ArSee v3.6.14 — IEC-101/104 engineering scaling and source-grounded Signal Mapping

Release candidate notes — not a statement of publication. This document is bound to the source version 3.6.14 in Directory.Build.props. Public links, actual tag/commit, installer SHA-256 and provenance must be filled from a successfully completed immutable Package workflow. Until then, the latest published stable remains v3.6.13.

1. Engineer-configurable analog scaling

  • IEC-101/104 measured values may be normalized (TI9/10/21/34), signed scaled (TI11/12/35), or IEEE-754 short float (TI13/14/36). The IEC type identifies encoding, not an RTU-specific engineering-unit factor.
  • Signal List provides mutually exclusive Factor and TwoPoint projections. Factor uses engineering = source × normalized-full-scale(if NVA) × scale × primary/secondary + offset. TwoPoint uses Y = Y0 + (X−X0) × (Y100−Y0)/(X100−X0), where X is the decoded source value (NVA in per-unit, SVA signed integer, IEEE float as sent).
  • Both negative and positive ranges are supported. Invalid/nonfinite endpoints or zero X span are refused. TwoPoint does not additionally multiply by Factor, CT/PT or NVA full-scale. Off-range values are extrapolated rather than silently clamped; never interpret extrapolation as RTU certification.
  • Original capture bytes, IEC quality, CA/IOA, timestamps, controls and GI evidence are preserved. The engineering projection appears in Values, Event Log and its history/CSV and Frame Trace when the exact point identity and trusted measurement are available.
  • TI13 P is identity when the upstream device already sends MW. TI11 Q requires the authorized gateway signed counts → MVar conversion. A raw observation such as 13641 must not appear as 13641 MVar merely because a unit field says MVar.

2. SCADA I/O list — 31 exact point names

Based on the operator-provided I/O LIST PENGUJIAN SCADA (31 rows, page 1) previously reconciled in #240, the bundled example uses BAY TYPE + TYPE + MNEMO + LAB (when present), preserving CA=105, original IOAs, IEC TI, command policy and feedback:

  • FEEDER TM P — IOA 790446, TI13; FEEDER TM Q — IOA 790447, TI11.
  • KOPEL TM P 1 / KOPEL TM Q 1 — IOA 790438/790439, TI13/TI11.
  • TRAFO TM P 2 / TRAFO TM Q 2 — IOA 790442/790443, TI13/TI11.
  • TRAFO SOGI TM POAQ — IOA 790449, TI9, source-documented real power setting (0/1000); X0=0, X100=1 NVA, Y0=0, Y100=1000 engineering.
  • Existing digital indication, remote command, and command-feedback identities remain source-aligned, with no guessed station alias for an unrelated CA or Type ID.

CT 2000/1 A and PT 500/0.1 kV from the I/O list provide a theoretical apparent-power nominal magnitude (~1732.05 MVA) but do not establish the RTU TI11 signed-count scaling to MVar. The bundled default deliberately labels those three uncalibrated reactive-power readings counts. The separate provisional scaling example is not a default or FAT-approved calibration.

3. Upgrade existing Signal Lists safely

Already-saved local user Signal Lists are never replaced by installation. For an older project mapping, open Signal List → Sync 31 I/O, check the preview of exact CA+IOA+TI matches, and confirm only if those points belong to the intended project. Save & Apply to a new JSON filename. This updates names and business metadata, replaces an uncalibrated legacy TI11 Q label MVar with counts, and applies the documented TI9 POAQ mapping only to legacy identity/unconfigured rows.

The action keeps custom Factor/TwoPoint calibration, command policies, feedback IOAs, station identity, communications, and other stations unchanged. The editor also now retains business type and optional engineering min/max metadata on save/duplicate. No user profile is silently migrated at startup.

To display actual MVar, have the approved RTU/gateway factor or two independent endpoint pairs and then enter them in the selected Q point. The software must not infer a usable calibration from one observed 1730 MVar reference.

4. Software release acceptance and boundaries

The source-milestone PRs #239, #240 and #241 have been merged. Their software regression work and the prior merge commit's exact-source CI/CodeQL/hygiene were green before preparing this version. These results are not qualification for a future v3.6.14 release binary.

A public stable release requires all gates from Release Packaging: exact-source Windows build, protocol and all xUnit suites, real-WPF acceptance of the packaged executable, independent genuine previous-release installed-updater FAT, immutable package verification, SHA-256 sums, SPDX SBOM and provenance. Physical RTU/SCADA signal scaling, serial 1200-bps 2,000-event SOE parity, and multi-vendor controls/GI tests remain separate field acceptance. The binaries are currently unsigned; nothing here claims IEC conformance certification.

Sources: engineering scaling guide, document-backed mapping analysis, and the immutable v3.6.13 stable release.