Migration
Up to 1.x the integration opened its connection to the controller itself, with
its own reconnect logic and block planner. Since 2.0 it asks Home Assistant's
modbus integration for a unit on the connection to the controller's
address. Home Assistant keeps one connection per endpoint and serialises
everything that goes over it, so two entries of this integration, or another
integration asking for the same endpoint, queue up behind one link. A hub from
the YAML modbus: configuration is not part of that: it opens a client of
its own. The wire is handled by the
modbus-connection
library, which Home Assistant installs with its modbus integration.
Upgrading: update Home Assistant to 2026.9.0 or later first, then install 2.0 or later and restart. Existing entries migrate on first start; an entry keeps the host and port you configured. If the controller does not answer during setup, Home Assistant retries.
- The entities, their unique IDs and history - except the web-interface entities of 1.x, which the migration removes together with the stored web-interface login (their empty devices go too since 2.1.2, also from an entry migrated before), and except where the recorder notices below say otherwise. Coming from the upstream 2.0 pre-release, the migration also removes its web-interface login and the heat pump's MAC address from the entry (since 2.1.2).
- The entity IDs you chose. One exception: an ID of the three relabelled
second-heat-source counters that ends in the old label, such as
..._switching_cycles_e_heating_2, takes the new label - also when you chose it, unless another entity already holds that ID; then it keeps the old one and the log says so. - The shipped power map you selected. A power map of your own has to be compiled once (see How Data Updates); until then the heating power reads unknown.
The web-interface scraping of 1.x with its settings, this integration's own
pymodbus requirement, the pygal requirement (the preview picture is drawn
by the compile script, not at runtime), its reconnect and back-off logic, and
the five-register block limit: the controller serves each address band in one
read.
A switch beside every setpoint the controller can switch off, the Options dialog (poll interval, EEPROM write warning and limit) and the write counters. Apart from the three relabelled second-heat-source counters, nothing existing is renamed. Prefix and device postfix can no longer be changed after setup.
An automation that matched on an old one needs the new name; Home Assistant raises no notice for them.
| Register | Value | Was (1.x) | Is |
|---|---|---|---|
| Operating status (30006) | 0 (undefined) | system_operationmode_pvmode |
system_operationmode_undefined |
| Operating status (30006) | 10 (utility lock) | system_operationmode_sgtariff |
system_operationmode_evu |
| Operating status (30006) | 37, 39 (heating, hot water in SG-Ready mode) |
..._heating_sgr, ..._hotwater_sgr
|
..._heating_sgr3, ..._hotwater_sgr3
|
| Heat pump operation (33101) | 0 (undefined) | heatpump_operationmode_pvmode |
heatpump_operationmode_undefined |
| Heat pump operation (33101) | 36 | heatpump_operationmode_bereitschaft |
heatpump_operationmode_regenerativ |
| Heat pump operation (33101) | 37, 39 |
..._heating_sgr, ..._hotwater_sgr
|
..._heating_sgr3, ..._hotwater_sgr3
|
The 1.x names are those of the fork point. The codes follow Weishaupt's 2025 data-point list, where 0 is "undefined", 10 the utility lock and 36 "regenerative".
The recorder raises a notice once per sensor whose statistics changed; open Developer tools → Statistics to settle each:
- A changed unit on the three relabelled second-heat-source counters (hours and cycles had swapped names) and on a few unit-less rows (an empty unit became none): choose to update the unit of the recorded statistics - the history is the register's and stays.
- A changed unit on H1.2 to H1.5: they read °C now, as the data-point list says. 1.x recorded their raw register words - tenths of a degree, and 32768 without a sensor - so delete their old statistics instead; with the unit updated they would read ten times too high.
- A removed state class on the seven "... yesterday" energy sensors: a yesterday's value is no growing total, so they keep no long-term statistics any more. Delete their old statistics; the matching "... today" sensors keep them.
From 2.0.0 or 2.0.1 to 2.0.2 or later
-
SG-Ready 1 and 2 (35101, 35102) showed their input as a number, 0 or 1;
they now read off and on, states
w2_status_ausandw2_status_ein. Their long-term statistics end there; the recorder notes this once per sensor. - Settings the controller only reports, and registers without a known meaning, moved to the Diagnostic category; they no longer appear on automatically generated dashboards.
- A power map of your own compiled before 2.0.2 carries its file name in the picture's title; compile it again if that name should not be public.
From 2.0.2 to 2.1
-
Reported setpoints (room, flow and hot-water setpoint) read 0 °C while
the controller demands nothing; 2.0.2 showed unknown. An automation that
waited for
unknownshould look at thedemandattribute instead (see How Data Updates). - Heating circuits are compared with the controller's setup at every load, with a repair notice where they differ (see Installation and Setup).
- Devices of heating circuits switched off in the entry are removed when the entry loads. Switched on again, the circuit comes back with its names, entity IDs and history.
- The integration is named "Weishaupt Modbus" everywhere, and some display names changed (English "Error" and "Hydraulic separator temperature", several Dutch names). Entity IDs stay as they are.
- Operating hours and switching cycles of the second heat source are totals since 2.1.0b3; up to 2.1.0b2 they were averaged. That older statistic stays in the database, but graphs no longer show it. In the first minutes after the update Home Assistant may list a mean type changed notice for them; it goes by itself with the next statistics run - do not delete the statistics for it.
- A counter reading 0x8000 or 0xFFFF, a percentage from 101 up, and a performance factor below 5 kWh of electricity read unknown (see How Data Updates).
- The write counters are kept with the entry, no longer in their sensors. 2.1.0 took over the counts the sensors held, but the way it read them fails on Home Assistant 2026.11; updating straight to 2.1.1 or later, they start over at 0.
From a 2.1 beta with the web interface (2.1.0b1 to 2.1.0b3)
- From 2.1.0b1 or 2.1.0b2 straight to 2.1.1 or later, the write counters start over at 0, as they do coming from 2.0.2.
-
The heating power limit of the web interface was a sensor until 2.1.0b2
and is a number now. The entry removes the sensor from the registry when it
loads; automations that read
sensor.…heating_power_limitmove to the number. Its history stays in the recorder: Developer tools → Statistics lists its long-term statistics as having no state and offers to delete them. - The web interface pauses instead of stopping after three failures in a row and resumes by itself; its repair notice is a warning now (see Web Interface).
Weishaupt Modbus
- Home
- Installation and Setup
- Entities
- How Data Updates
- Web Interface
- Troubleshooting and Diagnostics
- Migration