ardirec v0.2.0-alpha.13 — Calculation Parity Hotfix
Pre-release
Pre-release
·
315 commits
to main
since this release
alpha.13 is a calculation-parity hotfix driven by a side-by-side check against the SIGRA line1.CFG sample at the same trigger cursor.
What the audit proved:
- COMTRADE decoding/scaling was already sound: H1 RMS and H2/H3/H5 ratios matched the reference values.
- Phase-angle presentation used the wrong reference convention.
- Table Extremum used max-absolute-in-cycle instead of the last completed turning point.
- Compact DC was shown as absolute V/A while the reference table was configured for DC percent of H1.
- THD could be grossly inflated when a user requested harmonic orders above the record Nyquist limit.
Fixes:
- Phase is now sine-wave phase position at the cursor/reference instant for Table/Harmonics and the vector display.
- Harmonic requests are automatically clipped to the physically resolvable Nyquist order. A 1 kHz / 50 Hz record stops at H10, so aliased H11+ can no longer be double-counted in THD.
- Table uses Last extremum semantics: the latest completed local max/min before the cursor.
- Default Table DC presentation is percent of H1; signed absolute DC remains available in Detailed mode.
- Table exposes the sample rate and actual THD harmonic limit for auditability.
- Deterministic tests cover phase reference, Nyquist clipping, alias-safe THD and last-extreme selection.
Windows development distribution remains a portable ZIP folder. The executable is unsigned, so Windows SmartScreen may show a warning.