ampinvt-ui

A small desktop app for monitoring and configuring an AMPINVT TEL-series off-grid solar inverter over its USB serial port.

Built for a TEL-48502M100 (5000 W, 48 V → 120 V, 100 A MPPT), sold as "AMPINVT Solar Inverter 5000 Watt 48V to 120V". Tauri v2 + React + a hand-rolled Modbus RTU implementation.

The vendor publishes no protocol documentation. Everything this app knows was reverse-engineered against a physical unit. Read Confidence before changing anything.

Why this is not a generic Modbus tool

A generic Modbus client would show you 0x1103 = 150 and leave you none the wiser. The value here is entirely in the decoding:

  • the address space is sparse and 256-aligned — only 13 blocks of 256 exist
  • only function 0x03 is implemented; 0x04 (input registers) is silent everywhere
  • voltage settings are stored as 12 V-equivalent tenths — actual volts = raw × 0.4
  • voltage readings are plain tenths — raw ÷ 10. Mixing these up is the easiest mistake to make.

That knowledge lives in exactly one file, src/registers.ts. The Rust side (src-tauri/src/modbus.rs) is plain, device-agnostic Modbus RTU. Adding a second inverter should be a new map, not a rewrite.

Link parameters

Transport USB serial, CH340 (1A86:7523)
Baud / framing 9600 8N1
Slave address 1
Read function 0x03
Write function 0x06
Inter-frame gap 50 ms — mandatory, see below
Poll rate live blocks 1 Hz, settings 15 s

Frames get lost, so reads retry

Forensics on a real stall found 95 of 179 sweeps dropped at least one block, climbing in frequency for twenty minutes before the link failed completely — while the inverter was charging hard at 20 A. Readings were rock steady throughout; there was no drift, the link simply shed frames until it shed all of them.

Reads therefore retry up to three times. Modbus exceptions are not retried — an exception is the device answering correctly to say an address does not exist, and it will say so just as firmly the second time.

Ground offset is not the cause: the host is a laptop, galvanically floating, so a USB isolator would change nothing. The leading candidate is EMI coupled into the cable from a converter switching kilowatts a metre away, with MCU starvation under load and thermal drift as alternatives. All three are transient, which is what makes retrying effective.

Worth doing physically: ferrite chokes on the USB cable, keep it away from battery and AC runs, and use the shortest cable that reaches.

The inter-frame gap is not optional

Modbus RTU only requires 3.5 character times between frames — about 3.65 ms at 9600 8N1. This inverter needs roughly ten times that. Measured on a real unit, reading 0x1000 thirty times per step:

gap result
10 ms 15/30
15 ms 19/30
20 ms 21/30
25 ms 29/30
30 ms 30/30
60 ms 30/30

Below the threshold it answers roughly every other request — a burst with no gap scores exactly 13/25, a perfect alternating pattern. It is not mis-framing; it is slow to re-arm its receiver.

The app enforces 50 ms, measured from the end of the previous exchange, on every path including failures. A sustained 90-second run at the app's real duty cycle loses zero frames. Removing or shrinking this will produce intermittent, confusing timeouts that look like a hardware fault.

Unattended operation

The app is built to be left running on a machine nobody is sitting at:

  • Connect on startup — on by default. Reconnects to the port used last time, falling back to whatever identifies as the inverter's CH340, then the first serial port. Remembering the last port matters when more than one serial device is present, so a reboot cannot attach to the wrong one. Toggle is next to the Connect button.
  • Logging starts automatically when connected, unless turned off.
  • One log file per UTC day, never deleted.
  • Failed sweeps are recorded, not skipped — see below.
  • The port reopens itself after three consecutive failures.

Recovering from a USB drop

If the adapter is unplugged and replugged, the app reopens the port on its own. Two distinct failures are handled, and the second is easy to miss:

  1. Stale handle, same port. Reopening the remembered path fixes it.
  2. The device came back on a different COM number. Windows renumbers whenever the adapter is plugged into another socket. Pinning the remembered path would fail forever, so recovery falls back to hunting the CH340 by VID/PID (1A86:7523) and adopts whatever port it now occupies, remembering the new number.

Recovery is driven from both the logger and the UI poller, deliberately — if it lived only in the logger it would silently not exist whenever logging was switched off.

What it cannot fix is an inverter that is powered but mute. That is the point of logging failures: a reopen that succeeds and still reads nothing tells you the link is fine and the device is not, which is a different fault with a different cause.

Failure records

A sweep that returns no data writes a record rather than nothing at all:

{"t":"2026-08-27T04:12:05Z","ok":false,"failed":13,"blocks":13,"err":"0x0500: no reply (timeout)"}

Without these a mute device produced no records, which is indistinguishable from the app never having run — no timestamp, no reason, nothing to correlate against.

tools/outages.py separates the two failure modes, because they have different causes: a run of failure records means the device was mute while the app polled; a gap with no records at all means the app was not running or the machine slept.

Installing

Grab the .exe installer from the latest release. After that the app updates itself — see below.

Running from source

bun install
bun run tauri dev

Note that update checks fail under tauri dev. There is no signed bundle to compare against outside a real install, so the Updates tab reports an error there. That is expected.

Updates

The app checks GitHub Releases on launch and every six hours, and verifies the release signature before installing anything. The release body is rendered as markdown in the Updates tab; raw HTML in a release body is ignored, and links open in the system browser rather than navigating the app window.

Automatic installation is opt-in and off by default. When enabled, an available update installs itself once the app has been idle for a configurable period (default 5 minutes, measured from the last mouse/keyboard/focus event).

