Releases · ahpohl/libfronius
v1.4.2
v1.4.1
fix: correct float encoding into a slave mapping packToModbus() wrote floats with modbus_set_float_abcd(), which stores the four raw wire bytes into the register array. modbus_reply() reads that array back as host-order uint16 values and serialises each one high byte first, so on a little-endian host every float left the server with its bytes swapped inside each word. Writing 6.25 produced tab_registers[40071] = 0xC840 where the wire needs 0x40C8. Every float register served was wrong, which is why a client decoding them saw values like 4.2e11 for a power factor. Route the bit pattern through packInteger<uint32_t>() instead. It already produces most-significant word first in host order, which is the convention the reply path and every other multi-register type in this function use, so the float case now matches its neighbours. Only the write side was affected. getModbusDouble() decodes floats from a buffer filled by modbus_read_registers(), a different convention, and reads real hardware correctly. Found by serving a float meter model and reading it back through this library's own Meter: the integer model round-tripped, the float model returned garbage.
v1.4.0
fix!: correct meter decoding, nameplate reads and TCP reconnection Collects the work since v1.3.6: four wire-format and lifecycle faults found against a Primo 4.0-1 and a Smart Meter TS 65A-3 sharing one RS485 bus, one breaking callback change, and the documentation and header hygiene needed for release. Meter, proprietary register map ------------------------------- REG::SN was declared with NB=1 while carrying a UINT32 payload, so the read fetched one register and the decode consumed two; the low word was never transferred. It was also the only 32-bit read in the map not passing word_swap, though the Carlo Gavazzi EM/ET300 protocol the map derives from stores every 32-bit value least-significant word first. A meter reporting [0x08EC, 0x05B1] decoded as 149684224 against a barcode reading 95488236. The firmware version register is not a numeric major component. The same protocol defines it as a letter index -- 0 is "A" -- paired with a decimal revision, so a meter reporting [1, 5] runs B5, not 1.5. Report the raw numeric pair when the code exceeds 'Z', since a device that far outside the documented encoding is better described by its register contents than by a wrong letter. VR_MAJOR and VR_MINOR become FWVER and FWREV to match: the old names asserted the numeric versioning this removes, and the underscore form reads as the scale-factor suffix used throughout the SunSpec models. REG::A claimed register 270 was the total AC current. It is the phase sequence: 0 for L1-L2-L3, 1 for L1-L3-L2. Nothing decoded it, so no reported value was ever wrong -- getAcCurrent() already refused Phase::TOTAL on this map -- but the declaration read like a limitation to lift rather than the absence of a register, and lifting it would have reported a rotation code as amperes. The map has no system current at all; say so in the namespace documentation and expose 270 as REG::PHSEQ. Inverter nameplate block ------------------------ validateNameplateRegisters() fetched only the two-register block header at 40121/40122, leaving the payload from DERTYP onwards untouched, and nothing else covers that range. Every getAcPowerRating() call therefore indexed a region of regs_ that no transaction had written; because regs_ is zero-filled, all four outputs returned a clean 0 rather than failing. Read header and payload in one transaction, as I160 already does. On a Primo 4.0-1 the block holds WRtg=400 sf=1 and VARtg=400 sf=1, i.e. 4000 W and 4000 VA, where the library previously reported 0. Bus reconnection and callbacks ------------------------------- Pulling the inverter's ethernet cable left the bridge stuck until it was restarted. The kernel holds a TCP connection open across a link-down, so no ECONNRESET or EPIPE arrives; the only signal is ETIMEDOUT, classified TRANSIENT, which never clears connected_ and so never re-enters the only phase that calls tryConnect(). The timed-out request also stayed outstanding, so the late reply answered the next request and every read after it was one frame behind. Escalate ETIMEDOUT to RECONNECT in executeTransaction() when the transport is TCP, and only there: tryConnect() sees the same code from an unanswered SYN, where it is a genuine transient that Phase 1 already retries. onBusConnect_ fired when the state became connected while onBusDisconnect_ fired when an attempt to restore it failed, so the names implied a pair the fire sites did not form. An outage recovering on its first attempt left no trace beyond an errno, and the bus offered no analogue of setDeviceRetryCallback() despite having exactly that behaviour. Split the two meanings: onBusDisconnect_ becomes void() and fires once from the Phase 2 exit, where connected_ actually changed; onBusRetry_ takes over the old signature and fire site. The delay stays off the disconnect callback deliberately -- naming one at drop time is a prediction, since the attempt has not run and may never wait at all. Headers and comments --------------------- modbus_utils.h used std::reverse without <algorithm> and Register without register_base.h, compiling only because every consumer happened to include both first; on its own, or through registers.h, it failed outright. Every public header now compiles standalone. Comments that grew during the shared-bus and reconnect debugging into records of how a conclusion was reached are shortened to the operative rule and its reason, and those restating the statement below them are dropped. Where a rule is stated in full on the public API the implementation now refers to it rather than repeating it. Also drop the "[--] guard done, queue free" trace, which has announced the completion of a guard that no longer runs at that point since 634d926, and correct two stale declarations: getFwVersion()'s documented return format, and cbMutex_ guarding four callback vectors rather than three. BREAKING CHANGE: addBusDisconnectCallback() takes std::function<void()> instead of std::function<void(int)> and fires on the transition rather than per failed attempt. Consumers wanting the old per-attempt delay must register addBusRetryCallback() instead. REG::VR_MAJOR and REG::VR_MINOR are renamed to REG::FWVER and REG::FWREV, and REG::A is removed in favour of REG::PHSEQ. Consumers persisting the meter serial number or firmware version must migrate stored values: both differ from every previously reported one. fix: read the meter serial number as a full 32-bit value REG::SN was declared with NB=1 while carrying a UINT32 payload, so the read fetched one register and the decode consumed two. The low word was never transferred and the zero-initialised buffer was used instead. The word order was wrong as well. Every 32-bit value in this map is stored least-significant word first -- the Carlo Gavazzi EM/ET300 protocol the map derives from states this explicitly -- but the serial was the only 32-bit read not passing word_swap. On a Smart Meter TS 65A-3 reporting registers [0x08EC, 0x05B1] the old code produced 149684224; the meter's barcode reads 95488236. Consumers persisting the serial number need to migrate stored values: the corrected result differs from every previously reported one. fix: format the meter firmware version as a Carlo Gavazzi code The version register is not a numeric major component. The Carlo Gavazzi EM/ET300 protocol this register map derives from defines it as a letter index -- 0 is "A", 1 is "B" -- paired with a decimal revision code, so a meter reporting [1, 5] runs firmware B5, not 1.5. Report the raw numeric pair when the version code exceeds 'Z', since a device that far outside the documented encoding is better described by its actual register contents than by a wrong letter. Rename VR_MAJOR and VR_MINOR to FWVER and FWREV to match: the old names asserted the numeric versioning this commit removes, and the underscore form reads as the scale-factor suffix used throughout the SunSpec models (A_SF, W_SF). Consumers persisting the firmware version will see the string change on the next device read. fix: reconnect a TCP bus when a read on an established socket times out Pulling the inverter's ethernet cable left the bridge stuck until it was restarted. The kernel holds a TCP connection open across a link-down, so no ECONNRESET or EPIPE ever arrives; the only signal is ETIMEDOUT, which deduceSeverity() classifies as TRANSIENT. TRANSIENT does not clear connected_, so busLoop() stayed in Phase 2 and never re-entered Phase 1 -- the only place that calls tryConnect(). The socket was never closed. Worse, the timed-out request stayed outstanding on it. Once the link returned, the inverter's late reply was read as the answer to the next request and every read after that was one frame behind, reported as EMBBADDATA. That is also TRANSIENT, so the device retried the same dead socket with growing backoff indefinitely. Escalate ETIMEDOUT to RECONNECT in executeTransaction() when the transport is TCP. The check sits there rather than in deduceSeverity() because the rule is narrower than "TCP": tryConnect() also sees ETIMEDOUT on TCP, from a connect() whose SYN went unanswered, and that is a genuine transient Phase 1 already retries with backoff. modbus_read_registers() is the only call in the library that can produce the code on an established transport, so keeping the rule at that one site makes the wrong classification unreachable from the wrong one, and leaves modbus_error.h transport-blind. EMBBADDATA is deliberately not escalated. It is set in check_confirmation(), which is transport-agnostic and reached as readily by RTU, where a mismatched frame is what an RS485 collision