Added
An optional second state-of-charge sensor. Where a more accurate BMS measures the same
battery, the whole cascade now computes in its scale, and the difference to the inverter's
own reading is applied at the register boundary only: added when the discharge floor is
written, subtracted when it is read back. The inverter enforces its ToU registers against
its own BMS, so a floor derived from the accurate reading was enforced at the wrong state
of charge. Without the sensor the difference is zero and nothing changes.
A logbook message when the second reading is unusable and control falls back to the
inverter's own value. Nothing about the behaviour shows that fallback, and a reading taken
as zero would pull the floor to the bottom.
Changed
The state-of-charge field is now explicitly the value the inverter itself sees; the more
accurate sensor belongs in the new field. Instances that followed the earlier hint and put
a shadow sensor in the old field have to swap the two before the new one takes effect.
The inverter's shutdown state of charge is converted into the control scale before the
backup reserve builds on it, because that reserve is what holds in an outage.
Without discharge planning the ToU minimum is written converted as well, so the configured
percentage means the same state of charge everywhere it is used.
The balancing voltage stays as an input, now only as the threshold at which the measured pack
voltage counts as full while every BMS is offline — the fallback that starts a balancing run
when no cell voltages are readable. It is named and described for that role; value and effect
are unchanged.
Removed
The blueprint no longer writes any voltage to the inverter. Raising the float voltage for a
cell-balancing run, setting it back when the cooldown timer expires and the midnight check that
caught a voltage left raised by a lost timer are gone, together with the two float-voltage
inputs and the timer triggers that existed only to drive them. Writing a setpoint the charger
already manages means owning its failure modes for no gain: cell balancing works through the
throttled charge current alone.