Skip to content

Latest commit

 

History

17 Commits

Folders and files

NameName
Last commit message
Last commit date
 
 
 
 
 
 
 
 
 
 
 
 

Repository files navigation

EASUN ISolar SMG II 8/11kW (HA, Modbus RTU)

Product: https://www.powland.net/collections/isolar-smg-ii/products/isolar-smg-ii-11kw-48v-wifi

This repository provides a Home Assistant (Raspberry Pi) and ESPHome (ESP-32-WROOM) configuration, both using Modbus RTU and the documented register addresses for monitoring and controlling EASUN ISolar SMG II 8/11kW inverters.

Other Compatible Hardware

While designed for the EASUN ISolar SMG II, the Modbus map and configurations in this repository have been confirmed to work with the following rebranded models:

  • Anenji 11kW Hybrid Inverter (ANJ-HHS-11kW-48V-wifi)

Hardware Connection Note (Anenji 11kW): The RS232 port on the Anenji unit utilizes a standard DB9 connector. It requires a simple straight-through connection cable to connect directly to your PC or serial interface device.

Installation

ESP-WROOM-32

Use the provived /esphome/esp32-rs232.yaml in ESPHome Builder and flash the compiled .bin to your ESP32. Remember to change API/OTA keys and your Wi-Fi credentials.

Beware: I uncommented every sensor/select etc, so you'll probably have way more entities than you need inside your Home Assistant. Consider commenting yourself those you don't need.

Connect the pins as shown in this reference image:

image

Raspberry

It has been tested using an RS485 to USB adapter.

When connecting RS485 to USB, you must connect the positive terminal of one device to the positive terminal of the other, and the negative to the negative.

  • A+ (or D+, or TX+/RX+): This is the positive data line.
  • B- (or D-, or TX-/RX-): This is the negative data line.

We'll use the files in /homeassistant/smgii. Copy the smgii folder to the config folder in Home Assistant (using FTP or Samba). Then, in your configuration.yaml, add the following lines:

homeassistant:
   packages:
     easun_smg_ii: !include smgii/modbus.yaml

Registers

Thanks to gagara for the memory addresses and their description.

