Weishaupt Heat Pump – Modbus TCP Register Reference

Consolidated from the official data-point list 83807301 (1/2025-11), the manufacturer xlsx (2022), and the weishaupt_modbus Home Assistant integration — live-verified on a WBB unit (July and September 2026: full-range scan 30000-49999, block-width probes, menu ranges).

Disclaimer — community reference, no guarantee. Rows marked ⚠️ are not in the official documentation (found via the integration or register scans; live-checked but unofficial). Writing to registers can change how the heat pump operates and the controller EEPROM has a limited number of write cycles — use at your own risk.


Connection & Conventions

Parameter Value
TCP port / Slave ID 502 / 1 (all devices use the same ID; distinguished by IP)
Addressing literal: doc address 30001 = protocol address 30001 (no ±1 offset). Depending on your Modbus software, ±1 may be required.
Function codes 3xxxx → FC4 (input, read) · 4xxxx → FC3 (holding, read) / FC6 (write)
Block read data-point list: max. 5 registers; live: any width inside an address band, see Address bands
⚠️ EEPROM Write limit 100,000 accesses over lifetime → write setpoints rarely!
⚠️ Operating status Internal operating states can override Modbus commands → read status (30006 / 33101) regularly.

Data Formats & Special Values

Format Type Value range / encoding
Temperature signed short −500…5000 = −50.0…500.0 °C (÷10)
Percent / humidity unsigned short 0…100 % · 0xFFFF (65535) = no value
Setpoint signed short −32768 = no setpoint demand active · 1 = same · 50…5000 = 5.0…500.0 °C (2025 list). For the writable setpoints with an "off" (41109–41112, 42105) 0x8000 is a settable state: the controller's menu offers Aus beside the value
Heating curve unsigned short 0 = OFF · 5…150 = 0.05…1.50 (÷100)
Flow rate unsigned short ÷100 → m³/h
Energy unsigned short 0…65535 kWh (16-bit, overflows!)
Digital unsigned short 0 = OFF · 1 = ON · 2…65535 = undefined
Operating hours / counter unsigned short 0…65535 h

Sensor special values (temperature / sensor format)

Re-evaluate on each poll — these are not permanent states.

signed unsigned / hex Meaning
−32768 32768 · 0x8000 no sensor installed
−32767 32769 · 0x8001 sensor open circuit (faulty)
−32766 32770 · 0x8002 sensor short circuit
−32758 32778 · 0x800A sensor digital status OFF
−32757 32779 · 0x800B sensor digital status ON

System

Address Name FC Access Format Value range / encoding
30001 Outdoor temperature 1 4 R Temperature −50.0…500.0 °C (÷10)
30002 Outdoor temperature 2 (air intake) 4 R Temperature −50.0…500.0 °C
30003 Error 4 R Error code N = error code · 65535 = no error
30004 Warning 4 R Error code N = warning code · 65535 = no warning
30005 Error-free 4 R Status 0 = error active · 1 = fault-free operation
30006 Operating status display 4 R Status 0…43 → code table below
40001 System operating mode 3 R/W Selection 0=AUTO · 1=HEATING · 2=COOLING · 3=SUMMER · 4=STANDBY · 5=2nd heat gen. · 0 and 2 only with cooling enabled (data-point list 2025; WBB manual ch. 6.7.2, cooling release in the heating circuit), 5 only with a second heat source set up. Without the release the controller acknowledges a 0 (counts as a write) but keeps the previous mode (live)
40002 SollwertPV (PV power setpoint) 3 R/W PV unsigned 0…65535 W; 0 = function off. Not stored in EEPROM, so no write limit. Documented in data-point list ch. 3.2 / 4.3

Heating Circuit 1

HC2–4: same registers with offset +100 / +200 / +300 (data-point list). HC5 (+400) ⚠️ comes from the integration only; on the WBB tested the band answers the "not served" exception.

