v0.9.9
See RELEASENOTES.md for full details.
Fixes
- ENERGY_GUARD false-zeroes WIT 15K daily sensors after gateway reconnect (#335): Stale heuristic (\hours × 2 kWh/h) and 20 kWh spike threshold replaced — WIT profiles now use 80 kWh threshold; only exact yesterday-match used as stale indicator.
- MOD/MID-XH Grid Import Energy Total missing and incorrect (#336): Registers 3069/3070 were absent from \mod.py, causing fallback to unstable VPP range. Sensor showed wrong values and dropped backward in the HA energy dashboard.
Documentation
- WIT control guide expanded: timed vs continuous control (30408=0), write order, 30407 reboot failsafe, Patterns 1–7 with correct entity names and two-step termination sequence (confirmed on WIT 15KTL3 hardware)
- VPP V2.03 DTC table corrections, EEPROM-safe note for 30407/30408/30409, export limitation section
Contributors
Hardware testing and official Growatt protocol documentation by @Wojak129 — WIT 15KTL3 + DIY 32 kWh EVE/JK BMS system.