status octet" DPTHVACStatus from then on.
  • Add DPT 22.102 (DPTCombinedStatusHVA, value_type "combined_status_hva") - KNX v01.03.01 - HVAC S-Mode FBs 07.19.20 - §9.3. Its value CombinedStatusHVA carries the valve position, the short circuit and overload alarms and the valve kick, service mode, manual operation, forced position, locked position and calibration mode status of a heating/cooling valve actuator.
  • Add DPT 22.103 (DPTCombinedStatusRTC, value_type "combined_status_rtc") - KNX v01.03.01 - HVAC S-Mode FBs 07.19.20 - §9.2. Its value CombinedStatusRTC carries the fault, heat_cool_mode (HeatCool), dew point, frost and overheat alarm, controller inactive, additional stage and heating/cooling enabled status of an RTC (Room Temperature Controller). Like DPT 21.107 it becomes mandatory one year after publication and replaces DPTHVACStatus; DPT 22.101 DPTStatusRHCC becomes optional.

Devices

  • Add DeviceUpdate.from_state_address telling if the telegram causing a device update was sent to a state address of the device - a group_address_*_state or a passive address given with it, that isn't also used for writing. Such a telegram reports a state, eg. an actuators feedback, rather than commanding a change. Device.is_state_address() and RemoteValue.is_state_address() answer the same for any group address.
  • Add Cover.remaining_travel_time() (and TravelCalculator.remaining_travel_time()) returning the estimated seconds until the designated position is reached - 0 if not traveling.

Bugfixes

  • Cover: TravelCalculator no longer raises ZeroDivisionError for the position of a cover asked right after it stopped, before the clock advanced - e.g. within the 15.6 ms resolution of time.time() on Windows.
  • ValueReader (used by RemoteValue.read_state() and the StateUpdater): the response timeout starts when the GroupValueRead is actually sent instead of when it is queued, so reads waiting behind other outgoing telegrams no longer time out before reaching the bus ("Could not sync group address"). A GroupValueRead that can't be sent within 10 seconds is given up with a warning.
  • StateUpdater: a state update received while a read for the same RemoteValue is running no longer frees its parallel_reads slot before the read has finished.
  • Address parsing: GroupAddress and IndividualAddress raise CouldNotParseAddress instead of ValueError for strings of non-ASCII digits like "²" (which str.isdigit() accepts but int() rejects) and reject a trailing newline ("1/2/3\n"). The ValueError escaped GroupAddressDPT.set() and aborted the whole group address to DPT mapping.
  • DPTBase.parse_transcoder() no longer resolves strings like "TPD-9" or "PPP9" to DPT 9: only a leading "DPT" / "DPT-" prefix is removed, not any of its characters.

Internals

  • TaskRegistry: exceptions of Task targets and of background() tasks are logged with the task name instead of being noticed only as "Task exception was never retrieved" at garbage collection. background() tasks are cancelled on stop(). Tasks started after stop() - e.g. by device telegrams processed while XKNX is shutting down - are only registered and started on the next start(), instead of running unmanaged.
  • DPT lookups by number or value_type (DPTBase.transcoder_by_dpt(), transcoder_by_value_type(), parse_transcoder(), get_dpt()) use lazily built lookup tables per base class instead of walking all transcoder classes on every call - about 100 times faster, which matters when GroupAddressDPT.set() maps thousands of group addresses. The tables are rebuilt when a new DPTBase subclass is defined.
  • KNXIPFrame.from_knx() resolves the body class from a lookup table instead of a chain of comparisons.
  • IP Secure: the session keepalive is a rescheduled loop.call_later() timer instead of a task cancelled and recreated for every frame sent.