produces; libmodbus recovers from it with modbus_flush() under MODBUS_ERROR_RECOVERY_PROTOCOL and reserves modbus_connect() for link errors. Escalating it would apply link-class recovery to a protocol-class fault and, on a shared serial bus, drop every other device for one bad frame. It also cannot arise here once the timeout escalates, because the socket is closed before a desync can accumulate. Also corrects the deduceSeverity() comment, which asserted that a dropped peer follows ETIMEDOUT with ECONNRESET/EPIPE. That holds for a serial hangup, not for a TCP link-down. The missing "Inverter 'primo' disconnected, trying to reconnect in ..." line needs no separate fix. onBusDisconnect_ fires only from Phase 1 when tryConnect() fails, so it reappears once the bus actually reconnects. refactor!: make the bus callbacks mirror the device callbacks BREAKING CHANGE: addBusDisconnectCallback() takes std::function<void()> instead of std::function<void(int)> and fires on the transition rather than per failed attempt. Consumers wanting the old per-attempt delay must register addBusRetryCallback() instead. onBusConnect_ fired when the state became connected; onBusDisconnect_ fired when an attempt to restore it failed. The names implied a pair the fire sites did not form, and the asymmetry had two consequences. An outage that recovered on its first attempt reported nothing but an errno through onBusError_, conventionally logged at debug, so a brief drop left no trace. And the bus offered no analogue of setDeviceRetryCallback() even though it had exactly that behaviour, which made a bus retry and a device retry indistinguishable in a consumer's callback set despite meaning different things: the transport is gone, versus the transport is fine but this slave will not validate. Split the two meanings. onBusDisconnect_ becomes void() and fires once from the Phase 2 exit, where connected_ actually changed -- reached by a RECONNECT error from executeTransaction() and by triggerReconnect() alike. onBusRetry_ takes over the old signature and fire site. The bus now mirrors the device: a state pair, an error channel, a retry notice. The reconnect delay stays off the disconnect callback deliberately. Naming one at drop time would be a prediction -- the attempt has not run, and if it succeeds the wait never happens -- which was the objection in af4010b that kept onBusDisconnect_ out of this site in the first place. It applies to the delay, not to the notification, so a callback without one can fire here without reviving the double reporting af4010b removed. Shutdown does not fire onBusDisconnect_ even though it is a transition. Consumers log their own teardown, and firing then would race with the removeBusCallback() calls their destructors are making. fix: read the nameplate payload, not just its block header validateNameplateRegisters() fetched I120::ID.NB + I120::L.NB, which is the two-register block header at 40121/40122. It checked the model ID and the block length and returned, leaving the payload from DERTYP (40123) onwards untouched. Nothing else covers that range: fetchInverterRegisters() polls the active state code, the I10X/I11X inverter block and the I160 MPPT extension, and none of them reach I120. So every getAcPowerRating() call indexed a region of regs_ that no transaction had ever written. regs_ is resized to 0xFFFF and zero-filled, so all four outputs - WRtg, VARtg and both VArRtg quadrants - returned a clean 0 rather than failing, which is why this read as a plausible value instead of an error. Read the header and the payload in one transaction, matching what validateMultiMpptRegisters() already does for I160. The nameplate block is static, so the single read at validation time serves every later call. Verified against a Primo 4.0-1 on the integer map: registers 40124-40127 hold WRtg=400 sf=1 and VARtg=400 sf=1, i.e. 4000 W and 4000 VA, where the library previously reported 0 for both. fix: 270 is the phase sequence, not a total current REG::A claimed register 270 was the meter's total AC current. In the Carlo Gavazzi EM/ET300 map this driver's proprietary path derives from, 270 is the phase sequence: 0 for L1-L2-L3, 1 for L1-L3-L2. An mbpoll capture of a TS 65A-3 sub-meter confirms it, reading 0 while L1 drew 0.167 A and L2 drew 5.325 A. Nothing decoded it, so no reported value was ever wrong: getAcCurrent() already refused Phase::TOTAL on the proprietary map and returned before reaching the register. The declaration was still a trap - the guard reads like a limitation to lift rather than the absence of a register, and lifting it would have silently reported a rotation code as amperes. That map has no system current at all: three phase currents, a neutral current on some variants, nothing equivalent to M20X::A. Say so in the namespace documentation, and expose 270 as REG::PHSEQ, which is what it is. It sits inside the 16-register system block