Combs that reach the bottom terminals.

Use it

New since 0.8.0

  • Four bottom combs in the bundled library, one for each top comb: 3-phase, 3-phase + N, 1-phase and L+N, 12 units wide and resizable. They are drawn along the bottom edge of the modules and feed their bottom terminals. The library is version 11; the four top combs are unchanged, so projects that use them still open.
  • The README explains that the pattern of a comb repeats once per unit, so the comb to choose is the one whose period is the width of the modules under it (3-phase for 3-pole modules of 3 units, 3-phase + N for 4-pole modules of 4); a comb of the wrong period joins different phases and Check reports it.

Limits

  • A comb has to be dragged from the library onto the rail by hand; there is no command that puts one under a selection.
  • A bottom comb that feeds nothing is not an error, but Check advises that the inputs of the modules under it are not fed.
  • Touch was tried in an emulated touch screen of Chromium, not on a phone with Safari or Android.
  • Wire lengths are estimates from where terminals stand on the panel; the conductor diameters for the duct fill and its 50 % limit are typical values and are not verified.
  • The cable ampacity table was compared with IEC 60364-5-52:2009 (copper, PVC, methods B1, B2, C and E, 1.5 to 35 mm2). Resistivity, reactance, voltage drop limits and trip multiples are not verified; the checks are advice, not a design verification.
  • This is a planning layout, not a manufacturing drawing.
  • File and library formats may still change without migration.