Setting Units Data type Register Addr Register Count Read/Write Comment Protocol Number
Fault Code uint32 100 2 R 32-bit error code, each bit corresponds to an error code, see details in Error Code Table 3,4,5,6
Warning Code uint32 104 2 R 32-bit warning code, each bit corresponds to a warning code, see details in Warning Code Table 3,4,5,6
Type of device uint16 171 1 R 3,4,5,6
Protocol Number 184 1 R 0x03 3
Protocol Number 184 1 R 0x04 4
Protocol Number 184 1 R 0x05 5
Protocol Number 184 1 R 0x06 6
Serial number ASCII 186 12 R 3,4,5,6
Power flow State unit16 198 1 R See Power Flow State Description 3,4,5,6
Working Mode 201 1 R 0: Power On Mode; 1: Standby Mode; 2: Mains Mode; 3: Off-Grid Mode; 4: Bypass Mode; 5: Charging Mode; 6: Fault Mode 3,4,5,6
Total Grid Current 0,1A unit16 202 1 R
Total Grid Frequency 0,01Hz unit16 203 1 R 3,4,5,6
Total Grid Active Power 1W uni16 204 1 R
Total Grid Apparent Power 1VA unit16 205 1 R
Total Grid Charging Power 1W unit16 206 1 R 3,4,5,6
Expansion of Power flow State uint16 207 1 R See Power Flow State Expansion Description 3,4,5,6
not used 208 18
Total Inverter Current 0,1A uint16 226 1 R
Total Inverter Frequency 0,01Hz uint16 227 1 R 3,4,5,6
Total Inverter Active Power 1W uint16 228 1 R
Total Inverter Apparent Power 1VA uint16 229 1 R
Total Charging Current 0,1A uint16 230 1 R 3,4,5,6
Inverter Module Temperature 1°C uint16 231 1 R 3,4,5,6
not used 232 20
Total Output Current 0,1A uint16 252 1 R 4,6
Total Output Frequency 0,01Hz uint16 253 1 R 3,4,5,6
Total Output Active Power 1W uint16 254 1 R 4,6
Total Output Apparent Power 1VA uint16 255 1 R 4,6
Total Load Percentage 1% uint16 256 1 R 4,6
not used 257 20
Battery Voltage 0,1V uint16 277 1 R 3,4,5,6
Battery Current 0,1A uint16 278 1 R A positive number indicatesa charge and a negative number indicates a discharge. 3,4,5,6
Battery Power 1W uint16 279 1 R 3,4,5,6
Battery SOC 1% 280 1 R 3,4,5,6
DC Module Temperature 1°C uint16 281 1 R 3,4,5,6
not used 282 20
Total PV Power 1W uint16 302 1 R 3,4
Total PV Charging Power 1W uint16 303 1 R 3,4
Total PV Charging Current 0,1A uint16 304 1 R 3,4
PV Module Temperature uint16 305 1 R 3,4,5,6
not used 306 20
External CT Total Power Balance 1W int32 326 2 R Positive: consumed from grid; Negative: feed to grid
not used 328 10
L1 Grid Voltage 0,1V uint16 338 1 R 3,4,5,6
L1 Grid Current 0,1A uint16 339 1 R
L1 Grid Active Power 1W int16 340 1 R Positive: energy consumed from grid; Negative: energy feed to grid 3,4,5,6
L1 Grid Apparent Power 1VA uint16 341 1 R
L1 Inverter Voltage 0,1V uint16 342 1 R 3,4,5,6
L1 Inverter Current 0,1A uint16 343 1 R 3,4,5,6
L1 Inverter Active Power 1W int16 344 1 R Positive: DC->AC flow; Negative: AC->DC flow 3,4,5,6
L1 Inverter Apparent Power 1VA uint16 345 1 R
L1 Output Voltage 0,1V uint16 346 1 R 3,4,5,6
L1 Output Current 0,1A uint16 347 1 R 3,4,5,6
L1 Output Active Power 1W uint16 348 1 R 3,4,5,6
L1 Output Apparent Power 1VA uint16 349 1 R 3,4,5,6
L1 Output Load Percentage 1% uint16 350 1 R 3,4,5,6
PV1 Voltage 0,1V uint16 351 1 R 3,4,5,6
PV1 Current 0,1A uint16 352 1 R 3,4,5,6
PV1 Power 1W uint16 353 1 R 3,4,5,6
L1 Output Power? 1W int32 354 2 R Positive: energy consumed from grid; Negative: energy feed to grid
not used 356 20
L2 Grid Voltage 0,1V uint16 376 1 R
L2 Grid Current 0,1A uint16 377 1 R
L2 Grid Active Power 1W int16 378 1 R Positive: energy consumed from grid; Negative: energy feed to grid
L2 Grid Apparent Power 1VA uint16 379 1 R
L2 Inverter Voltage 0,1V uint16 380 1 R
L2 Inverter Current 0,1A uint16 381 1 R
