This candidate adds the explicit SCADA data-item/bay association received from the operator on 19 November to the already merged and tested PR #263, based on master@b13f47117762f8520e9bf8eefaf54b6daa222101. The older v3.6.17-rc.3 remains immutable. This is not a stable promotion or RTU field FAT certification.
Source-specific Q scaling now visible in the bundled 31-point Signal Map
The older scada.sdb photograph provided two Q engineering ranges but did not identify which bay used each. The later operator clarification resolves that gap for this particular reference:
| Operator's bay | SCADA data item | CA | IOA | IEC Type | Decoded IEC signed source | Engineering display range |
|---|---|---|---|---|---|---|
| Feeder | Q Diri Sendiri | 105 | 790447 | TI11 | SVA I16 −32768..32767 | −2078..+2078 MVar |
| Kopel — Lab SOGI 3 | Q Lab | 105 | 790439 | TI11 | SVA I16 −32768..32767 | −260..+260 MVar |
| Trafo — Lab SOGI 4 | Q Lab | 105 | 790443 | TI11 | SVA I16 −32768..32767 | −260..+260 MVar |
Each bundled reference Q now contains scalingMode=TwoPoint, all four endpoints, unit=MVar, and the corresponding engineering min/max. The same JSON is used for the Windows packaged seed and human-readable docs mirror. This is a source-reported engineering display map, not evidence that every field gateway's raw IEC SVA matches SCADA's internal raw domain. Compare with actual signed RX and independent SCADA measurement before accepting site calibration.
At raw signed X=0, the literal asymmetric −32768..32767 conversion yields approximately +0.0317 MVar Feeder and +0.00397 MVar Lab; the firmware does not silently clamp/alter the original source value or IEC QDS to report an attractive zero. Calibration must be checked at zero and both sign directions before approving.
Safe upgrade of an existing locally saved Signal Map
An installer does not overwrite a saved project JSON or silently remap its Q readings. Open Signal Map / Sync 31 I/O to preview matching CA=105 / exact IOA / TI11 rows; only a truly legacy, uncalibrated Factor identity row with no custom endpoints or min/max is eligible for its corresponding Feeder/Lab SOGI 3/4 Q TwoPoint reference. Any custom Factor or TwoPoint mapping, different station/Type, command config, point identity, feedback wiring, or raw record is preserved. Accept the preview and Save As a NEW JSON profile; that new copy must then be applied to the active monitoring session.
Manual per-signal SCADA reference range preview remains available with explicit confirmation, including a warning when choosing an alternative to the latest operator association; nothing is imposed on user-owned profiles.
Unchanged source semantics / continued RC.3 fixes
- POAQ inbound TI9 normalized feedback IOA790449 remains 0..1200 MW, and distinct POOP outbound TI48 setpoint command IOA70537 remains 0..1000 command metadata. No setpoint encoder changes, physical command TX or new command privileges.
- Original CA/IOA/TI, IEC ASDU raw HEX, QDS OV/IV, timestamps, GI/SBO and Event Log forensic evidence are unchanged.
- Unknown extra received IOAs such as 790349, 1790446, 1790447 continue to show unmapped exact physical identities, not guessed aliases.
- TI13 P source float identity and TI5/TI32 step-position family remain as before. Historical tap range −4..14 versus 1..19 requires separate station evidence and is not inferred here.
- Separate old documentation-only ±1732 all-bay nominal CT/PT hypothesis is marked superseded for this source; it must not be mistaken for an approved feeder or lab mapping.
Software qualification versus physical FAT
The source PR #263 passed Windows CI, 1,249 xUnit (0 failures), 19/19 protocol smoke, Signal Map real WPF acceptance, repository hygiene, dependency review, and CodeQL. This source-level qualification is not package certification. Before publishing the public release, the exact RC.4 package build must pass full xUnit, WPF packaged executable smoke, setup EXE, portable ZIP, SHA-256, SBOM and artifact attestation.
Physical IEC101/104 FAT on SICAM/other third-party devices, actual 1200-bps SOE completeness, Lab Q calibration at negative/zero/positive samples, and independent RTU-to-SCADA engineering reference are NOT TESTED by this report. Do not promote to stable or claim field approval based on synthetic tests alone.
Expected artifacts after a successful source-bound public workflow:
ARIEC60870-v3.6.17-rc.4-setup-win-x64.exeARIEC60870-v3.6.17-rc.4-win-x64.zipARIEC60870-v3.6.17-rc.4-sbom.spdx.jsonSHA256SUMS.txt
Earlier RC.3 package stays available without modification. Choose the portable ZIP first for isolated read-only evaluation.