Dam SCADA
The dam SCADA at http://localhost:8120/scada is the customer's supervisory system: a web HMI that works on the customer tree only and sends operator commands back over MQTT. Real dams use IEC 61850, DNP3 or IEC 60870-5-104 here; in this environment everything, including the grid operator's MW setpoint, is an MQTT topic. It never reads the CH tree: that is the machine builder's data.
Styling follows ISA-101 like Sweet Harmony's modern HMI: muted greys, saturated colour only for alarms.

| Screen | Shows | Deep link |
|---|---|---|
| Plant overview | Reservoir and tailwater level, head, total MW against the setpoint, river flow, status of Units 1–3, spillway and bottom outlet | /scada#overview |
| Reservoir and spillway | Level against the operating limits, inflow, spillway gate positions and flow, bottom outlet; gate mode and position commands | /scada#reservoir |
| Unit detail (Unit1–3) | Mimic from inlet valve to draft tube, state, gate position and setpoint, MW against the rough zone, speed, flow, net head, the customer's bearing temperatures and cooling water flow; start, stop, emergency stop, reset, control mode, local MW setpoint | /scada#unit/Unit1 |
| Governor and HPU | Gate position vs. setpoint and governor oil pressure per unit | /scada#governor |
| Alarms and events | Active alarms by priority, acknowledge, the event journal | /scada#alarms |
| Trends | Any numeric customer tag, from the SCADA's in-memory trend store |
/scada#trends, /scada?trend=Plant/TotalMW,Plant/MWSetpoint&range=60
|

The grid operator's setpoint and AGC switch sit on the overview: they stand for the dispatcher at the other end of the line.
operator clicks Start ─► POST /api/cmd {"path": "Powerhouse/Unit1/Cmd/Start", "value": true}
─► dam-scada publishes v1.0/DRWPA/CopperCanyon/Powerhouse/Unit1/Cmd/Start (QoS 1, not retained)
─► dam-sim checks the permissives, starts the sequence, reports on Plant/Events
─► the measured topics (State, InletValveOpen, Speed, …) show the result
The SCADA journals every operator command. A refused command shows up in the journal from
Plant/Events, with the reason.
The SCADA has its own alarm engine (ISA-18.2-style). An alarm is listed while active, and stays listed after it clears until it is acknowledged (return to normal, RTN). Priorities: 1 high, 2 medium, 3 low.
Limits on customer tags (ALARMS in scada/main.py):
| Alarm | Condition | P | Delay |
|---|---|---|---|
RES_LEVEL_HH / _H
|
Reservoir > 420.5 / > 419.0 m a.s.l. | 1 / 2 | — |
RES_LEVEL_L / _LL
|
Reservoir < 387.0 / < 385.0 m a.s.l. | 2 / 1 | — |
RIVER_FLOW_L |
River flow < 10 m³/s | 1 | 30 s |
TRASH_DP_H / _HH
|
Trash rack DP > 0.5 / > 0.8 m | 3 / 2 | 10 s |
GRID_FREQ_H / _L
|
> 50.2 / < 49.8 Hz | 2 | 5 s |
PLANT_SP_UNREACHABLE |
Plant/MWSetpointReachable false |
3 | 60 s |
PENSTOCK_P_H |
Penstock pressure > 12.5 bar | 2 | — |
UNIT<n>_<BEARING>_H |
A customer bearing RTD > 75 °C | 3 | 5 s |
UNIT<n>_GOV_OIL_L |
Governor oil pressure < 54 bar | 3 | 5 s |
COMM_DAM |
No fresh dam data for 5 s | 1 | — |
Unit controller codes from Powerhouse/<unit>/ActiveAlarms become alarms too: every TRIP_*
is priority 1; BEARING_TEMP_HIGH, COOLING_WATER_FLOW_LOW, GOV_OIL_PRESSURE_LOW and
HARDWIRED_IO_FAULT priority 2.
A value older than 5 s is shown as bad quality and isn't evaluated.

| Route | |
|---|---|
GET /api/state |
Every value with its age, the alarm list, the last 40 events |
GET /api/config |
Tags, commands, alarm limits, operating zones (rough zone and max MW per head), links |
GET /api/trend?paths=a,b&minutes=60&points=300 |
Bucket means; 1 s resolution for 2 h, then 1 min for 48 h |
GET /api/events?limit=200 |
The journal |
POST /api/cmd |
{"path": "<command path>", "value": ...} |
POST /api/alarms/ack |
{"id": "..."} or {"all": true}
|
curl -s -X POST -H 'Content-Type: application/json' \
-d '{"path": "Plant/Cmd/MWSetpoint", "value": 90}' localhost:8120/api/cmdTrends and the journal are kept in memory: a restart of dam-scada starts empty.
Start
Understand
- Copper Canyon Dam
- Architecture
- Customer data vs. machine-builder data
- Example Unified Namespace
- Failure modes
- RCA demo walkthrough
- RCA with Claude: a guide for engineers
Use
- Dam SCADA
- CH asset viewer
- Instructor station
- Node-RED and MQTT Explorer
- Namespace
- Interface reference
- Configuration
For vendors
Contribute