Network

ziogianni92 edited this page Oct 4, 2026 · 2 revisions

This page explains how the application finds the nodes on the CANopen network, reads who they are, follows their NMT state and notices when one stops sending its heartbeat, and how the NMT commands are sent, confirmed and checked.

Source files:

How a node is found

A node becomes known in three ways (FR-NET-01):

Way Frame When
boot-up 0x700 + ID, data 00 the node has just started or been reset
heartbeat 0x700 + ID, data = NMT state every period of 0x1017, if the node produces it
scan answer on 0x580 + ID to an SDO request the user presses Scan

Nodes are not found from their PDOs or EMCY messages. canopen's own NodeScanner does that, but a PDO can be moved to any COB-ID, and a TPDO configured on 0x1AA would make a "node 42" appear even if node 42 does not exist.

Passive listening starts as soon as the connection opens: nodes that send a heartbeat appear by themselves within one period. The scan is a gesture of the user, never automatic: it sends 127 requests, which on a production network should be a choice.

The scan

sequenceDiagram
    participant User
    participant Panel as NodePanel
    participant Ctrl as NetworkController
    participant Reg as NodeRegistry (worker)
    participant Bus as CAN bus

    User->>Panel: Scan
    Panel->>Ctrl: scan_requested
    Ctrl->>Reg: scan() in the worker
    loop Node-ID 1..127
        Reg->>Bus: 0x600+ID  40 00 10 00 (read 0x1000)
    end
    Bus-->>Reg: 0x580+ID answers (any answer, even an abort)
    Note over Reg: waits scan_window():<br/>1 s, longer on slow buses
    loop every node not identified yet
        Reg->>Bus: read 0x1008, 0x1018:01..04, 0x1017
        Bus-->>Reg: values or aborts
    end
    Reg-->>Ctrl: done
    Ctrl-->>Panel: nodes_changed, scan_running(False)
Loading
  • Any answer counts, an SDO abort too: a node that has no object 0x1000 still exists.
  • The waiting time is 1 s, or twice the time needed to send 127 requests and 127 answers at the current bitrate (about 6 s at 10 kbit/s).
  • The requests go through RecordingNetwork.send_message(), so they appear as sent frames in the bus monitor and in the bus load (Data flow).

Identity

read_identity(node_id) reads, one SDO upload each:

Object Field of NodeInfo
0x1008 Manufacturer device name name
0x1018:01..04 Identity vendor_id, product_code, revision, serial
0x1017 Producer heartbeat time heartbeat_ms

An object that cannot be read (abort, timeout) stays None, and the reason is added to identity_error (for example 0x1008:00 abort 0x06020000). The node stays in the list in any case: the Smart IMU of today has no 0x1008 and shows as "Node without name". After the identity is read the node is recognised and gets the EDS of its product (EDS and products).

The identity is read once per node. It is read again after a boot-up message, because a node that restarted may have new settings.

States of a node

The NMT state comes from the heartbeat byte (bit 7, the toggle bit of node guarding, is ignored):

Byte NmtState LED Text
0x00 BOOTUP yellow Boot-up
0x04 STOPPED grey Stopped
0x05 OPERATIONAL teal Operational
0x7F PRE_OPERATIONAL yellow Pre-operational
none yet UNKNOWN grey State unknown (found by the scan, no heartbeat seen)
stateDiagram-v2
    [*] --> Unknown: answers the scan
    [*] --> BootUp: boot-up message
    [*] --> Operational: heartbeat
    BootUp --> PreOperational: heartbeat 0x7F
    PreOperational --> Operational: NMT Start
    Operational --> PreOperational: NMT Enter pre-operational
    Operational --> Stopped: NMT Stop
    Stopped --> Operational: NMT Start
    Operational --> BootUp: NMT Reset node or communication
    state "Heartbeat missing" as Missing
    Operational --> Missing: no heartbeat for 1.5 x period
    Missing --> Operational: heartbeat again
Loading

The names of the NMT states are the same in Italian and English, as in the CANopen documentation.

Heartbeat alarm (FR-NET-05)

check_heartbeats() runs four times a second (NetworkController, 250 ms). A node is in alarm when no heartbeat arrived for more than 1.5 times the expected period:

  1. the expected period is 0x1017 when it was read;
  2. if 0x1017 could not be read, the period observed between the last two heartbeats;
  3. if 0x1017 is 0, the node produces no heartbeat: no alarm, and the row says "heartbeat off";
  4. if nothing is known (a node found by the scan with 0x1017 unreadable and no heartbeat), no alarm.

The time is counted from the last heartbeat, or from when the node was found if no heartbeat has arrived yet. Each change (alarm on, alarm off) is reported once: the row turns red with "Heartbeat missing for 3.2 s", and the status bar shows "Node 29: heartbeat missing", then "Node 29: heartbeat back". The color is never the only signal.