L2 Inverter Active Power 1W int16 382 1 R Positive: DC->AC flow; Negative: AC->DC flow
L2 Inverter Apparent Power 1VA uint16 383 1 R
L2 Output Voltage 0,1V uint16 384 1 R 4,6
L2 Output Current 0,1A uint16 385 1 R 4,6
L2 Output Active Power 1W uint16 386 1 R 4,6
L2 Output Apparent Power 1VA uint16 387 1 R 4,6
L2 Output Load Percentage 1% uint16 388 1 R 4,6
PV2 Voltage 0,1V uint16 389 1 R 3,4
PV2 Current 0,1A uint16 390 1 R 3,4
PV2 Power 1W uint16 391 1 R 3,4
L2 Output Power? 1W int32 392 2 R Positive: energy consumed from grid; Negative: energy feed to grid
not used 394 20
L3 Grid Voltage 0,1V uint16 414 1 R
L3 Grid Current 0,1A uint16 415 1 R
L3 Grid Active Power 1W int16 416 1 R Positive: energy consumed from grid; Negative: energy feed to grid
L3 Grid Apparent Power 1VA uint16 417 1 R
L3 Inverter Voltage 0,1V uint16 418 1 R
L3 Inverter Current 0,1A uint16 419 1 R
L3 Inverter Active Power 1W int16 420 1 R Positive: DC->AC flow; Negative: AC->DC flow
L3 Inverter Apparent Power 1VA uint16 421 1 R
L3 Output Voltage 0,1V uint16 422 1 R
L3 Output Current 0,1A uint16 423 1 R
L3 Output Active Power 1W uint16 424 1 R
L3 Output Apparent Power 1VA uint16 425 1 R
L3 Output Load Percentage 1% uint16 426 1 R
PV3 Voltage 0,1V uint16 427 1 R
PV3 Current 0,1A uint16 428 1 R
PV3 Power 1W uint16 429 1 R
L3 Output Power? 1W int32 430 2 R Positive: energy consumed from grid; Negative: energy feed to grid
not used 432 168
Output Mode uint16 600 1 R/W 0: Single; 1: Parallel; 2: 3-Phase P1; 3: 3-Phase P2; 4: 3-Phase P3; 5: Split-phase P1; 6: Split-phase P2 3,4,5,6
Output Priority (primary) uint16 601 1 R/W 1: SUB; 2: SBU; 3: SUF 3,4,5,6
Output Priority (secondary) uint16 602 1 R/W 0: Secondary output disabled; 1: SUB; 2: SBU; 3: SUF 3,4,5,6
Start time from secondary output priority uint16 603 1 R/W Range: 0000-2359,thousands and hundreds are hours, tens and single digits are minutes 3,4,5,6
End time from secondary output priority uint16 604 1 R/W Range:0000 2359,thousands and hundreds are hours, tens and single digits are minutes 3,4,5,6
Current Output Priority uint16 605 1 R 1: SUB; 2: SBU; 3: SUF 3,4,5,6
Output Voltage Setting 0,1V uint16 606 1 R/W 2200: output 220V; 2300: output 230V; 2400: output 240V; 3,4,5,6
Output Frequency Setting 0,01Hz uint16 607 1 R/W 5000: 50Hz output; 6000: 60Hz output; 3,4,5,6
OP2 Overload Alarm Setting 1% uint16 608 1 R/W Range: 10%-100% 4,6
OP2 Output Allowed Setting uint16 609 1 R/W 0: Disabled 1: Enabled 4,6
not used 610 20
Battery Type uint16 630 1 R/W 0: AGM; 1: FLD; 2: USER; 4: Li2; 6: Li4; 8: LiB 3,4,5,6
Overvoltage protection Setting 0,1V uint16 631 1 R/W 3,4,5,6
Charger Source Priority (primary) uint16 632 1 R/W 1: Solar First (SOF); 2: Solar & Utility (SNU); 3: Only Solar (OSO); 4: Solar Residual (SOR) 3,4,5,6
Charger Source Priority (secondary) uint16 633 1 R/W 0: Disabled; 1: (SOF); 2: (SNU); 3: (OSO); 4: (SOR) 3,4,5,6
Start time for secondary charger source priority uint16 634 1 R/W Range: 0000 2359, thousands and hundreds are hours, tens and single digits are minutes 3,4,5,6
End time for secondary charger source priority uint16 635 1 R/W Range: 0000 2359, thousands and hundreds are hours, tens and single digits are minutes 3,4,5,6
Current Charger Source Priority uint16 636 1 R 1: (SOF); 2: (SNU); 3: (OSO); 4: (SOR) 3,4,5,6
Bulk Charging Voltage Setting 0,1V uint16 637 1 R/W 3,4,5,6
Floating Charging Voltage Setting 0,1V uint16 638 1 R/W 3,4,5,6
Bulk Charging time (CV stage) Setting 1m uint16 639 1 R/W Interval: 1-900 minutes, 0 - auto 3,4,5,6
Max Charging Current Seting 0,1A uint16 640 1 R/W 3,4,5,6
