An interactive terminal for communicating with IDEC MicroSmart PLCs over the IDEC Maintenance Protocol.
IDEC-TUI provides a persistent command shell around MiSmSerial.py. It is
intended for maintenance, testing, register inspection, diagnostics, and direct
PLC interaction without opening WindLDR.
- Interactive serial connection to an IDEC PLC
- Persistent connection settings
- Command history and tab completion
- Read and write word registers
- Read and write individual bits
- Read inputs and control outputs using
IandQaliases - Read and write IEEE-754 floating-point values
- Read timer information and write timer or counter values
- Read PLC error-code words
- Read and write blocks of registers
- Read and write multi-register unsigned integers
- Automatic Maintenance Protocol BCC-mode detection
- Optional raw TX/RX debugging
- PLC clock setting from the host computer
- Hardware and health diagnostics through the
checkcommand - Direct access to additional public
MiSmSerialmethods
The interactive TUI currently uses the serial Maintenance Protocol. The
repository also contains TCP, SD-card, and HMI-related libraries, but those are
not the active transport used by hoc_tui.py.
The current implementation has been exercised with FC5A and FC6A hardware over USB serial connections.
The Maintenance Protocol is shared across several IDEC MicroSmart generations, so some earlier CPUs may also work. CPU identification is intentionally conservative:
- Legacy
D8002CPU codes are reported as FC5A or earlier - The broad CPU class, such as
10-I/O, is printed when known - Unique FC6A CPU codes are identified directly
- Attached expansion modules are checked independently from the CPU generation
Exact CPU and module identification depends on the information exposed by the PLC. Some older expansion modules may not have a known type mapping.
- Python 3.10 or newer
pyserial- A serial or USB Maintenance Protocol connection to the PLC
readlinefor history and tab completion on Linux and macOS
Install the Python dependency with either:
python3 -m pip install pyserialor on Debian, Ubuntu, and Linux Mint:
sudo apt install python3-serialgit clone https://github.com/FOSSBOSS/IDEC-TUI.git
cd IDEC-TUI
chmod +x hoc_tui.py
./hoc_tui.pyThe program is currently run directly from the source tree. hoc_tui.py and
MiSmSerial.py must remain importable from the same project directory.
The current user must have permission to access the serial device. On many
Linux systems, that means membership in the dialout group:
sudo usermod -aG dialout "$USER"Log out and back in after changing group membership.
Common PLC serial devices include:
/dev/ttyACM0
/dev/ttyACM1
/dev/ttyUSB0
Start the terminal:
./hoc_tui.pyConfigure the connection:
plc[disconnected]> config
Typical USB settings are:
Port: /dev/ttyACM0
Device: FF
Baud: 9600
Timeout: 1.0
Bytesize: 8
Parity: N
Stopbits: 1
Debug: n
BCC mode: auto
Connect and read a register:
plc[disconnected]> connect
Connected to /dev/ttyACM0 (baud=9600, device=FF, bcc_mode=auto)
plc[connected]> read D8002
0
Disconnect or quit:
plc[connected]> disconnect
plc[disconnected]> q
Connection settings are saved to:
~/.plc_terminal_config.json
Command history is saved to:
~/.plc_terminal_history
On systems with readline, the up and down arrow keys navigate command history
and Tab completes commands, methods, and common register names.
| Command | Description |
|---|---|
config |
Configure and save serial connection settings |
connect |
Open the configured serial connection |
disconnect |
Close the current serial connection |
status |
Show connection state and saved configuration |
check |
Run the bundled PLC diagnostic and return to the TUI |
set-time |
Set the PLC clock from the host computer |
methods |
List supported and dynamically detected methods |
help |
Show command help |
clear |
Clear the terminal |
q, quit, exit |
Exit IDEC-TUI |
read <address>
write <address> <value>
Examples:
read D0100
write D0100 42
read D8005
read returns an unsigned 16-bit value from 0 through 65535.
read_bit <address>
write_bit <address> <0|1>
Examples:
read_bit M0000
write_bit M0000 1
read_bit M8004.15
write_bit M8004.15 0
The word.bit form reads or modifies one bit within a word value.
input <address>
output <address> <0|1>
Examples:
input I0
input X0
output Q0 1
output Q0 0
I is accepted as an input alias for X. Q is accepted as an output alias
for Y.
read_float <address> [endian]
write_float <address> <value> [endian]
Examples:
read_float D0200
read_float D0200 1
write_float D0200 12.5
The optional word-order argument is:
0 = low word first
1 = high word first
read_timer [timer_number] [count]
write_counter <counter_number> <preset>
Examples:
read_timer
read_timer 0 4
write_counter 10 500
read_error [address] [number_of_bytes]
Examples:
read_error
read_error 0 12
The default reads the six documented error-code words.
