Repository navigation
Operator console
The DCS operator console is at http://localhost:8110/operator. It follows ISA-101 (high-performance HMI): grey by default, saturated colour only for alarms (priority 1 red, 2 amber, 3 violet, bad quality magenta). Process media get muted colours so you can tell lines apart: oxygen blue, nitrogen green.
Port Arden (http://localhost:8120/operator) and Vadhana (http://localhost:8130/operator) run the same console. Its header names the site, the consumer boxes and KPI tiles follow it, and the drawings are Haltenberg's: equipment a site doesn't have is drawn dashed, and its tags are left out. See Global sites.
The whole unit on one display (ISA-101 level 2). Click any value to open its faceplate, or click equipment to open its detail display.

Every data block shows the tag's value and a small bar: the tag's full range, darker zones beyond its alarm limits, the PV as a pointer and, for controllers, the SP as a hollow triangle.
Each unit has a detail display (level 3) with every stream and instrument of that unit:
| Display | Covers |
|---|---|
K-101 |
Intake filter, main air compressor, antisurge recycle, C-102 aftercooler |
R-201 |
Mole-sieve beds A/B, E-204 regeneration heater, KS-201 sequence panel |
K-102 |
Booster air compressor, its ratio to the pumped LOX (internal compression) |
E-301 |
Main heat exchanger: every stream's temperature at both ends; X-303 expander inlet / outlet temperature and pressure |
C-401 |
HP / LP columns, E-404 main condenser, P-501 LOX pump, boiling-point scale |
products |
GOX and GAN headers, consumers, K-503 GAN compressor, PIC-502 / PIC-504 split ranges |
T-505 |
LOX / LIN tanks, backup pumps P-505 / P-506, backup vaporizers E-507 / E-508 |
How to use them:
- Open one by clicking the equipment on the overview, from the Detail displays bar, or with a
direct link such as
/operator#detail/E-404(any equipment tag of a display works). - The arrows at the edge of a display are links: follow a stream from display to display.
- ◀ Back returns to the previous display (the browser's Back button works too). ✕ Close or Esc returns to the overview.
- Values, faceplates, alarms and trends behave exactly as on the overview.
The double column and main condenser, with a live boiling-point scale: measured column
temperatures against the boiling points at column pressure. The calculated tags TY-411
(N₂ condensing temperature at HP pressure), TY-412 (O₂ boiling temperature at LP pressure) and
TY-413 (N₂ boiling temperature at LP pressure) are historized and published over OPC UA like
every other tag.

The mole-sieve display shows both beds, the valve line-up commanded by the KS-201 sequence and the step progress.

The heat-exchanger display shows every stream through E-301 with its temperature at both ends, and the expander's inlet and outlet. The values come from one heat balance, so they agree with each other (details).

Every DCS tag with PV, SP, output and mode. The faceplate switches MAN/AUTO/CAS, changes setpoints and the SP ramp rate, and shows a 30-minute trend.

Each interlock with its causes and first-out, equipment start/stop with permissives, Normal line-up, ESD, and the KS-201 mole-sieve bed switching sequence. How to restart after a trip: Process behaviour.

Alarm summary with acknowledge, and the event journal (alarms, trips, sequence steps, operator actions) stored in the historian.

Up to 8 points, 15 min to 7 days. Here the PPU cycle is compressed to 5 min per bed: CO₂ at the PPU outlet, regeneration gas temperature, bed ΔP and valve stroke time over three bed switch-overs.

🎓 Training in the console header opens the trainers: 🎓 Process, ⚙️ Engineering and 🔌 IT/OT, as an overlay card on the live console. The Process trainer walks through the process step by step. It:
- Dims the overview except for one process step and numbers the steps ①–⑦.
- Shows a card with a plain-language explanation and what that step is doing right now, e.g. which bed is heating and to what temperature, or whether the vaporizer is helping out.
- Lists the tags worth watching; clicking one opens its faceplate.
- Has Go deeper buttons into the Engineering and IT/OT trainers, at the same unit.
Step with ◀ ▶ (or the arrow keys) or click a numbered circle; Esc closes it. The console never opens the card by itself. Like the rest of the console, it is built only from DCS data. It never reveals the instructor's hidden scenarios.

Every view can be opened directly, which is also how the screenshots are taken (headless Chrome):
| Link | Opens |
|---|---|
/operator#overview, #tags, #ilk, #alarms, #trends
|
a tab |
/operator#detail/C-401 |
a detail display |
/operator?tag=PIC-502 |
a faceplate |
/operator?training=1&step=2 |
the Process trainer at a step |
/operator?training=eng&topic=C-401&step=2 |
an Engineering or IT/OT topic at a step (Trainers) |
/operator?trend=AI-202.PV,TIC-204.PV&range=15 |
trend points and window (minutes) |
Start
Understand
Global DataOps
Use
- Trainers
- Operator console
- Instructor station
- Data access
- Browsing OPC UA
- Interface reference
- Configuration
Contribute