UPS sources: a UPS is no longer necessarily an SNMP device. Every UPS entry now has
a "Read via" selector, and the second source is a NUT server (Network UPS Tools,
TCP 3493) — the answer for UPS devices with no network card, i.e. everything attached
by USB or a serial cable. Any existing upsd works: the UPS server built into a
Synology/QNAP/TrueNAS NAS, a Raspberry Pi, an OPNsense box, or a NUT install on a
Proxmox host. Configuration is host, port, the UPS name from upsd's ups.conf, and
optionally a user name and password.
PVE-UPS acts strictly as a read-only NUT client: it only ever sends LIST VAR, never
a command, and never runs upsmon. NUT is used as a device driver — the shutdown
decision, the thresholds and the host policy stay in this appliance, so there are still
no config files to write and no shutdown scripting on any host.
The UPS test now names the trigger conditions the device cannot feed at all ("This UPS
does not report: runtime remaining, battery charge"), because a threshold that can never
fire is more dangerous than a visible error. Applies to both source types — plenty of
NUT drivers omit battery.runtime, and plenty of SNMP cards omit upsEstimatedMinutesRemaining.
type field in each UPS entry of the /api/status snapshot, and the dashboard card
says which source a UPS is read through.
tests/nutsim.py, a fake upsd for development and tests — the NUT counterpart of
snmpsim + snmpdata/. Runnable standalone (python -m tests.nutsim --scenario battery)
to click through the wizard without any UPS hardware.
Changed
POST /api/test/ups replaces POST /api/test/snmp as the wizard's test endpoint and
handles every source type. The old path stays as an alias and behaves identically.
Event-log wording and trigger reasons no longer say "SNMP" where they apply to any
source ("No response for 3 polls …" instead of "No SNMP response for 3 polls …").
The fail-safe behaviour itself is unchanged.
The per-object test diagnosis was generalised from "per SNMP object (OID)" to "per
object" and gained two outcomes: missing (the driver does not publish this variable)
and stale (upsd answers, but its driver has lost contact with the UPS).
Configuration schema: UPS entries carry an explicit type (snmp or nut). Existing
configuration files and backups are migrated on load — an entry without type is read
as SNMP, exactly as before — and the field is written out on the next save.
Security
A NUT server that reports stale data (ERR DATA-STALE, ERR DRIVER-NOT-CONNECTED) is
treated as unreachable rather than as a valid reading. upsd keeps serving the last
known values when its driver dies, and accepting those would have meant reporting
"on mains" through an outage. The same applies when a driver omits ups.status
entirely: the UPS counts as unreachable (alarm, never a shutdown) instead of silently
looking healthy.