the driver already reads, so surfacing it later costs no bus traffic. getAcCurrent() keeps its guard and its structure; only the now-nameless proprietary argument changes, to a default Register. That argument is unreachable behind the guard, and were it ever reached it decodes to EINVAL rather than to whatever sits at the address. Verified against the capture: the phase-block base and 14-register stride, and A/W/VA/var/PF/V for L1 and L2 (V*I, sqrt(P^2+Q^2) and the VA register agree to 0.1 % on L2). Still unverified: 320-326, the tail of the L3 block, which read zero throughout because nothing was connected to L3, and 258-268, which fell outside the captured window. docs: trim implementation comments to release length Several comments grew during the shared-bus and reconnect debugging into multi-paragraph narratives that recorded how a conclusion was reached rather than what a reader needs to keep the code correct. Shorten them to the operative rule and its reason, and drop comments that only restate the statement below them. The load-bearing rationale is kept in every case: the ETIMEDOUT transport dependence, the RTU pre-send flush, the EPROTO-over-EINVAL severity choice, the no-join-under-mtx_ deadlock, and the RetryEntry lifetime invariant. Where a rule is already stated in full on the public API, the implementation now refers to it instead of repeating it, so the two cannot drift apart. Also fix two inaccuracies found while reading: cbMutex_ guards four callback vectors, not three, and drop the duplicated callback banner comment in fronius_bus.h. No functional change. docs: describe the meter firmware version as a Carlo Gavazzi code getFwVersion() has returned a letter-plus-revision code such as "B5" for the proprietary map since cd9e73d, but the declaration still promised "major.minor" format, e.g. "1.5". Correct the Doxygen comment to match. fix: make modbus_utils.h self-contained and drop a stale trace line modbus_utils.h used std::reverse without <algorithm> and Register without register_base.h. It compiled only because every consumer happened to include both first; including it on its own, or through registers.h, fails outright. Add the two includes. The "[--] guard done, queue free" trace dates from 469ce57, when a guard delay followed each transaction. 634d926 removed the post-failure sleep and moved the remaining guard ahead of the send, so the line now announces the completion of something that no longer happens there. The [tx]/[rx] pair already brackets the transaction. Remove it. The 500 ms slave-switch guard is left alone: 634d926 raised it from 100 ms deliberately, and it is the same on every branch. clang-format corrections
v1.3.6
build: ship a shlibs control file in the runtime package The runtime package registered no dependency information for the libfronius SONAME, so dpkg-shlibdeps in a downstream package aborted with "no dependency information found for libfronius.so.1" instead of emitting a Depends. Consumers had to either declare the dependency by hand or leave it out entirely, in which case the resulting package installed cleanly and then failed at exec with an unresolved SONAME. CPACK_DEBIAN_PACKAGE_GENERATE_SHLIBS has no per-component variant, but CPack resolves the package name per component before writing the file, so only the runtime package gains an entry -- the devel package carries just the dangling namelink, which is not an ELF object and is skipped. The default policy is an exact-version match, which would pin every consumer to the libfronius release it was built against and break the install on any upgrade. The SOVERSION already guards the ABI, so >= is the correct constraint. Generated entry: libfronius 1 libfronius1 (>= 1.3.5)
v1.3.5
fix: report a bus disconnect once per reconnect attempt Every outage produced two identical "reconnect in N seconds" reports a few milliseconds apart. busLoop() fired onBusDisconnect_ from the post-drain block when connected_ had been cleared, and Phase 1 fired it again with the same reconnectDelay as soon as its tryConnect() failed. An overnight inverter standby logged nine warnings for eight backoff steps. Drop the post-drain fire. The delay it carried was only a prediction -- the attempt it referred to had not run yet, and if that attempt succeeds the wait never happens -- whereas Phase 1 reports a wait it is about to perform. This also matches what addBusDisconnectCallback() already documents: fired when a connection attempt fails, carrying the seconds until the next one. The drop itself stays visible. Whatever cleared connected_ reported it through onBusError_, and notifyDevicesDisconnected() still runs, so the device-level unavailable callbacks fire and availability is published as before. The one behavioural change is that an outage recovering on the first reconnect attempt now produces no disconnect report, which the callback documentation now states.
