Description
Added ability to override source air conditions for IZXFER and DOAS. New optional inputs --
These values have subhourly variablity.
Motivation: support "pseudo-interior" leaks to provide relief leakage area for zones adjacent to non-modelled spaces (e.g. spaces modelled with EnergyPlus in CBECC). This required change only to pressure-dependent types, but the feature is implemented in a general fashion to support IZXFER ivNVTypes AIRNETEXT, AIRNETEXTFLOW, AIRNETEXTFAN, and AIRNETHERV plus DOAS.
Added tests and documentation for new capabilities.
No results changes for pre-existing cases.