ArSee v3.6.19 — reliable IEC-101 event evidence, operator UX and Windows upgrade

Windows x64 · stable release candidate, 21 November 2026. This document is release preparation, not proof of publication. A public release is valid only after exact-source Windows native updater/installer FAT, source CI, security and package provenance gates have passed and GitHub publishes the immutable tag v3.6.19 with its assets. It builds on published ArSee v3.6.18.

IEC-101: source-backed Class-1 pending indication in the Events COT column

The former buffer classifier first used an absolute RTU-to-PC clock difference and then required RTU event time to advance much faster than host RX time. Both were insufficient: a time-zone difference can cause permanent false positives, while a real 1200-bps Class-1 queue can drain at an ordinary event-time rate and be missed.

  • On a verified original IEC-101 FC10 Class-1 poll → matching FC8 secondary user-data response, ArSee reads the secondary ACD access-demand bit. ACD=1 makes that received event's COT display 3 · spontaneous (buffer); ACD=0 immediately removes the suffix for the new event.
  • Meaning: (buffer) is a compact operator Class-1 data still pending cue at that particular RTU response. IEC-101 does not provide a universal per-event FIFO-origin bit. Neither ACD=1 nor its transition to zero independently proves the generation age or persistent FIFO storage of any one event. ACD=0 is not a physical FIFO integrity/overflow certificate.
  • The original COT=3 is never rewritten, no new Delivery grid column is added, and each decision and its evidence basis are preserved with the individual event in the indexed history/exports. Multi-object ASDUs share one verified original physical response and do not fabricate additional independent polls.
  • Mismatched source/Link A–B, FC11 Class-2 replies, invalid frames and unproven TX/RX pairing cannot supply an IEC-101 Class-1 queue claim. Where exact ACD evidence is unavailable, analysis remains conservative and independent of absolute RTU/PC clock offsets. Actual master polling, FCB, serial RX/TX, control, GI and redundancy ownership have not been changed by the buffer-display fix.

Operator field observation (single real IEC-101 RTU, November 21): a screenshot of the current source build shows 777 retained events with 3 · spontaneous (buffer) for one series of FC10 responses, automatically returning to 3 · spontaneous on a subsequent response, with ordinary FC11 background measurements interleaved. No issues are indicated in that observed screenshot. This is useful single-device UI/communication evidence, not independently archived byte-for-byte ACD proof, a 2,000-event lossless soak or multi-vendor interoperability certification.

Connection-profile and cockpit corrections

  • Isolated IEC-101 address/field-width persistence from IEC-103 defaults so that switching protocols cannot silently replace a working IEC-101 2-octet Link/CA/COT and 3-octet IOA configuration. Uncertain migrated settings require operator verification before active communication; a 1-octet configuration remains legal where explicitly chosen.
  • Refined IEC-104 Connection Setup height and placement of advanced APCI controls to reduce unnecessary scrolling while retaining accessible detailed settings.
  • Removed intrusive Frame Details hover tooltips, reduced Connection Setup close-button size and improved restrained WPF panel geometry.
  • Improved healthy/degraded dual-link status presentation and source-qualified timeline facts without changing the underlying Class-1/Class-2 or active/standby logic.
  • Made command select/execute and feedback more readable and better distinguished proven protocol confirmations from physical breaker/IED action; commands remain operator-authorized and source-bound.

Windows installer and upgrades from v3.6.17/v3.6.18

  • Official release artifacts use ArSee-v3.6.19-setup-win-x64.exe, ArSee-v3.6.19-win-x64.zip, an SPDX SBOM, and SHA256SUMS.txt; public release provenance is generated by the packaging workflow.
  • An existing registered legacy program installation under %LOCALAPPDATA%\Programs\ARIEC60870 is moved to the canonical %LOCALAPPDATA%\Programs\ArSee using the verified previous Inno uninstaller and the direct official installer, with collision/missing-registration checks that fail closed rather than deleting unknown files.
  • Existing canonical ArSee installations continue to update in place. Existing custom installation paths are not silently moved. A legacy-folder installation cannot safely be relocated by the previous in-app update worker; run the new official setup directly, after closing active IEC sessions and saving captures.
  • This migration replaces old program binaries, but deliberately preserves the distinct user-owned %LOCALAPPDATA%\ARIEC60870 workspace containing signal lists, profiles, settings, evidence and updater records. Do not manually delete that folder or uninstall your previous installation before following the direct-upgrade procedure. The move is not a fully transactional binary rollback if power is lost during the brief uninstall→install interval.
  • The portable release is a self-contained Windows x64 .NET publish and does not require installing a separate .NET Desktop runtime in advance. Windows/COM drivers, permission policies and site-specific hardware prerequisites remain the operator's responsibility. No blanket claim is made that arbitrary missing third-party VC++ runtimes or serial drivers are installed automatically.

Integrity, verification and safe use

A release is not considered publicly shipped until its exact-source Windows build, xUnit/protocol smoke, WPF acceptance, CodeQL, repository hygiene, genuine installed previous-release updater FAT, v3.6.17→ArSee naming/migration FAT, package file/hash validation, SBOM and provenance pass on the release SHA. Check the real results on GitHub Actions and download only the named files from the resulting GitHub Release. Confirm SHA256 before running setup.

Not claimed: certified IEC 60870 interoperability/conformance; balanced-mode IEC-101; 1200-bps two-/four-channel passive hardware isolation; RTU FIFO fullness/age/overflow validation; independent 101/103/104 multi-vendor field FAT; genuine Windows DPI 125/150% physical-monitor FAT; or safe remote-control operation on energized switchgear. Perform commands and timing tests only on authorized, isolated equipment. Preserve raw RX evidence for any event-buffer dispute.