Repository navigation
Device profiles
A profile describes one device type in YAML. Two are bundled, and both are invented:
| Profile | Device type | PV | SV |
|---|---|---|---|
pressure |
0xFA01 |
pressure, kPa, sensor limits -100 to 2500, range 0 to 1000 | sensor temperature, degC |
temperature |
0xFA02 |
temperature, degC, sensor limits -200 to 850, range 0 to 150 | terminal temperature, degC |
There are no profiles after real products, because most device-specific HART commands are not public. Their
manufacturer ID 0x00FA deliberately belongs to nobody.
Any key other than profile, polling_address and device_id overrides the profile:
devices:
- {profile: pressure, polling_address: 1, device_id: 0x000001, tag: PT-101}
- profile: pressure
polling_address: 2
device_id: 0x000002
tag: PT-102
long_tag: "Tank 2 level"
alarm: lowWith alarm: low, a failed sensor drives the loop to 3.6 mA instead of 21 mA.
Duplicate tags, polling addresses and device IDs are refused, and the error names the entry.
Save it next to the bench file and use profile: flow.yaml:
kind: flow-transmitter
manufacturer_id: 0x00FA
device_type: 0xFA03
device_revision: 1
tag: FT-301
long_tag: "Line 3 flow"
descriptor: "SIM FLOW"
min_span: 1
alarm: high
pv:
unit: bar
sensor_limits: [0, 40]
range: [0, 25]
damping: 0.5
source:
- {type: constant, value: 10}
- {type: sine, offset: 0, amplitude: 2, period: 30}
- {type: noise, sigma: 0.05}
sv: {name: body temperature, unit: degC, source: {type: constant, value: 23.5}}A source may be one entry or a list, whose values are added up:
| Type | Parameters |
|---|---|
constant |
value |
ramp |
start, stop, period
|
sine |
offset, amplitude, period
|
noise |
sigma |
The units are inH2O psi bar mbar kPa degC degF K mA %. There is no flow unit, so this example measures a
differential pressure in bar.
The PV maps from the range (lower to upper range value) to 4-20 mA. Outside that, the current saturates at 3.8 and 20.5 mA. A failed sensor gives the alarm current. Command 40 fixes the current, and command 6 sets the 4 mA of multidrop mode.
To test a specific value, set it from outside. auto hands it back to the source:
hart-sim set PT-101 pv 123.4
hart-sim set PT-101 pv autoThe value still passes through the damping of the profile, 0.5 s on the bundled devices, so it does not arrive
at once. Use damping: 0 if a test reads it straight away.
Next: Testing in CI.