Skip to content

Namespace

github-actions[bot] edited this page Nov 6, 2026 · 2 revisions

Namespace

Every topic on the Copper Canyon broker. The single source of truth is common/namespace.py; the generated, tested list of every concrete topic is inventory/topics.csv (see Interface reference). Both trees written out in full, with the dam's and the vendor's view explained: Example Unified Namespace.

Broker: mqtt://localhost:1884 from the host, mosquitto:1883 inside the compose network. Anonymous, no TLS. All topics start with the version v1.0/.

Customer tree

Prefix v1.0/DRWPA/CopperCanyon/. Published by the dam simulator every second, retained.

Area / module Tags
Reservoir Level (m a.s.l.), Inflow (m³/s), Volume (hm³ above 380 m)
River TailwaterLevel (m a.s.l.), Flow (m³/s)
Plant GrossHead (m), TotalMW, MWSetpoint (MW, incl. AGC), MWSetpointReachable, AGCEnabled, GridFrequency (Hz)
Intake GatePosition (%), TrashRackDP (m), RakerRunning
Penstock Pressure (bar), Flow (m³/s)
Spillway/Gate01, /Gate02 Position (%), Flow (m³/s), Mode (AUTO/MAN)
BottomOutlet ValvePosition (%), Flow (m³/s), Mode (AUTO/MAN)
Powerhouse/Unit1…Unit3 State, BreakerClosed, ControlMode (PLANT/LOCAL), MWSetpoint, MW, MVAr, GatePosition (%), GateSetpoint (%), Speed (rpm), Flow (m³/s), NetHead (m), InletValveOpen, ActiveAlarms (list of codes)
Powerhouse/Unit1…Unit3 (hardwired) ThrustBearingTemp, UpperGuideBearingTemp, LowerGuideBearingTemp, TurbineGuideBearingTemp (°C), CoolingWaterFlow (L/s), GovernorOilPressure (bar)

82 topics. State is one of Stopped, Starting, SpeedNoLoad, Synchronising, Generating, Stopping, Tripped; the ActiveAlarms codes are listed on Copper Canyon Dam.

Payload (the Sweet Harmony format):

{"value": 36.65, "unit": "MW", "timestamp": "2026-10-20T12:00:00.000Z"}

Booleans are true/false, states and modes strings, ActiveAlarms a JSON list, e.g. {"value": ["TRIP_BEARING_TEMP", "BEARING_TEMP_HIGH"], "unit": "", ...}.

Events v1.0/DRWPA/CopperCanyon/Plant/Events (not retained): commands accepted or refused, state changes, trips, raker starts.

{"timestamp": "2026-10-20T12:00:01.200Z", "source": "Unit1", "kind": "refused",
 "text": "Unit1: start refused, governor oil pressure below 55.0 bar"}

kind is command, refused, state, trip or info.

Commands

A Cmd branch next to the measured values. The dam simulator subscribes; the result shows up on the measured topics. Payload: a bare value (42, true, PLANT) or JSON {"value": ...} (optionally with "source"). For a trigger any payload works. Never retain a command: a retained Start would replay on every simulator restart.

Topic (after the prefix) Value
Plant/Cmd/MWSetpoint 0–130 MW (the grid operator)
Plant/Cmd/AGC true / false
Intake/Cmd/GatePosition 0–100 %; closing is refused while a unit is not stopped
Spillway/Gate01/Cmd/Mode, Gate02/Cmd/Mode AUTO / MAN
Spillway/Gate01/Cmd/Position, Gate02/Cmd/Position 0–100 % (switches the gate to MAN)
BottomOutlet/Cmd/Mode AUTO / MAN
BottomOutlet/Cmd/Position 0–100 % (switches to MAN)
Powerhouse/<unit>/Cmd/Start trigger
Powerhouse/<unit>/Cmd/Stop trigger
Powerhouse/<unit>/Cmd/EmergencyStop trigger
Powerhouse/<unit>/Cmd/Reset trigger (at standstill)
Powerhouse/<unit>/Cmd/ControlMode PLANT / LOCAL
Powerhouse/<unit>/Cmd/MWSetpoint 0–42 MW (switches the unit to LOCAL)
mosquitto_pub -h localhost -p 1884 -t 'v1.0/DRWPA/CopperCanyon/Plant/Cmd/MWSetpoint' -m '{"value": 90}'

CH tree

v1.0/CH/Fleet/<CustomerId>/<SiteId>/<AssetSerial>/<Subsystem>/<Component>/<Metric>, here v1.0/CH/Fleet/DRWPA/CopperCanyon/CH-FR-1987-0042/... (Unit1), CH-FR-1987-0043 (Unit2), CH-FR-1989-0051 (Unit3). The component level is left out where there is only one.

