BusConductor without any module #2

@M256-Automation

Description

@M256-Automation

This is a recap of the problem discussed in the PLCnext Communuty Forum

busconductor-without-any-module

I have a project in which I can choose the file config.txt to place in /opt/plcnext/projects/BusConductor.
The selection is made in eHMI, so the user can select the local configuration during the startup of the plant.
I have 20 different configurations and everything works perfectly.
Now I have to define a configuration with no module, so I made a config.txt with just a "0" inside.
But the configuration doesn't seem to work. This is what I get in the Output.log:

27.04.20 06:51:01.245 BusConductor.BcComponent INFO - Resetting local I/O driver...
 27.04.20 06:51:01.274 BusConductor.BcComponent INFO - Done resetting driver.
 27.04.20 06:51:01.274 BusConductor.BcComponent INFO - Creating local I/O configuration...
 27.04.20 06:51:01.315 BusConductor.BcComponent INFO - Done creating configuration.
 27.04.20 06:51:01.316 BusConductor.BcComponent INFO - Reading local I/O configuration...
 27.04.20 06:51:01.322 BusConductor.BcComponent INFO - Done reading local I/O configuration.
 27.04.20 06:51:01.322 BusConductor.BcComponent ERROR - Read local I/O configuration failed. Response message too short.

Looking at the code I see the cause of exclusion (that comes before the file reading):

// Get the number of I/O modules detected
  // TODO: Check the "More Follows" word (receiveData[3]), and handle the situation where
  // there are more I/O modules than can fit in one message.
  if (receiveData.size() < 8)
  {
  this->log.Error("Read local I/O configuration failed. Response message too short.");
  return false;
  }

  num_modules = receiveData[7];

I tried commenting out just the "return false;" and leaving there the error message, and it worked, even if the LED D is flashing:

    27.04.20 08:09:07.732 BusConductor.BcComponent INFO - Resetting local I/O driver...
    27.04.20 08:09:07.784 BusConductor.BcComponent INFO - Done resetting driver.
    27.04.20 08:09:07.784 BusConductor.BcComponent INFO - Creating local I/O configuration...
    27.04.20 08:09:07.826 BusConductor.BcComponent INFO - Done creating configuration.
    27.04.20 08:09:07.826 BusConductor.BcComponent INFO - Reading local I/O configuration...
    27.04.20 08:09:07.829 BusConductor.BcComponent INFO - Done reading local I/O configuration.
    27.04.20 08:09:07.830 BusConductor.BcComponent ERROR - Read local I/O configuration failed. Response message too short.
    27.04.20 08:09:08.831 BusConductor.BcComponent INFO - Loading local I/O process data mapping...
    27.04.20 08:09:08.835 BusConductor.BcComponent INFO - Done loading process data mapping.
    27.04.20 08:09:08.835 BusConductor.BcComponent INFO - Enabling I/O data output...
    27.04.20 08:09:08.839 BusConductor.BcComponent INFO - Done enabling data output.

As suggested, instead of changing the code, i just bypassed the BusConductor procedure for this specific configuration, leaving a not running local bus.

It works but generates a red flashing LED D.

Thanks