Repository navigation
Append HMI Studio 1.2.0
What's new
Indirect tags. Three new tag types, IndirectDiscrete, IndirectAnalog and IndirectMessage, have no value of their own.
- Linking: a script points one at any tag of the same kind with
LinkIndirectTag("Indirect", "Tag"). - Reading and writing: reading or writing the indirect tag then reads or writes that tag. Dotfields (
.Name,.InAlarm,.Acked, the engineering range) and alarm colors follow the linked tag. - Names from expressions: names can be built, e.g.
"SV" + Text(Unit, "000") + "_Status". - One set of links per Run, shared by every window.
- Errors: a failed link shows an Indirect Tag Error window. Literal names are checked by Validate.
ShowWindow script function. ShowWindow(name[, left, top[, modal[, wait]]]) opens a window from a script.
- left, top: move the window for this showing.
- modal: makes a popup modal or not.
- wait: pauses the script until the window closes. By default the script carries on.
- Errors: a failure shows a Window Error window.
Examples in LiquidWeighHMI and the User Manual.
- One faceplate: the example's 14 valve and pump faceplates are now a single Device Faceplate, driven by indirect tags (manual section 9.4).
- Beside the device: each symbol opens the faceplate beside itself with ShowWindow.
- Confirm before ABORT: ABORT waits for the operator's answer in the Confirm Abort popup (section 9.5).
- Function reference: the manual lists the new functions.
Fixes
- Scripts read any tag: an action or window script now reads tags that no object on its window shows. Before, they had bad quality, so IF branches on them didn't run.
- Touches pass through hidden objects: a touch on an object hidden by a Visibility link now reaches the visible object beneath it. Before, it was lost.
Downloads
| File | Platform |
|---|---|
Append-HMI-Studio-1.2.0-Setup.exe |
Windows 10/11 x64, installs for all users over earlier versions (silent: /S) |
Append-HMI-Studio-1.2.0-x86_64.AppImage |
Linux x64, runs without installing |
Append-HMI-Studio-1.2.0-amd64.deb |
Debian/Ubuntu (sudo apt install ./Append-HMI-Studio-1.2.0-amd64.deb) |
Known issues
- The installers are not code-signed, so Windows SmartScreen asks for confirmation on first run.
- There is no automatic update. Install new versions over the old one.