Summary

Built on go-dnp3 v1.4.1. The simulated outstation (server start) no longer crashes on a malformed request, and it answers as the DNP Users Group's IED certification procedures require; go-dnp3 now runs those in CI.

Security

  • server start no longer crashes on a malformed READ: go-dnp3 v1.3.2 and earlier took the whole outstation process down on a READ of g70v5 (file transport) whose header carries indices but no objects. Any master that can reach a server start could send it. Fixed in go-dnp3 v1.4.0: such a request is answered with IIN2.2.

Changed

The simulated outstation follows go-dnp3 v1.4.x:

  • An OPERATE after the select timeout is answered TIMEOUT, not NO_SELECT. A control it does not support (NOT_SUPPORTED) also sets IIN2.2. A control whose request carries a status is refused with FORMAT_ERROR.
  • A read of a point type the model has no points of is answered with IIN2.1.
  • Relative-time events carry an unsynchronized CTO (g51v2) until the time is synchronized.
  • A variation without flags reports a point with abnormal flags in the variation with flags.
  • The response that reports a broadcast to confirm or optional asks for confirmation.
  • A READ sent while an unsolicited response waits for its confirmation is answered after it.

client against an outstation that answers NOT_SUPPORTED with IIN2.2 (go-dnp3 v1.4, opendnp3) reports the echoed statuses, as for any refused control: exit code 6, or 7 when other controls of a direct operate were executed. With go-dnp3 v1.4.0 it would have reported only the IIN error.

Docs

  • FAQ: go-dnp3 is tested against dnp3-interop v0.5.1 and with the IED certification procedures (dnp3c).
  • SECURITY: use 0.6.6 or later.

Upgrade notes

  • No breaking changes in the command line or the JSON output.