Summary
Container contract 1.3: KNX IP Secure sessions over UDP, the servers'
secure routing, and Calimero tools' Data Secure through go-knx as the
surrogate.
Additions
--udpwith--securein the goknx and calimero-tools adapters (xknx:
unsupported, its secure sessions are TCP only);server --secure --routingin the goknx and calimero-server adapters.- The test profile: go-knx's routing source 15.15.255 is a device with a
tool key, the only sender of the new Data Secure group 1/3/3; Calimero
tools' tool key for 15.15.240. - The
securesuite: secure sessions over UDP (connect, write, read);
each server's secure routing in from secure routers (seen through a
secure tunnel) and out to them (from a secure tunnel); Calimero tools
write Data Secure over secure routing through the surrogate. - calimero-server 3.0-M1 secure routing: the adapter sets the latency
tolerance and opensio.calimero.knxnetipto the server module (the
official image fails with an IllegalAccessException otherwise). - Known differences narrowed: Calimero tools' Data Secure through a tunnel
(no surrogate there) and towards xknx alone (xknx is no surrogate). - The goknx adapter builds knxctl v0.4.0 by default.