The 1.5 factor leaves room for the jitter of a busy bus and of the operating system without hiding a node that really stopped: with the default 1000 ms, the alarm comes 1.5 s after the last heartbeat, plus at most 250 ms.

NMT commands (FR-NET-04)

An NMT command is one frame on COB-ID 0x000 with two bytes: the command specifier and the Node-ID (0 = every node). send_nmt() in src/rumia_configurator/core/network/nmt.py sends it through RecordingNetwork, so it appears as a sent frame in the bus monitor.

Command Byte Expected after it Per node Whole network
Start 0x01 Operational no confirmation confirmation
Stop 0x02 Stopped no confirmation not offered
Pre-operational 0x80 Pre-operational no confirmation confirmation
Reset node 0x81 boot-up confirmation confirmation (Reset button)
Reset communication 0x82 boot-up confirmation not offered

Where the user finds them:

  • the NMT button in the header of the selected node (Workspace.nmt_button) and the right click on a row of the panel open the same NmtMenu (src/rumia_configurator/gui/views/nmt_menu.py); the entries that ask for confirmation end with "…";
  • the Start, Pre-op and Reset buttons at the bottom of the panel send to the whole network.

Why some commands ask first

A command to the whole network reaches every node, also the ones the application does not list (a node without heartbeat that was never scanned, a device of another vendor). Start makes machines move, Pre-operational stops the PDOs a PLC may depend on, and a reset makes nodes restart and lose the settings not stored with 0x1010. For one node, Start, Stop and Pre-operational are the normal tools of commissioning and do not ask; the resets do, because they lose settings. The texts of the confirmations say what will happen, what it causes and what to check first (Recipes).

Checking the effect (NFR-REL-03)

NMT has no answer. After sending, NodeRegistry.verify_nmt() watches the heartbeats, in the same one-thread worker as the scan:

Outcome Meaning
CONFIRMED a heartbeat with the expected state arrived after the command; for a reset, a boot-up message
NOT_CONFIRMED heartbeats arrived, but in another state
NO_HEARTBEAT nothing arrived in time
NOT_VERIFIABLE the node produces no heartbeat (0x1017 = 0)

Each node gets 2 times its heartbeat period, at least 1 s and at most 10 s. For a command to the whole network the nodes in the list are checked. The result goes to the status bar ("Node 29: Stop confirmed by the heartbeat", "Whole network: Pre-operational confirmed by 2 of 2 nodes"); if a node did not confirm, a warning callout under the node header says what happened, why it can happen and what to do.

The registry uses time.perf_counter() as its clock: on Windows time.monotonic() advances in steps of about 16 ms, and a boot-up arriving right after the command got the same time as the command itself.

Model and view

NodeRegistry (core, no Qt)            NetworkController (gui)          NodePanel (gui)
  callbacks in the receive thread  ->   4 Hz timer: check_heartbeats,  -> NodeRow per node
  scan / read_identity (worker)         snapshot -> nodes_changed         node_selected
  snapshot(): list[NodeInfo]            one-thread pool for SDO           Scan button
  • NodeRegistry keeps one record per node under a lock. Heartbeat and SDO answers arrive in the python-can receive thread; scan() and read_identity() are blocking. snapshot() returns frozen NodeInfo copies, with silent_for computed at that moment. A new registry is created at every connection; close() unsubscribes everything.
  • NetworkController creates the registry when the connection opens and closes it when it ends. Its QThreadPool has one thread: the scan and the identity reads are SDO transactions, and two transactions on the same node at the same time would mix their answers. Nodes found by heartbeat get their identity read automatically in that same thread.
  • NodePanel shows one NodeRow per node, updated in place: Node-ID in mono, name (elided, full name in the tooltip), StatusLed with the state written out, and the heartbeat period. A row is selected with a click, Enter or Space; Up and Down move the selection. The selected node is shown in the header of the work area by Workspace.set_node().

Tests

  • tests/test_node_registry.py: scan and identity, passive discovery, NMT state, heartbeat alarm on and off, heartbeat off, node without 0x1008, no nodes from PDOs, identity read again after boot-up, scan frames recorded, scan window.
  • tests/test_nmt.py: NMT frames, Start, Stop, Pre-operational and both resets confirmed by the heartbeat, whole network, silent node, heartbeat off, node that ignores the command, commands recorded as sent.
  • tests/test_nmt_gui.py: buttons enabled only when connected; a cancelled reset sends nothing; confirmed commands are sent and checked; Stop from the node menu asks nothing, a reset asks first; warning when a node does not confirm; the dialog defaults to Cancel.
  • tests/test_node_panel.py (acceptance of T1.4): in demo mode the scan shows both nodes with their state; when a simulated node stops its heartbeat its row turns red and the status bar says so; selection by mouse and keyboard; the panel empties on disconnection and fits in 272 px.

The simulated nodes can stop and resume their heartbeat with stop_heartbeat() and resume_heartbeat() (Simulator and demo mode).