OPC UA condition-assessment case

Question: a furnace temperature stops changing. Is the process steady, acquisition frozen, the source unreliable or the connection down?

The small custom model exposes five existing furnace signals plus an independent acquisition sequence. Inputs are fictional. Client/server traffic uses real local OPC UA.

Experiment Engineering distinction
Normal Establish typed-read/subscription baseline
Steady Old value timestamp can be valid while acquisition progresses
Frozen Server alive does not prove source is acquiring
Bad / Uncertain Do not promote unreliable data or invent zero
Process fault FAULTED equipment can still have Good-quality measurements
Server restart Re-establish subscription and readiness before resuming
Client write Server must reject even a correctly typed write
MQTT outage A telemetry candidate does not prove broker delivery

Run the guide, inspect retained evidence, then read the condition-assessment report.

For each finding, identify the raw observation, alternative explanations and next check. Automated code tests do not establish personal mastery: explain three traces and predict a changed scenario before running it.

No physical condition, field measurements, predictive-maintenance accuracy or calibrated digital-twin claim follows from this software case.