Skip to content

Latest commit

 

History

10 Commits

Folders and files

NameName
Last commit message
Last commit date
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Repository files navigation

NOD154

A 154-bus Nordic Distribution grid (NOD) used for publication. Grid data taken from a real distribution grid in Norway.

Grid Overview

Grid Drawing

The NOD154 is a medium-voltage distribution grid model derived from a real Norwegian distribution network. It consists of 154 buses at the 23 kV level, supplied through a single 132/23 kV transformer connected to the external grid at bus B0.

Component Count Description
Buses 154 1 at 132 kV (B0), 153 at 23 kV (B1–B153)
Lines 152 All at 23 kV
Transformer 1 132/23 kV, 40 MVA, with on-load tap changer (OLTC)
Loads 79 Active power loads (0.05–2.0 MW range)
Synchronous machines 5 SM1 (3.3 MVA), SM2 (0.1 MVA), SM3 (8.5 MVA), SM4 (5.7 MVA), SM5 (2.0 MVA)
Solar PV units 23 Rated from 0.05 to 2.0 MVA

The grid has a radial topology with a single main feeder and multiple lateral branches. Distributed generation includes both synchronous machines and solar PV installations spread across the network.

Grid Data

The grid data is provided in grid_data/grid_data.xlsx (see also grid_data/original_grid_data.xlsx for the unmodified source) and contains the following sheets:

  • busbars — Bus indices, names, and nominal voltages.
  • lines — Line parameters including impedance (R, X), capacitance, current limits, and connectivity.
  • loads — Load bus assignments with nominal active and reactive power.
  • gens — Synchronous generators with ratings, voltage setpoints, and slack bus assignment.
  • static gens — Static generators (solar PV) with rated power and bus assignments.
  • trafos — Transformer parameters including voltage levels, impedance, and tap changer settings.

OPF experiment data (time-series for reproducibility)

The folder opf_experiment_data/ publishes the training and validation CSVs used for multi-period OPF experiments on NOD154 (e.g. droop-based ORPD): per-bus load and generation for quarter-hour steps, aligned with the grid model. It includes:

  • training/train_n_1.csv, train_n_2.csv, train_n_4.csv (1, 2, and 4 training days).
  • validation/validation_day91.csvvalidation_day100.csv plus optional *_factors.csv aggregate files.
  • voltage_reference_statistics.csv — Per-bus voltage statistics for droop references and limits.

See opf_experiment_data/README.md for schema, day indexing, and how training vs. validation days are defined.

Repository Structure

NOD154/
├── figures/                # Grid diagrams and visualizations
│   ├── grid_drawing.png
│   └── grid_drawing.pdf
├── grid_data/              # Raw grid model data
│   ├── grid_data.xlsx
├── opf_experiment_data/    # Published OPF training/validation time-series (CSV)
│   ├── README.md
│   ├── training/
│   ├── validation/
│   └── voltage_reference_statistics.csv
├── operating_points/       # Operating point data (load/generation scenarios)
├── test_results/           # Power flow results (CSV per scenario)
├── LICENSE
└── README.md

Operating Points

Four power flow scenarios are defined by combining two load levels and two generation levels. Loads are scaled uniformly from their rated apparent power (s_base_mva), and generators are scaled from their rated capacity (S_rated_mva). All synchronous machines (SM1–SM5) are modelled as PQ buses with Q = 0. Solar PV units are static generators (PQ) with Q = 0.

Scenario Load factor Hydro (SM1–SM5) Solar PV
Low load, low gen 0.1 P = 0.2 × S_rated P = 0, Q = 0
Low load, high gen 0.1 P = 0.9 × S_rated P = 0.9 × S_rated
High load, low gen 0.8 P = 0.2 × S_rated P = 0, Q = 0
High load, high gen 0.8 P = 0.9 × S_rated P = 0.9 × S_rated

The slack bus (B0, external grid connection at 132 kV) balances the system.

Test Results

Power flow results for each scenario are stored as CSV files in test_results/ (bus results and branch results per scenario).

Scenario P_gen (MW) P_load (MW) Losses (MW) V_min (pu) V_max (pu)
Low load, low gen 1.90 1.81 0.09 (4.8%) 1.000 (B0) 1.034 (B103)
Low load, high gen 3.69 1.81 1.88 1.000 (B0) 1.166 (B99)
High load, low gen 16.81 14.48 2.32 (16%) 0.828 (B84) 1.000 (B0)
High load, high gen 14.86 14.48 0.38 (2.6%) 1.000 (B0) 1.048 (B103)

Key observations:

  • High load, high gen is the most balanced operating point, with local generation covering most of the demand and losses at only 2.6%.
  • Low load, high gen produces significant overvoltage at the feeder endpoints (V_max = 1.17 pu at B99) as excess generation flows back to the external grid through the radial feeders.
  • High load, low gen causes large voltage drops (V_min = 0.83 pu at B84) since the slack bus must supply the bulk of the demand through long, high-impedance radial feeders.

Usage

This grid model is intended for scientific research and power systems engineers studying voltage-constrained distribution grids with high penetration of distributed energy resources (DER). The data can be imported into any power flow tool that accepts bus/branch/generator data in tabular form.

Citation

License

See LICENSE for details.

Contact

About

A 154 bus distribution grid used for publication. Grid data taken from a real distribution grid in Norway.

Resources

Stars

0 stars

Watchers

0 watching

Forks

Releases

Packages

Contributors