It will not install automatically while:

  • writes are unlocked, or
  • a guarded write is in flight

Installing requires a restart, and restarting mid-configuration of a 5 kW converter is not acceptable. Those conditions are surfaced in the Updates tab when they hold off an install. Manual "Install and restart" ignores them — that is an explicit choice.

Releasing

Releases are built and published exclusively from CI — see .github/workflows/release.yml. CI gives a reproducible build from a clean checkout, an auditable record tied to a commit, and keeps the signing key in repo secrets rather than on a workstation.

To cut a release: bump version in src-tauri/tauri.conf.json, commit, then

git tag v0.1.0 && git push origin v0.1.0

The workflow refuses to build if the tag and the config version disagree. It can also be run manually via workflow_dispatch.

Required repo secrets:

Secret Purpose
TAURI_SIGNING_PRIVATE_KEY minisign key the updater verifies against
TAURI_SIGNING_PRIVATE_KEY_PASSWORD empty for a --ci-generated key

The matching public key is committed in src-tauri/tauri.conf.json. Losing the private key means installed clients can no longer verify updates from a new key — keep a backup.

Safety model

This talks to a 5 kW power converter attached to a large lithium battery. The app is built so that a mistake in the reverse-engineered map is an error message rather than damage:

  1. Read-only by default. Writes require an explicit unlock, per session.
  2. Guarded writes. Every write sends the value the UI last read as expect. The backend re-reads first and refuses if the device disagrees. If the map is wrong, or something else changed the setting, the write fails instead of landing.
  3. Verified writes. After writing, the register is read back and the app reports what the device actually holds, not what was requested.
  4. Confirmation step showing old → new in real units before anything is sent.
  5. Output voltage and frequency are deliberately not writable from this app.

Do not add a code path that bypasses the expect guard.

Write tiers

Settings are split into two tiers, because they are not equally consequential.

Tier Gate Contents
normal Unlock writes Currents, cutoff voltages, SOC thresholds
setup Unlock writes and Setup mode Battery type

Setup mode is a second, separately-armed gate with its own confirmation step. It exists because a setup register does not change one value — changing the battery type makes the inverter immediately rewrite its constant-charge, boost and float voltages to that profile's defaults, discarding anything tuned by hand.

Registers that cascade declare it (cascades: [...] in the map). After such a write the app diffs those registers and reports what the inverter actually rewrote, for example:

✓ wrote L16; device now reads L16
Charge profile rewritten by the inverter: Float voltage 55.2V → 54.4V

Leaving setup mode is one click; locking writes exits setup mode too.

Confidence

Each register carries a confidence level, shown in the UI:

Level Meaning
high Matches a documented manual default, corroborated by neighbouring registers
medium Matches a documented default, but a sibling setting shares that default — the assignment could be swapped
low Shape decoded only; meaning is a guess

Only one mapping has been confirmed by an actual round trip: 0x1103 (AC charging current), written 400 → 150 with no other register in the block changing.

Two known ambiguities. 0x1009 and 0x100a both hold 130 (52.0 V) because settings [35] and [37] share that default; which is which is unresolved. Change one on the inverter's LCD and see which register moves — that technique settles any medium entry.

How registers get identified

By correlating a log against a known physical change. The strongest evidence so far came from unplugging a wall charger while logging: charge current dropped from 19.78 A to 0.53 A in one minute, with the battery pack's own readout photographed at both moments. Diffing the log across that step gave four identifications at once:

Register before (20 A wall) after (0.5 A solar) pack readout
0x0500 543 → 54.3 V 537 → 53.7 V 54.06 / 53.69 V
0x0501 65341 → −19.5 A 65524 → −1.2 A 19.78 / 0.53 A
0x061f 1076 → 107.6 V 0 wall unplugged
0x0507 757 → 75.7 V 1157 → 115.7 V PV ~120 V

0x061f collapsing to zero exactly when mains went away is unambiguous. 0x0507 rising when charging stopped is physically right — with the pack near full the MPPT backs off and the array drifts toward open-circuit.

tools/step_diff.py and tools/analyze_log.py automate this: log across a state change, then diff or rank by correlation.

Still unidentified

PV current, load power and output power. Two registers are known-but-unnamed:

  • 0x0502 — moves with charge activity but is not SOC; it read 85 then 79 while the pack held 92%.
  • 0x0509 / 0x0510 — track each other exactly, and rose 90 → 150 as charging stopped, which rules out PV current.

Register map

See src/registers.ts for the full annotated map. Highlights:

Register Setting Meaning Scale
0x0500 Battery voltage (live) ÷10
0x0501 Battery current (live), signed, −ve = charging ÷10 A
0x0507 PV voltage (live) ÷10 V
0x061f AC input voltage (live), 0 with no mains ÷10 V
0x1003 [07] Max charging current ÷10 A
0x1007 [09] Boost / absorption voltage ×0.4 V
0x1008 [11] Float voltage ×0.4 V
0x100b [14] Under-voltage alarm ×0.4 V
0x100c [12] Over-discharge voltage ×0.4 V
0x100d [15] Discharge limit voltage ×0.4 V
0x1018 [04] Battery → Mains switchover ×0.4 V
0x1019 [05] Mains → Battery switchover ×0.4 V
0x1103 [28] AC charging current ÷10 A
0x1106 [36] Max PV charging current ÷10 A
0x0418+ Firmware build date, ASCII one char per register

Hardware note

The inverter's USB port is a device-side CH340. On the test system it enumerated fine on a Windows PC but repeatedly failed to enumerate on a Home Assistant Green, logging Cannot enable. Maybe the USB cable is bad? and taking the rest of the USB bus down with it. That points at VBUS back-feed and/or a ground-potential difference between the inverter (bonded to the battery bank) and the host. A USB isolator is the fix; a mains-earthed laptop happens to dodge the problem.

Licence

MIT