Address Name FC Access Format Value range / encoding
31101 Room setpoint temperature 4 R Setpoint −32768 / 1 = no demand · 50…5000 = 5.0…500.0 °C
31102 Room temperature 4 R Temperature −50…500 °C · 0x8000 = no room sensor
31103 Room humidity 4 R Percent 0…100 % · 0xFFFF = no value
31104 Flow setpoint temperature 4 R Setpoint −32768 / 1 = no demand · 50…5000 = 5.0…500.0 °C
31105 Flow temperature (heating) 4 R Temperature −50…500 °C
31106 Operating mode (copy) ⚠️ 4 R Status undocumented · copy of 41103 (0=AUTO · 1=COMFORT · 2=NORMAL · 3=LOWERING seen); followed every mode change in the same poll, read 0 in AUTO with a time program fixed at comfort, so not the effective level. Room unit, holiday program, lock input untested
41101 Heating configuration 3 R Status 0=OFF · 1=PUMP CIRCUIT · 2=MIXED CIRCUIT · 3=SETPOINT (pump M1)
41102 Demand type ⚠️ 3 R/W Selection 0=OFF · 1=weather-compensated · 2=room-guided · 3=constant. Live-verified on WSB8 and WBB20 (upstream #126); the menu offers room-guided only with a room unit. The 2022 xlsx (2=constant) is wrong; not in the 2025 list
41103 Operating mode 3 R/W Selection 0=AUTO · 1=COMFORT · 2=NORMAL · 3=SETBACK · 4=STANDBY
41104 Pause / Party 3 R/W Selection 1…24 = pause 12.0…0.5 h · 25 = off · 26…49 = party 0.5…12.0 h
41105 Room setpoint Comfort 3 R/W Temperature 16…28 °C (step 0.5)
41106 Room setpoint Normal 3 R/W Temperature 16…28 °C
41107 Room setpoint Setback 3 R/W Temperature 16…28 °C
41108 Heating curve 3 R/W Curve 0 = OFF (setpoint shutdown) · 5…150 = 0.05…1.50
41109 Summer/winter switchover 3 R/W Temperature 3.0…30.0 °C · 32768 = no summer shutdown
41110 Heating constant temperature 3 R/W Setpoint 7…66 °C (controller menu; further clamped by the circuit's own min/max flow settings, which have no register; 2022 xlsx said 20…45) · 0x8000 = off (live)
41111 Heating constant temp. setback 3 R/W Setpoint 7…66 °C (like 41110) · 0x8000 = off (live: off)
41112 Cooling constant temperature 3 R/W Setpoint 7…30 °C (controller menu; setback 18.5…29.5, cooling min/max 7…30) · 0x8000 = off

Domestic Hot Water (DHW)

Address Name FC Access Format Value range / encoding
32101 DHW setpoint temperature 4 R Setpoint the DHW setpoint in force right now (e.g. normal or setback), not the flow setpoint the heat pump runs during a DHW charge – that one has no register (only the local web interface shows it, Info › Wärmepumpe › "Solltemperatur"). −32768 / 1 = no demand · 50…5000 = 5.0…500.0 °C
32102 DHW temperature 4 R Temperature −50…500 °C
42101 DHW configuration 3 R Status 0 = OFF · 1 = diverter valve · 8 = pump
42102 DHW push 3 R/W Selection 0 = OFF · 5…240 min
42103 DHW Normal 3 R/W Setpoint 20 °C … DHW maximum temperature (a menu setting without register, itself 20…80 °C)
42104 DHW Setback 3 R/W Setpoint 10 °C … DHW Normal
42105 SG-Ready boost 3 R/W Setpoint 0…30 °C · 0x8000 = off (settable; live: off)

