AlphaESS

PowerSync supports AlphaESS SMILE and Storion hybrid inverter-battery systems via Modbus TCP. An optional Cloud API can supplement telemetry when Modbus is temporarily unreachable.

Supported models

Model Description
SMILE5 Single Phase Hybrid
SMILE-Hi5 Single Phase Hybrid
SMILE-Hi10 Three Phase Hybrid
SMILE-B3 Three Phase Hybrid
SMILE-T10 Three Phase Hybrid
SMILE-G3 Three Phase Hybrid
Storion-T30 Three Phase Hybrid

All models use the same Modbus register map and control logic.

Prerequisites

Enable Modbus TCP on the inverter

Modbus TCP must be enabled on the inverter before PowerSync can connect. This is done in the AlphaESS app or via the local web interface depending on your firmware version.

  • Open the AlphaESS app → SettingsCommunication → enable Modbus TCP
  • Note the inverter's local IP address — assign a static IP (or DHCP reservation) so it does not change

Enable Modbus curtailment in firmware (required for DC curtailment)

This is the most common reason curtailment does not work on Smile5 systems.

AlphaESS firmware has a separate "Modbus curtailment" feature that must be enabled before the inverter will physically honour export-limit commands sent over Modbus. Without it, PowerSync can write the export-limit register (0x0800) and the value will appear to change, but the inverter will not throttle PV output.

To enable it:

  1. Open the AlphaESS app
  2. Go to SettingsGridExport Limit (label varies by firmware version)
  3. Set the export limit mode to Modbus or enable External Control
  4. Save and confirm

If you cannot find this setting, contact AlphaESS support or check your firmware release notes. Some older firmware versions do not support Modbus-controlled export limiting at all — a firmware upgrade may be required.


Setup in PowerSync

1. Modbus TCP connection

During initial setup, select AlphaESS as your battery system and enter:

Field Description Default
IP address Local IP of the inverter
Port Modbus TCP port 502
Slave ID Modbus unit ID 85 (0x55)
Export limit (kW) Safety cap on grid export Unlimited
Enable DC curtailment Turn on zero-export curtailment Off

Slave ID: The AlphaESS factory default is 85 (0x55). This is different from most other inverters (which default to 1). Only change it if you have altered the inverter's Modbus configuration.

Export limit: Optional hard cap in kW. PowerSync will never request more than this amount of export regardless of price. Leave blank for no cap.

2. DC curtailment toggle

The Enable DC curtailment toggle activates zero-export curtailment. When enabled, PowerSync monitors feed-in prices and writes 0% to the AlphaESS export-limit register (0x0800) when export is uneconomical (feed-in price below 1 c/kWh). It restores normal export when prices recover.

This toggle has no effect unless Modbus curtailment is enabled in the inverter firmware first (see Prerequisites).

3. Cloud API (optional)

The AlphaESS Cloud API provides a secondary telemetry source used as a fallback when Modbus is temporarily unreachable. It does not provide any additional control capability — all force charge, force discharge, and curtailment commands go via Modbus.

To use it:

  1. Log in at open.alphaess.com
  2. Go to API Management and create an application to get an App ID and App Secret
  3. Enter these in the Cloud API step of PowerSync setup
  4. Enter your inverter's serial number if prompted

Leave the Cloud API fields blank to skip it — Modbus alone is sufficient.


How curtailment works

When curtailment is triggered, PowerSync:

  1. Releases any active force-charge or force-discharge dispatch (register 0x0880 = 0) — active dispatch overrides the export-limit register on Smile firmware and must be cleared first
  2. Writes 0% to the export-limit register (0x0800)
  3. The inverter firmware enforces zero grid export — solar continues to power the home and charge the battery, only grid feed-in is blocked

When curtailment is lifted, PowerSync restores 0x0800 to the previously stored value (or 100% if none was stored).

Limitations

  • Curtailment is DC-coupled PV behind the AlphaESS MPPT. PowerSync has no direct PV power setpoint — it relies on the AlphaESS firmware to enforce the export limit. If the firmware ignores the register, PV output is unaffected.
  • Some firmware versions acknowledge the Modbus write but do not enforce the value. If you write 0% and export continues unchanged, the most likely cause is that Modbus curtailment is not enabled in the firmware settings.
  • Mode 7 (Maximise Consumption) is documented to physically disable PV output on some hardware, but it also forces grid charging and is not currently used by PowerSync as it changes battery behavior in ways that conflict with LP optimizer decisions.

Force charge / force discharge

The LP optimizer and manual force-mode services control the battery via the AlphaESS dispatch block (registers 0x0880–0x0888), using Mode 2 (State of Charge Control):

  • Force charge: charges from grid at the requested power rate until the target SoC is reached or the duration expires
  • Force discharge: discharges to grid at the requested power rate until the floor SoC is reached or the duration expires

The inverter auto-stops when the dispatch timer elapses, so a lost connection will not leave the battery permanently locked in a forced mode.


Troubleshooting

Modbus connection fails

  • Confirm Modbus TCP is enabled in the AlphaESS app
  • Confirm the IP address is correct and reachable from Home Assistant
  • Try slave ID 85 (0x55) — this is the AlphaESS default and differs from most other inverters
  • Check that nothing else on the network is connected to port 502 on the inverter at the same time (AlphaESS typically allows only one Modbus TCP client)

Curtailment enabled but export continues

  1. Check firmware setting first — Modbus curtailment must be enabled in the AlphaESS app under Settings → Grid → Export Limit. This is the most common cause.
  2. Check the PowerSync logs for AlphaESS export limit set to 0% — if this does not appear, the write is not being attempted
  3. Check for AlphaESS curtail: releasing active dispatch in logs — if dispatch release is failing, the export register may not be evaluated
  4. Read back register 0x0800 using a Modbus tool to confirm the write sticks
  5. If the register sticks at 0% but export continues, the inverter firmware is not enforcing it — contact AlphaESS support about enabling Modbus export control for your firmware version

Battery not responding to force charge / force discharge

  • Confirm the battery SOC is not already at the target level
  • Check logs for AlphaESS dispatch CHARGE/DISCHARGE — confirms the full dispatch block was written
  • Verify the inverter is not in a fault or protection state (check the AlphaESS app)