v1.3.4
feat: add fronius.h and registers.h umbrella headers Consumers currently must include several individual headers to use the library, e.g.: #include <fronius/fronius_bus.h> #include <fronius/fronius_device.h> #include <fronius/inverter.h> #include <fronius/meter.h> #include <fronius/modbus_config.h> #include <fronius/modbus_error.h> Add two umbrella headers reflecting the two natural tiers of the public API: - fronius.h: the core object API (bus, device, inverter, meter, config, error, types) needed by consumers driving devices through the high-level Inverter/Meter interface. - registers.h: raw Modbus register access (SunSpec common block, per-device register maps, register_base, and the ModbusUtils pack/unpack helpers) needed by consumers that build a virtual Modbus TCP slave mapping or otherwise touch raw registers directly. Both are header-only and require no CMake changes, since headers are already installed flatly under include/fronius/ via the existing install(DIRECTORY include/ ...) rule. Verified with g++ -std=c++23 and a warning-free Doxygen run.
v1.3.3
fix: join the connect-notify thread instead of detaching it After a successful connect the bus thread spawned a detached thread to run notifyDevicesConnected() (onBusConnected() blocks on future.get(), so it cannot run on the bus thread). That thread locks mtx_ and schedules retries, but the destructor never waited for it: on a shutdown shortly after a connect it could lock mtx_ after ~FroniusBus had destroyed it, aborting with std::system_error "Invalid argument" from pthread_mutex_lock on a freed mutex. Track it as notifyConnectThread_ (a reconnect joins the previous one first) and join it in the destructor, after the bus thread and before retries_ is moved out. running_ is already false by then, so any scheduleDeviceRetry() it runs returns without queuing work and the join is immediate; retries it did schedule are still captured by the existing retries_ join.
v1.3.2
fix: flush the RTU receive buffer before each transaction A transient line glitch (a single bad-CRC frame) permanently wedged a shared RTU bus: every device on it went unavailable and never recovered, needing a restart. Observed at least daily on a two-slave bus. Once a corrupted or short frame leaves unread bytes in the serial input buffer, the bus desynchronises by one frame -- each read returns the previous request's reply, so every transaction fails "response not from requested slave" (or bad CRC on the partial frame). The trigger is TRANSIENT (a CRC/timeout/wrong-slave error is not FATAL, by design, so a USB-serial hiccup does not tear down the bus), which means the bus is never reconnected -- and reconnect was the only place modbus_flush() ran. Nothing drained the stale bytes, so the one-off glitch became permanent. Flush the input buffer before issuing each request on an RTU bus, so a transaction always starts from a clean buffer. The flush must precede the request, not follow a failed read: when a stale-frame read fails it returns instantly while the genuine reply is still in flight, so flushing afterwards only discards the current stale frame and lets the in-flight one become the next -- the lag survives. Flushing before the send drops the stale frame and lets the read block for this request's own reply, resynchronising on the next poll. On a healthy bus the buffer is already empty (a successful read consumes its frame exactly), so this discards nothing. TCP is unaffected and skipped.
v1.3.1
fix: classify transport hiccups (ENOENT/ENODEV/EBADF/EIO) as TRANSIENT These four errno values were previously FATAL, which on a shared RTU bus causes the bus thread to set connected_=false, fire onBusError_ callbacks with FATAL severity, and — via the application-layer shutdown hook that fronius-bridge registers on each bus error callback — terminate the whole process. On RTU these codes are the typical errno values seen when a USB-to- serial adapter momentarily disappears (device unplug, kernel re- enumeration, udev settle race, adapter firmware glitch). A simple reconnect almost always recovers, and busLoop()'s Phase 1 already implements that reconnect with exponential backoff. Classifying them as FATAL therefore takes down the entire bridge for a condition the bus is already designed to handle. A misconfigured RTU device path (e.g. typo in YAML) also surfaces as ENOENT, but TRANSIENT remains the right call there too: it produces a repeated, visible warning every backoff cycle rather than a silent startup exit during a boot-time enumeration race. This change is a prerequisite for the upcoming EBZ Easymeter integration in fronius-bridge, where the USB-IR dongle is known to glitch occasionally and must recover without taking down the rest of the bridge. The fix also benefits existing Fronius RTU users on shared buses.
v1.3.0
feat: added support for multiple inverters and meters