ArIEC103 is a free and open-source Windows desktop IEC 60870-5-103 / IEC-103 active master tester and analyzer for protection relay communication checks, FAT/SAT evidence, commissioning support, and troubleshooting review.
It connects to one IEC-103 slave relay, runs a controlled master session, decodes relay responses, keeps raw TX/RX frame evidence available, and presents the result as readable engineering output for protection, SCADA, panel FAT, site acceptance, and substation automation teams.
No license key. No subscription. No account required. Released under the Apache-2.0 license.
ArIEC103 is designed for engineers who need to answer practical IEC-103 questions quickly:
- Is the relay answering on the selected COM port, baudrate, parity, and link address?
- Does General Interrogation start and finish cleanly?
- Are Class 1 events requested only when the relay indicates pending event data?
- What value/status did the relay send, and what was the relay timestamp?
- Can the test evidence be exported for FAT/SAT notes, troubleshooting review, or handover?
The tool does not hide the protocol behind a black box. It shows readable evidence first, while keeping raw FUN/INF/Type/COT/DPI/frame details available when deeper investigation is needed.
Get the latest Windows portable package from GitHub Releases:
Typical release assets:
ArIEC103-vX.Y.Z-win-x64-portable.zip
SHA256SUMS.txt
First run:
- Extract the portable ZIP to a local folder.
- Run
Start-ArIEC103.bat. - Open Setup.
- Select COM port, baudrate, link address, common address, timeout, GI option, and optional mapping profile.
- Click Start.
- Review Operator Evidence, Value Viewer, Relay Event Log, Frame Trace, and Diagnostics.
- Export evidence after the test session.
| Operator evidence | Setup overlay |
|---|---|
![]() |
![]() |
| Value and event review | Protocol visibility |
|---|---|
![]() |
![]() |
- IEC 60870-5-103 relay communication check during panel FAT or bench testing.
- IEC-103 master polling verification for Class 1 event data and Class 2 background data.
- Protection relay event log review with relay timestamp basis visible.
- SCADA protocol troubleshooting when a relay does not respond as expected.
- User-owned signal mapping review using project JSON profiles.
- Evidence export for FAT/SAT notes, troubleshooting records, or engineering handover.
- Windows desktop IEC-103 active master tester.
- CLI tools for active master runs, offline trace analysis, and simulator checks.
- Sample mapping profile.
- Sanitized IEC-103 test vectors for parser/decoder smoke tests.
- Quick Start and Troubleshooting guides.
- Markdown / JSON evidence output.
- License, notices, and checksum file.
- COM port setup for IEC-103 serial communication.
- Active master session against one relay/IED slave.
- Setup overlay for baudrate, link address, common address, timeout, GI, and polling behavior.
- Operator Evidence grid for readable session activity.
- Line Monitor / Frame Trace view for raw TX/RX frame inspection.
- Value Viewer snapshot for latest decoded relay points.
- Relay Event Log for relay-timestamped state changes and events.
- AutoTest-style assessment checklist.
- Diagnostics tab for recoverable runtime issues.
- Markdown evidence export.
ArIEC103 decodes IEC-103 protocol fields such as Type, COT, FUN, INF, DPI/value, timestamp, checksum, and raw frame bytes.
Readable project signal names come from your own JSON mapping profile. This avoids guessed vendor naming and keeps FAT/SAT evidence aligned with the approved project signal list.
Example mapping entry:
{
"schema": "ariec103-mapping-profile-v1",
"profileName": "Project A Feeder 01",
"deviceName": "Relay Bay 01",
"linkAddress": 1,
"commonAddress": 1,
"signals": [
{
"id": "bay01.breaker.position",
"fun": 192,
"inf": 36,
"type": "DPI",
"name": "Breaker Position",
"group": "Switchgear",
"stateMap": {
"1": "Open",
"2": "Closed"
}
}
]
}If mapping is loaded, the app can display:
Breaker Position | Closed | FUN 192 / INF 36 | relay timestamp
If mapping is not loaded, the app keeps raw protocol evidence visible:
FUN 192 / INF 36 | DPI=2 | relay timestamp
ArIEC103 uses a conservative master policy suitable for relay testing:
Startup:
Open transport
Optional startup delay
Optional reset remote link
Reset FCB
Optional clock sync
Optional General Interrogation
Bounded GI follow-up
Normal runtime:
Poll Class 2 at the configured interval
If ACD=1:
Drain Class 1 until NO DATA / GI END / ACD clear / DFC busy / max drain / timeout
If DFC=1:
Back off and record busy evidence
If timeout or invalid response:
Keep FCB state stable, record diagnostic evidence, and recover according to the configured timeout policy
Class 1 is treated as pending high-priority/event data, not as a blind continuous polling loop.
ArIEC103 includes a lightweight validation kit so releases are easier to evaluate and regressions are easier to catch:
- dependency-free protocol smoke tests;
- sanitized FT1.2 / ASDU test vectors in
samples/test-vectors/; - validation matrix template in
docs/VALIDATION_MATRIX.md; - troubleshooting guide for no response, checksum errors, malformed frames, GI issues, and mapping gaps.
Run the protocol checks:
dotnet run --project tests/ArIEC103.Protocol.TestsBy default, exported evidence uses the mapping profile file name instead of exposing the full local workstation path.
Before sharing reports outside a project team, review project names, relay addresses, serial settings, mapping labels, comments, and raw frame evidence.
Requirements:
- .NET 8 SDK
- Windows for the WPF desktop app
- Visual Studio 2022/2026 or command line
dotnet
Build:
dotnet restore
dotnet buildRun WPF desktop:
dotnet run --project src/ArIEC103.DesktopRun a simulated master session without hardware:
dotnet run --project src/ArIEC103.Cli -- master --simulate --duration 10 --mapping samples/mapping-profiles/example-user-mapping.profile.json --report out/demo-master-evidence.md --json out/demo-master-evidence.jsonRun active master against a real relay:
dotnet run --project src/ArIEC103.Cli -- master --port COM1 --baud 9600 --link 1 --ca 1 --duration 30 --mapping samples/mapping-profiles/example-user-mapping.profile.json --report out/master-evidence.md --json out/master-evidence.jsonRun offline analyzer:
dotnet run --project src/ArIEC103.Cli -- analyze samples/sample_iec103_trace.log --report out/report.md --json out/report.jsonRun deterministic slave simulator:
dotnet run --project src/ArIEC103.Cli -- slave --port COM2 --baud 9600 --link 1 --ca 1 --duration 300Run protocol smoke tests:
dotnet run --project tests/ArIEC103.Protocol.TestsArIEC103 is intentionally focused:
- one IEC-103 connection first;
- active master tester first;
- offline trace analyzer as a supporting mode;
- user mapping profiles instead of guessed vendor profiles;
- raw FUN/INF/Type/COT/DPI/frame evidence always preserved;
- no built-in vendor-specific signal database.
It is not a vendor-specific tester, not a multi-protocol SCADA gateway, and not a replacement for formal site acceptance procedures.
Current releases are suitable for test-bench evaluation, communication troubleshooting, protocol evidence review, and public feedback.
For production or contractual FAT/SAT use, validate the package with the target relay, project communication settings, and approved project signal mapping before relying on exported evidence.
ArIEC103 is free and open source under the Apache License, Version 2.0. See LICENSE.