Heat Pump

Address Name FC Access Format Value range / encoding
33101 Operation 4 R Status 0…43 → code table below
33102 Fault message 4 R Status 0 = fault · 1 = fault-free
33103 Power demand 4 R Percent 0…100 %
33104 Flow temperature 4 R Temperature −50…500 °C · sensor B4, the condenser flow sensor (manual WBB 12…20, ch. 6.7.1.2), right at the heat pump's outlet. Live in 0.5 K steps
33105 Return temperature 4 R Temperature −50…500 °C · sensor B9 (manual). Live in 0.5 K steps. Spread over the heat pump = 33104 − 33105
33106 Evaporation temperature ⚠️ 4 R Temperature undocumented; plausible live
33107 Compressor suction gas temp. ⚠️ 4 R Temperature undocumented; plausible live
33108 Hydraulic separator 4 R Temperature −50…500 °C (2025 official)
33109 Regenerative (flow demand) 4 R Temperature −50…500 °C (2025 official)
33110 Buffer 4 R Temperature −50…500 °C (2025 official)
33111 Common flow (B7) 4 R Temperature −50…500 °C (2025 official) · the manual's outlet flow sensor (B7), the heating circuit's flow temperature. 0.1 K steps, but refreshed by the controller only every ~3 minutes (live, October 2026): against the continuously refreshed return, B7 − 33105 goes negative while starting and double-digit after a stop. Equal to 33104 at rest
33126 Electrical power consumption ⚠️ 4 R Number, W 0…65535 W, 0 at standstill; documented nowhere. Checked against an external meter on a WBB 12 (heating, up to 1 kW): tracks it with r = 0.97, about 80 W below — the circulation pump and the controller are not included. Older firmware may not serve it (unconfirmed). evcc reads it the same way.
43101 Configuration 3 R Status config code (live 4)
43102 Quiet mode 3 R Selection code (live 0)
43103 Pump start mode 3 R Selection code (live 1)
43104 Pump power heating 3 R Percent 0…100 %
43105 Pump power cooling 3 R Percent 0…100 %
43106 Pump power DHW 3 R Percent 0…100 %
43107 Pump power defrost 3 R Percent 0…100 %
43108 Flow rate heating 3 R Flow rate ÷100 → m³/h (live 1.68). The indoor unit's flow sensor is B10 per the manual; whether 43108–43110 carry its actual value or a setting is open. The local web interface shows the actual value (0.0 at rest, 1.7 m³/h during a DHW charge)
43109 Flow rate cooling 3 R Flow rate ÷100 → m³/h
43110 Flow rate DHW 3 R Flow rate ÷100 → m³/h

⚠️ The table above is a WBB's, live-verified (43104–43107 = pump powers, 43108–43110 = flow rates). The manufacturer docs (2022) list 43101 twice (Configuration and Quiet mode) and end the block at 43109, one register shorter.

⚠️ Shorter block on a WSB 8 (WWP-CPU COM V5.2): 43110 is refused, and the pump powers sit one register lower, as in the manufacturer docs. This integration reads the block as a whole, so on such a controller all of 43101–43110 should go unavailable; older versions read each register and showed the wrong value, for example 253 % as the defrost pump power. Display and web interface fit heating, cooling and DHW there, though two equal values leave the roles to the docs; defrost and the flow rates are from the docs only, and which models have this layout is not known.

Register WBB (table above) Manufacturer docs 2022, seen on a WSB 8
43102 Quiet mode Pump start mode or Quiet mode (the docs disagree)
43103 Pump start mode Pump power heating
43104 Pump power heating Pump power cooling
43105 Pump power cooling Pump power DHW
43106 Pump power DHW Pump power defrost
43107 Pump power defrost Flow rate heating
43108 Flow rate heating Flow rate cooling
43109 Flow rate cooling Flow rate DHW
43110 Flow rate DHW not there (Illegal Data Address)

ℹ️ 43102–43110 are holding registers, but the weishaupt_modbus integration exposes them read-only (NUMBER_RO).


2nd Heat Generator

Address Name FC Access Format Value range / encoding
34101 Status 2nd heat gen. 4 R Digital 0 = OFF · 1 = ON
34102 Operating hours 2nd heat gen. 4 R Counter 0…65535 h
34103 Switching cycles 2nd heat gen. 4 R Counter 0…65535 (old docs; no longer listed in the 2025 list)
34104 Status electric heater 1 4 R Digital 0 = OFF · 1 = ON
34105 Status electric heater 2 4 R Digital 0 = OFF · 1 = ON
34106 Operating hours electric heater 1 4 R Counter 0…65535 h
34107 Operating hours electric heater 2 4 R Counter 0…65535 h
44101 W2 configuration 3 R Status config code · 255 = not present (live)
44102 Configuration EP1 ⚠️ 3 R Status config code (live 5); not listed in docs
44103 Configuration EP2 ⚠️ 3 R Status config code (live 6); not listed in docs
44104 Limit temperature 3 R/W Temperature −20…40 °C · 0x8000 if inactive
44105 Bivalence temperature 3 R/W Temperature −20…40 °C (live −20.0)
44106 Bivalence temperature DHW 3 R/W Temperature −20…40 °C (live −20.0)

⚠️ The manufacturer docs (2022) list limit/bivalence temperature at 44102–44104 — they are actually at 44104–44106 (EP1/EP2 config in between; live-verified).


