It is not possible to define the nature of Modbus addressing zones, i.e. whether server addressing is performed on 5 digits (as is the case with most basic PLCs) or 6 digits (full range for advanced controllers).
5 digits addressing:
Coil or Register Number | Protocol Data Offset | Table Name
00001 - 09999 | 0000h-270Eh | Output coils
10001 - 19999 | 0000h-270Eh | Discrete inputs
30001 - 39999 | 0000h-270Eh | Input registers
40001 - 49999 | 0000h-270Eh | Holding registers
6digit addressing:
Coil or Register Number | Protocol Data Offset | Table Name
000001 - 065536 | 0000h-FFFFh | Output coils
100001 - 165536 | 0000h-FFFFh | Discrete inputs
300001 - 365536 | 0000h-FFFFh | Input registers
400001 - 465536 | 0000h-FFFFh | Holding registers