When connected, methods also lists additional public methods found on the
current MiSmSerial object. These methods can be called directly from the TUI.
Examples:
read_block D0100 4
read_uint D0105 2 1
write_block D0100 [1, 2, 3]
write_uint D0105 69420 2 1
write_timer 420 100
Arguments are parsed as Python-style values where possible. Decimal, binary, octal, hexadecimal, booleans, strings, lists, and numeric values can be used:
42
0x002A
0b101010
true
[1, 2, 3]
The serial Maintenance Protocol does not use the same request-BCC convention on every CPU, adapter, or bridge.
The available modes are:
auto
enq
no_enq
auto first tries a BCC that includes the ENQ byte. If the PLC returns NAK code
10, the request is retried without ENQ in the BCC calculation. The successful
mode is retained for the current connection.
Use auto unless a specific connection requires a fixed mode.
Enable debug in config to print Maintenance Protocol traffic:
TX(ascii): FF0RD800202
TX(hex): 05464630524438303032303232420d
RX(hex): 063031303030303033370d
This is useful for protocol investigation, BCC troubleshooting, and comparing requests with WindLDR captures.
The check command launches the bundled debug.py diagnostic. In the current
layout, hoc_tui.py expects it at:
SERIAL/debug.py
The diagnostic can:
- Scan available serial ports for a responsive PLC
- Report the host operating system and current host time
- Report the connected serial device
- Read the CPU type code from
D8002 - Report a legacy CPU as
FC5A or earlierwith its broad I/O class - Read the connected expansion-module count from
D8037 - Identify known expansion modules from the
D8470register range - Decode the
D8005general-error bitfield - Read selected PLC status bits
- List active outputs
- Read the raw
D8056value - Read the firmware version from
D8029 - Read the PLC date and time
Example:
plc[connected]> check
Running diagnostic: .../SERIAL/debug.py
Disconnected.
PLC connection: OK on /dev/ttyACM0
Hardware inventory:
CPU type D8002: 0x0000 (0)
CPU: FC5A or earlier CPU detected
CPU class: 10-I/O
Connected expansion modules: 2 (D8037)
Expansion slot 1: FC6A-J4CN1
Expansion slot 2: FC6A-J4CN1
Diagnostic finished with exit code 0
Connected to /dev/ttyACM0
When check is started from an active TUI connection, the TUI closes the port,
runs the diagnostic, and then attempts to reconnect using the saved
configuration.
With the PLC connected:
plc[connected]> set-time
This writes the host computer's current local date and time to the PLC clock registers and applies the new clock value.
This project can write directly to PLC registers and physical outputs.
Commands such as these can immediately alter machine behavior:
write
write_bit
output
write_block
write_uint
write_timer
write_counter
force
force_io
Before writing:
- Confirm the correct PLC is connected
- Confirm the register or output address
- Make sure the machine is in a safe state
- Do not rely on software alone for emergency-stop or safety interlocking
- Avoid forcing outputs on operating equipment unless the consequences are fully understood
The TUI exposes additional public library methods dynamically. That is useful for development, but it also means advanced or experimental methods may be available from the prompt.
- The interactive TUI currently connects through
MiSmSerial - Operand addresses currently use the four-digit registers
- Exact CPU generation cannot always be determined from
D8002 - Hardware type tables are incomplete for modules older than FC5A
- The TUI does not currently upload or download PLC user programs
- This is not a replacement for WindLDR project editing
- Hardware and protocol support is still being validated across PLC generations
| File | Purpose |
|---|---|
hoc_tui.py |
Interactive terminal application |
MiSmSerial.py |
Serial Maintenance Protocol client |
SERIAL/debug.py |
PLC connectivity, health, CPU, and module diagnostic |
setTime.py |
Standalone PLC clock-setting utility |
IDEC-TUI is released under the MIT License. See LICENSE for the complete
license text.
IDEC-TUI is usable for direct serial maintenance work, register inspection, and diagnostics, but it remains an active protocol-development project. Raw protocol debugging and conservative hardware reporting are intentional parts of the current design.
CPU Series Modules: FC5A, FC6A
Expansion Series modules: FC4A, FC5A, FC6A
Exact compatabliity is unknown, but modules remained responsive with a wide array of mixxing and matching hardware. Responsive hardware does not mean supported operation.