Inputs

Address Name FC Access Format Value range / encoding
35101 SG-Ready 1 4 R Digital 0 = OFF · 1 = ON · 2…65535 = undefined (live 0, config 45101 = 1)
35102 SG-Ready 2 ⚠️ 4 R Digital Documented inconsistently: the 2025 list gives Format FormatDigital but the value column says "counter 0…65535 h", a text otherwise used only for FormatBetriebsstunden rows (34102, 34106, 34107). Most likely a copy error and 0 = OFF · 1 = ON like SG-Ready 1. Live 0 (config 45102 = 2), so undecidable here
35103 Input H1.2 4 R Sensor temp −500…5000 = −50.0…500.0 °C · −32768 no sensor · −32767 open · −32766 short · −32758 / −32757 = digital OFF / ON when the input carries a contact. Live 0x800A (= −32758, digital OFF) with config 45103 = 3
35104 Input H1.3 4 R Sensor like H1.2. Live 0x8000 (no sensor), config 45104 = 4
35105 Input H1.4 4 R Sensor like H1.2. Live 0 with config 45105 = 3 - the same config code as H1.2, which reports the digital special value instead; meaning of 0 here unknown
35106 Input H1.5 4 R Sensor like H1.2. Live 0x8000 (no sensor), config 45106 = 4
35107 Input DE1 ⚠️ 4 R Digital same documented inconsistency as 35102 (Format Digital, value text "counter 0…65535 h"); most likely 0 = OFF · 1 = ON. Live 0, function off (45107 = 0xFFFF)
35108 Input DE2 ⚠️ 4 R Digital as DE1. Live 0, function off (45108 = 0xFFFF)
45101–45108 Configuration SGR1 · SGR2 · H1.2 · H1.3 · H1.4 · H1.5 · DE1 · DE2 3 R Status the currently set function of the input, as a code. Checked live (October 2026): DE1 switched in the portal from off to utility lock → 45107 went from 0xFFFF to 1 at once, and back to 0xFFFF when reset. Codes – the values of the local web interface's selection lists, matching SGR1 = 1, SGR2 = 2 and the DE1 test: 0 = SG Ready (SGR1 only) · 1 = utility lock (EVU-Sperre) · 2 = elevated operation · 3 = heating-circuit lock · 4 = heat/cool switchover · 5 = quiet mode · 6 = emergency off · 7 = system standby · 8 / 9 / 10 = generator lock HC / DHW / HC and DHW · 11–14 = DHW standby / setback / normal / push · 15 = dew-point guard · 16–19 = heating circuit 1 standby / setback / normal / comfort · 33 = 2nd heat source · 34 = compressor lock · 35 = power limitation + lock (SGR1 only) · 36 = power limitation · 0xFFFF = off (no function). Live 1/2/3/4/3/4/0xFFFF/0xFFFF (SGR1 switched to utility lock, factory default SG Ready). ⚠️ H1 terminals unresolved: the web interface and the portal offer only "input H1.3", set to heating-circuit lock (3). Modbus reads 45103 = 3 (with 35103 = digital status OFF) and 45104 = 4. Either 45103/35103 belong to terminal H1.3, or the H1 registers encode something else. Every function comes with a contact type (normally open / closed); SG Ready occupies SGR1 and SGR2 as a pair

ℹ️ The weishaupt_modbus integration still names H1.2–H1.5 (35103–35106) Ausgang (output) - the name carries the entity's unique id and cannot change; the data-point list calls them inputs (Eingang), multifunction terminals.


Statistics

All FC4, R, unsigned 0…65535 kWh. Suffix: x1 = today · x2 = yesterday · x3 = month · x4 = year.

