Repository navigation
v0.6.6
Date: 2026-10-21
Previous release: v0.6.5
Summary
Built on go-dnp3 v1.4.1. The simulated outstation (server start) no longer crashes on a malformed request, and it answers as the DNP Users Group's IED certification procedures require; go-dnp3 now runs those in CI.
Security
server startno longer crashes on a malformed READ: go-dnp3 v1.3.2 and earlier took the whole outstation process down on a READ of g70v5 (file transport) whose header carries indices but no objects. Any master that can reach aserver startcould send it. Fixed in go-dnp3 v1.4.0: such a request is answered with IIN2.2.
Changed
The simulated outstation follows go-dnp3 v1.4.x:
- An OPERATE after the select timeout is answered TIMEOUT, not NO_SELECT. A control it does not support (
NOT_SUPPORTED) also sets IIN2.2. A control whose request carries a status is refused with FORMAT_ERROR. - A read of a point type the model has no points of is answered with IIN2.1.
- Relative-time events carry an unsynchronized CTO (g51v2) until the time is synchronized.
- A variation without flags reports a point with abnormal flags in the variation with flags.
- The response that reports a broadcast to
confirmoroptionalasks for confirmation. - A READ sent while an unsolicited response waits for its confirmation is answered after it.
client against an outstation that answers NOT_SUPPORTED with IIN2.2 (go-dnp3 v1.4, opendnp3) reports the echoed statuses, as for any refused control: exit code 6, or 7 when other controls of a direct operate were executed. With go-dnp3 v1.4.0 it would have reported only the IIN error.
Docs
- FAQ: go-dnp3 is tested against dnp3-interop v0.5.1 and with the IED certification procedures (dnp3c).
- SECURITY: use 0.6.6 or later.
Upgrade notes
- No breaking changes in the command line or the JSON output.