Dam SCADA

github-actions[bot] edited this page Oct 20, 2026 · 1 revision

Dam SCADA

The dam SCADA at http://localhost:8120/scada is the customer's supervisory system: a web HMI that works on the customer tree only and sends operator commands back over MQTT. Real dams use IEC 61850, DNP3 or IEC 60870-5-104 here; in this environment everything, including the grid operator's MW setpoint, is an MQTT topic. It never reads the CH tree: that is the machine builder's data.

Styling follows ISA-101 like Sweet Harmony's modern HMI: muted greys, saturated colour only for alarms.

Dam SCADA overview

Screens

Screen Shows Deep link
Plant overview Reservoir and tailwater level, head, total MW against the setpoint, river flow, status of Units 1–3, spillway and bottom outlet /scada#overview
Reservoir and spillway Level against the operating limits, inflow, spillway gate positions and flow, bottom outlet; gate mode and position commands /scada#reservoir
Unit detail (Unit1–3) Mimic from inlet valve to draft tube, state, gate position and setpoint, MW against the rough zone, speed, flow, net head, the customer's bearing temperatures and cooling water flow; start, stop, emergency stop, reset, control mode, local MW setpoint /scada#unit/Unit1
Governor and HPU Gate position vs. setpoint and governor oil pressure per unit /scada#governor
Alarms and events Active alarms by priority, acknowledge, the event journal /scada#alarms
Trends Any numeric customer tag, from the SCADA's in-memory trend store /scada#trends, /scada?trend=Plant/TotalMW,Plant/MWSetpoint&range=60

Unit detail

The grid operator's setpoint and AGC switch sit on the overview: they stand for the dispatcher at the other end of the line.

How a command travels

operator clicks Start ─► POST /api/cmd {"path": "Powerhouse/Unit1/Cmd/Start", "value": true}
   ─► dam-scada publishes v1.0/DRWPA/CopperCanyon/Powerhouse/Unit1/Cmd/Start  (QoS 1, not retained)
   ─► dam-sim checks the permissives, starts the sequence, reports on Plant/Events
   ─► the measured topics (State, InletValveOpen, Speed, …) show the result

The SCADA journals every operator command. A refused command shows up in the journal from Plant/Events, with the reason.

Alarms

The SCADA has its own alarm engine (ISA-18.2-style). An alarm is listed while active, and stays listed after it clears until it is acknowledged (return to normal, RTN). Priorities: 1 high, 2 medium, 3 low.

Limits on customer tags (ALARMS in scada/main.py):

Alarm Condition P Delay
RES_LEVEL_HH / _H Reservoir > 420.5 / > 419.0 m a.s.l. 1 / 2 —
RES_LEVEL_L / _LL Reservoir < 387.0 / < 385.0 m a.s.l. 2 / 1 —
RIVER_FLOW_L River flow < 10 m³/s 1 30 s
TRASH_DP_H / _HH Trash rack DP > 0.5 / > 0.8 m 3 / 2 10 s
GRID_FREQ_H / _L > 50.2 / < 49.8 Hz 2 5 s
PLANT_SP_UNREACHABLE Plant/MWSetpointReachable false 3 60 s
PENSTOCK_P_H Penstock pressure > 12.5 bar 2 —
UNIT<n>_<BEARING>_H A customer bearing RTD > 75 °C 3 5 s
UNIT<n>_GOV_OIL_L Governor oil pressure < 54 bar 3 5 s
COMM_DAM No fresh dam data for 5 s 1 —

Unit controller codes from Powerhouse/<unit>/ActiveAlarms become alarms too: every TRIP_* is priority 1; BEARING_TEMP_HIGH, COOLING_WATER_FLOW_LOW, GOV_OIL_PRESSURE_LOW and HARDWIRED_IO_FAULT priority 2.

A value older than 5 s is shown as bad quality and isn't evaluated.

Alarms

API

Route
GET /api/state Every value with its age, the alarm list, the last 40 events
GET /api/config Tags, commands, alarm limits, operating zones (rough zone and max MW per head), links
GET /api/trend?paths=a,b&minutes=60&points=300 Bucket means; 1 s resolution for 2 h, then 1 min for 48 h
GET /api/events?limit=200 The journal
POST /api/cmd {"path": "<command path>", "value": ...}
POST /api/alarms/ack {"id": "..."} or {"all": true}
curl -s -X POST -H 'Content-Type: application/json' \
  -d '{"path": "Plant/Cmd/MWSetpoint", "value": 90}' localhost:8120/api/cmd

Trends and the journal are kept in memory: a restart of dam-scada starts empty.