Base Group Notes
36101–36104 Total energy kWh
36201–36204 Heating energy kWh
36301–36304 DHW energy kWh
36401–36404 Cooling energy kWh
36501–36504 Defrost energy ⚠️ kWh · undocumented, responds live
36601–36604 Total energy II ⚠️ kWh · undocumented, responds live
36701–36704 Electrical energy ⚠️ kWh · undocumented — useful for COP/SPF
36801 unknown ⚠️ responds (live 0); meaning unclear

⚠️ Year registers (x4) read 0 on every controller seen - a WBB in service for years (display and portal show 6705 kWh) and the Evoblock WEB scan in upstream #193. A full-range scan found the yearly total in no other register. Treat 36x04 as not served; the yearly total exists on the display, in the WEM portal and in the local web interface only (Info › Statistik, three decimals).

ℹ️ Total energy II (366xx) equalled Total energy (361xx) on the WBB with defrost energy at 0 - possibly total including defrost; unconfirmed. Yesterday (x2) values change once a day and can fall: not a rising meter.


Address bands (live, September 2026)

The controller serves its registers in contiguous bands. A block read of any width inside a band answers normally (12 registers tested); a block that crosses a band end - or an address in no band - answers a malformed exception frame whose code equals 2 x count. So the "max. 5" of the data-point list is a guideline for building automation, not a controller limit. A band the controller does not have (heating circuit 5 on the WBB, a second heat generator on many units) answers the same exception for the whole band.

Space Bands
Input 30001-30006 · 31101-31106 (+100 per circuit, 2-5) · 32101-32102 · 33101-33111 · 33126 · 34101-34107 · 35101-35108 · 36101-36104 … 36701-36704 · 36801
Holding 40001-40002 · 41101-41112 (+100 per circuit, 2-5) · 42101-42105 · 43101-43110 · 44101-44103 · 44104-44106 · 45101-45108

Note the split between 44103 and 44104: one block over 44101-44106 is refused. The band list is checked in the integration's tests against the addresses of the data-point list (tests/documented_registers.json).


Operating Status Display — Codes 0…43

For registers 30006 & 33101 (per 2025 docs).

Code Meaning Code Meaning
0 undefined (the integration ≤1.x showed "PV Mode") 22 switchover heat/cool
1 relay test 23 cooling operation
2 emergency stop 24 passive cooling
3 diagnostics 25 summer operation
4 manual operation 26 swimming pool
5 manual operation heating 27 holiday
6 manual operation cooling 28 screed drying
7 manual defrost 29 locked
8 defrost 30 lockout (outdoor temp)
9 2nd heat gen. 31 lockout (summer)
10 utility lockout 32 lockout (winter)
11 SG tariff 33 operating limit
12 SG maximum 34 heating-circuit lockout
13 tariff charging 35 standby / ready ¹
14 boosted operation 36 regenerative ²
15 idle time 37 SGR3 heating ²
16 standby operation 38 SGR3 cooling ²
17 flushing operation 39 SGR3 DHW ²
18 frost protection 40 SGR4 heating ²
19 heating operation 41 SGR4 cooling ²
20 DHW operation 42 SGR4 DHW ²
21 anti-legionella 43 oil return ²
44…65535 undefined

¹ Older docs / the integration call code 35 "Setback" — the 2025 docs say "STANDBY / READY". ² New in data-point list 1/2025-11.


Legend & Sources

Legend: R = read only · R/W = read/write (FC6) · ⚠️ = not in official docs (integration / scan; live-checked, unofficial). Temperatures are signed short ÷10.

Sources:

  • Weishaupt data-point list Modbus TCP (WWP), doc. no. 83807301, 1/2025-11 (applies to WAB / WBB / WSB / WGB; the Evoblock WEB 7/10 serves the same register set per the scan in upstream #193)
  • Controller menu and WEM portal of a WBB (setting ranges, September 2026); Weishaupt WBB 12-20 manual 83315301
  • Upstream issue #126 (41102 code mapping, WSB8/WBB20)
  • Manufacturer xlsx (2022)
  • OStrama/weishaupt_modbus integration
  • Own live verification on a WBB unit (July 2026; September 2026: full-range scan, block widths, bands)