ARIEC60870 v3.6.13

Choose a tag to compare

@github-actions github-actions released this 17 Nov 02:16
289caef

ArSee v3.6.13 — Reliable IEC-101 Master and verifiable IEC-104 GI (Windows x64)

This document describes the v3.6.13 release candidate source contents, prepared 16 November 2026. It does not assert that v3.6.13 is already published or that any later binary passes acceptance. The latest published stable remains v3.6.12 until a successful tagged release completes.

IEC-101 single-link and redundant A/B Master

The reviewed standalone hardening PRs #219–#225 now use one bounded transaction and FCB/FCV authority per physical IEC-101 COM link, correlate observed secondary responses with the active request, handle delayed ambiguous FC11 responses, preserve ACD Class1/Class2 fairness, and recover real serial-port faults with independent A/B ownership and controlled backoff. No application-level mutating control is automatically replayed after a transport ambiguity.

The next stages #226, #227 and #228 harden SBO selection/execute source and command epochs, feedback-target identity, and the IEC-104 TCP connection association. GI is counted at application level only for a request-correlated positive ACTCON and matching ACTTERM on the same physical owner/association. A GI ACTTERM does not prove all configured IOAs were received. A command ACTCON or ACTTERM does not prove physical breaker operation.

The broad historic draft #145 remains unmerged; its entire branch was not rolled into this release.

Mapping, SOE and bounded memory

#229 makes read-only names consistent across online Values and re-opened portable .ariec captures, with a source-scoped CA-ambiguity check before allowing unique process IOA display aliases. The bundled mapping for FEEDER CB STATUS = CA105 / IOA16712689 / TI31 is available when the operator loads an appropriate Signal List. If two stations or other IOA identities conflict, the original CA/IOA/TI remains visible and the name is not guessed. This never changes command addresses, GI expected-point proof or original wire bytes.

Accepted IEC-101 spontaneous digital objects have their own cumulative counter. 60/500/2,000-event deterministic synthetic tests validate software accounting and bounded report retention, not physical RTU-generated events. Both single/A/B IEC-101 and IEC-104 now use the shared O(1) bounded evidence FIFO, with exact in-memory eviction counters and unchanged live event delivery.

#230 additionally prevents IEC-104 falsely terminating the GI receive burst or incrementing its GI counter from wrong-source/CA/OA/QOI, negative/TEST or pre-ACTCON responses. The lifecycle is evaluated only for accepted IEC-104 I-frames after an actual successful GI TX on the current connection, using the same tracker implementation as IEC-101.

Software acceptance and release delivery

Before publication, confirm the actual v3.6.13 tag/commit passes Windows Release (warnings-as-errors), all six xUnit suites and 19 protocol smoke tests, native real-WPF OBS-C 1,400-frame acceptance, CodeQL, repository hygiene, release-package executable check, official Windows installer/portable ZIP structure, SHA-256 checksums, SPDX SBOM and build provenance. A green PR is not a green release artifact.

The stable v3.6.13 Package workflow will refuse publication without a successful exact-commit native Windows independent updater FAT including genuine installed-old-release update-worker acceptance. This safeguard must not be bypassed. The real installed updater requires operator approval; the portable ZIP does not update itself. Windows builds remain unsigned.

FIELD FAT PENDING: No claim of complete 60/500/2,000 IEC-101 SOE acquisition at 1200 bps from an actual RTU/gateway until a separately implemented reference master confirms event-count parity on the same cable/adapter, using original RX/TX frames and independently generated RTU event totals; device FIFO overflow, physical USB COM recovery, A/B failover, real command feedback, multiple IEC-103 devices and multi-vendor IEC-104 TCP peers remain independently unqualified. The application is an engineering tester/analyzer, not a certified production SCADA master or IEC conformance test suite.

The website/README links deliberately continue to point at published v3.6.12 until v3.6.13 is actually published, then the public landing, download guide and checksums must be synchronized to the immutable new release assets.