Max AC Charging Current Setting 0,1A uint16 641 1 R/W 3,4,5,6
Max Discharge Current Protection Setting 1A uint16 642 1 R/W Range: 0-500A 3,4,5,6
Back to Battery Voltage Setting 0,1V uint16 643 1 R/W 0 - 100% SOC 3,4,5,6
Back to Grid Voltage Setting 0,1V uint16 644 1 R/W 3,4,5,6
OP1 Low Voltage Protection Setting (off-grid mode) 0,1V uint16 645 1 R/W 4,6
Low Voltage Protection Setting (off-grid mode) 0,1V uint16 646 1 R/W 3,4,5,6
Back to Battery SOC Setting 1% uint16 647 1 R/W 3,4,5,6
Back to Grid SOC Setting 1% uint16 648 1 R/W 3,4,5,6
OP1 Low SOC Protection Setting (off-grid mode) 1% uint16 649 1 R/W 4,6
Low SOC Protection Setting (off-grid mode) 1% uint16 650 1 R/W 3,4,5,6
Battery Equalization mode uint16 651 1 R/W 0: Disabled; 1: Enabled 3,4,5,6
Battery Equalization Voltage Setting 0,1V uint16 652 1 R/W 3,4,5,6
Battery Equalization Time Setting 1m 653 1 R/W Range: 0-900 minutes, step 5 3,4,5,6
Battery Equalization Timeout Setting 1m 654 1 R/W Range: 0-900 minutes, step 5 3,4,5,6
Battery Equalization Interval Setting 1d uint16 655 1 R/W Interval: 1-90 days 3,4,5,6
Equalization activated immediately uint16 656 1 R/W 0: Disabled; 1: Enabled 3,4,5,6
not used 657 20
AC Input Voltage Range uint16 677 1 R/W 0: APL; 1: UPS; 2:GNT 3,4,5,6
Buzzer Mode uint16 678 1 R/W 0: Silent; 1: Faults, Warnings, Source Change; 2: Faults, Warnings; 3: Faults 3,4,5,6
LCD Backlight uint16 679 1 R/W 0: Timed-off; 1: Always on 3,4,5,6
LCD Automatic return to homepage uint16 680 1 R/W 0: Disabled; 1: Enabled 3,4,5,6
Energy-saving Mode uint16 681 1 R/W 0: Disabled; 1: Enabled 3,4,5,6
Overload Automatic Restart uint16 682 1 R/W 0: Disabled; 1: Enabled 3,4,5,6
Overtemperature Automatic Restart uint16 683 1 R/W 0: Disabled; 1: Enabled 3,4,5,6
Overload Transfer to Bypass uint16 684 1 R/W 0: Disabled; 1: Enabled 3,4,5,6
PV parallel detection Mode uint16 685 1 R/W 0: Disabled; 1: Enabled
External CT enabled uint16 686 1 R/W 0: Disabled; 1: Enabled
Mask Warnings uint32 687 2 R/W Alerts matching 1 are displayed normally and alerts matching 0 are blocked. 3,4,5,6
Dry contact uint16 689 1 R/W 0: Normal mode; 1: Box Mode of grounding; 3,4,5,6
Automatic Mains Output enabled uint16 690 1 R/W 0: No mains output until power button pressed; 1: Mains outputs even if power button not pressed 3,4,5,6
Max PV power Connected 1W uint16 691 1 R/W Range: 200W. Rated power
Islanding Detection Enabled uint16 692 1 R/W 0: Disabled; 1: Enabled
Boot Method uint16 693 1 R/W 0: Can be turned on locally or remotely; 1: Can only be turned on locally; 2: Can be turned on remotely only 3,4,5,6
Remote Switch uint16 694 1 R/W 0: Remote shutdown; 1: Remote boot 3,4,5,6
Exit Fault State uint16 695 1 W 1: Exit fault state lock (will only take effect if the machine enters fault mode) 3,4,5,6
Inverter Date uint16 696 3 R/W Three numbers of 16 digits representing the year, month and day (for example: 07H E6H 00H 07H 00H 0EH means July 14, 2022) 3,4,5,6
Inverter Time uint16 699 3 R/W Three numbers of 16 digits representing hours, minutes and seconds (for example: 00H 0DH 00H 00H 00H 10H means 13:15:16) 3,4,5,6
Daily PV Energy generation 0,01kWh uint16 702 1 R 3,4,5,6
Total PV Energy generation 0,01kWh uint32 703 2 R 3,4,5,6
Reset generated Power uint16 705 1 W OxAA: Clear all the data on the energy production 3,4,5,6
Reset User Settings uint16 706 1 W OxAA: Reset user parameters to default value (takes effect in non-offgrid mode) 3,4,5,6
Ground Relay Enabled unit16 707 1 R/W 0: Disabled; 1: Enabled 4,6
Lithium Battery Activation Time 1m 709 1 R/W Interval: 6-300 minutes 3,4

Error Code Table (register 100)

Bit offset Description
0 Inverter overheating
1 PV Overtemperature
2 DCDC Overtemperature
3 Battery overvoltage
4 not used
5 Output short circued
6 Inverter overvoltage
7 Output overloaded
8 Bus overvoltage
9 Bus soft start failed
10 PV overcurrent
11 PV overvoltage
12 DCDC overcurrent
13 Inverter overcurrent
14 Bus voltage too low
15 not used
16 Over DC voltage in AC output
17 PV1 current is too distorted
18 Output current is too distorted
19 Inverter current is too distorted
20 Battery current is too distorted
21 PV1 current is too distorted
22 Inverter low voltage
23 Inverter negative power
24 Host in parallel system is lost
25 Synchronization signal abnormal in the parallel system
26 Battery type is incompatible
27 Parallel versions are incompatible
28 External TC settings are duplicated
29 Output current L2 is too distorted

Warning Code Table (register 104)

Bit offset Description
0 Mains zero crossing is lost
1 Mains waveform abnormal
2 Mains overvoltage
3 Mains low voltage
4 Mains overfrequency
5 Mains low frequency
6 PV1 low voltage
7 Overtemperature
8 Battery low voltage
9 Battery not connected
10 Overload
11 Battery Eq charging
12 Battery is discharged to low voltage and has not been recharged to the recovery point
13 Output power derating
14 Fan blocked
15 PV energy is too low to be used
16 Parallel communication interrupted
17 Output mode of Single and Parallel systems is inconsistent
18 Battery voltage difference of parallel system is too large
19 Communication with lithium battery is abnormal
20 Battery discharge current too high
21 Islanding detected
22 PV2 low voltage
23 OP1 is overloaded
24 OP2 load exceeds the set value
25 OP2 is overloaded
26-31 not used

Power Flow State (register 198)

Bit offset Description
0-1 0: PV is not connected; 1: PV is connected
2-3 0: Mains is not connected; 1: Mains is connected
4-5 0: Battery is not charging/discharging; 1: Battery is charging; 2: Battery is discharging
6-7 0: Load is not connected; 1: Load is connected
8 0: Mains is not charging; 1: Mains is charging
9 0: PV is not charging; 1: PV is charging
10 0: Battery icon is on; 1: Battery icon is off
11 0: PV icon is on; 1: PV icon is off
12 0: Mains icon is on; 1: Mains icon is off
13 0: Load icon is on 1: Load icon is off

Power Flow State Expansion (register 207)

Bit offset Description
0 0: PV1 is not connected; 1: PV1 is connected
1 0: PV2 is not connected; 1: PV2 is connected
2-3 0: AC input 1 is not connected; 1: AC input 1 is connected
4-5 0: AC input 2 is not connected; 1: AC input 2 is connected
6-7 0: AC input 3 is not connected; 1: AC input 3 is connected
8 0: OP1 loaded; 1: OP1 not loaded
9 0: OP2 loaded; 1: OP2 not loaded
10-15 not used

About

Register addresses and HA/ESPHome configs for EASUN ISolar SMG II 8/11kW.

Resources

Stars

6 stars

Watchers

1 watching

Forks

Releases

Packages

Contributors