Process values (every second, retained by default)

Subsystem Tags
Context (copied from the customer tree) MW, MVAr, GatePosition_pct, NetHead_m, Speed_rpm, UnitState, TailwaterLevel_m
Bearings/Thrust PadTemp01..06, OilBathTemp, OilLevel (%), HPLiftPressure (bar)
Bearings/UGB, /LGB, /TGB PadTemp01..04, OilTemp, OilLevel (%)
Cooling WaterInletTemp, WaterFlow_TB, WaterFlow_GB, WaterFlow_AirCoolers (L/s), OilCoolerOutletTemp
Governor/HPU AccumulatorPressure (bar), SumpLevel (%), OilTemp, Pump1Running, Pump2Running, PumpStartsPerHour, FilterDP (bar), ServoPositionA, ServoPositionB, GateSetpoint (%)
Turbine SpiralCasePressure, HeadcoverPressure, DraftTubePressure (bar, gauge, 1 s mean), ShaftSealWaterFlow (L/min), HeadcoverSumpPumpStarts (counter), ShearPinStatus (OK/BROKEN), WicketGateBreakawayAlarm
Vibration/UGB, /LGB, /TGB ShaftX/Overall_um_pp, ShaftY/Overall_um_pp (µm peak-to-peak)
Vibration/Headcover Vel_mm_s_rms (mm/s)
Generator StatorTemp01..06, AirGapMin_mm
Counters Starts, RunHours, EmergencyStops, LoadRejections (kept in data/ch_plc_counters.json)

74 topics per turbine. Payload:

{"value": 61.4, "unit": "°C", "timestamp": "2026-10-20T12:00:00.000Z", "quality": "GOOD", "seq": 128734}
  • quality is GOOD, UNCERTAIN or BAD. Only the context values use the other two (stale or never received customer data). A failing sensor (scenario G) stays GOOD: the PLC doesn't know.
  • seq is one counter per PLC over every message it sends (process, waveform, events), so gaps are detectable. The CH asset viewer counts them.

Waveform blocks (not retained)

The PLC does no spectral analysis. It publishes raw blocks so edge devices can run FFT, orbit and envelope analysis themselves.

Topic (after the serial) Unit Rate Block Every Size
Vibration/UGB/ShaftX/Waveform, ShaftY, same for LGB, TGB (6 channels) µm 1 kS/s 4 s = 4,000 samples 30 s ~25 KB each
Vibration/DraftTube/Pressure/Waveform bar (gauge) 100 S/s 10 s = 1,000 samples 30 s ~8 KB
Vibration/Headcover/Accel/Waveform m/s² 10 kS/s 0.5 s = 5,000 samples 5 min ~35 KB

Plus every block of the turbine right away when a vibration or shear-pin alarm is raised (at most once per 30 s). Interval, length and the number of detailed turbines are environment variables (see Configuration).

{"timestamp": "2026-10-20T09:24:00.000Z", "seq": 22197, "sampleRate": 1000, "samples": 4000,
 "unit": "µm", "speedRpm": 300.2, "keyphasorIdx": [13, 213, 413], "trigger": "periodic",
 "values": [12.4, 13.1, ...]}
  • timestamp is the time of the first sample; sample i is at timestamp + i / sampleRate.
  • keyphasorIdx lists the sample index of each shaft revolution mark, so orbits and phase work without a separate channel. Empty when the shaft stands still.
  • trigger is periodic, alarm or manual.
  • Rounding: shaft displacement 1 decimal (µm), draft-tube pressure 3 decimals (bar), accelerometer 2 decimals (m/s²). The design basis says 1 decimal; bar and m/s² need more.

Events, nameplate, status

Topic (after the serial) Retained Content
Events/Alarm no One message per PLC alarm raised or cleared
Events/ActiveAlarms yes The list of active PLC alarm ids, after every change
_meta/Nameplate yes The digital nameplate
_meta/Status yes ONLINE, or OFFLINE (MQTT last will) — a plain string, not JSON
{"timestamp": "2026-10-20T12:14:03.000Z", "seq": 130211, "serial": "CH-FR-1987-0042",
 "alarmId": "TGB_PAD03_H", "state": "ACTIVE", "severity": "WARNING",
 "tag": "Bearings/TGB/PadTemp03", "value": 75.12, "limit": 75.0, "text": "TGB pad 3 temperature high"}

state is ACTIVE or CLEARED, severity WARNING or CRITICAL. The alarm ids and limits are on Failure modes.

The nameplate carries the serial, manufacturer, product line, model CH-FR-V40-100, rated power, head, flow and speed, runner blades and wicket gates, the commissioning year, the PLC retrofit year and firmware, the data model version, the customer (id, name, site, unitName, unitTag) and the list of waveform channels with their rate, samples and interval.

Data rates

About 18 KB/s per turbine with the defaults (~74 messages/s): ~12 KB/s of process values (the long topics count) and ~6 KB/s of waveforms. The customer tree adds ~7 KB/s. The live figures per turbine are in the CH asset viewer, or:

curl -s localhost:8122/api/assets | python3 -m json.tool | grep -E '"(kbytes|msgs)_per_s"'

Subscribing

mosquitto_sub -h localhost -p 1884 -t 'v1.0/CH/#' -v                       # the CH tree (busy)
mosquitto_sub -h localhost -p 1884 -t 'v1.0/DRWPA/CopperCanyon/Plant/#' -v  # plant values + events
mosquitto_sub -h localhost -p 1884 -t 'v1.0/CH/Fleet/+/+/+/Events/Alarm' -v # every CH alarm

Python (paho-mqtt 2.x):

import json, paho.mqtt.client as mqtt

def on_message(client, userdata, msg):
    p = json.loads(msg.payload)
    print(msg.topic, p["value"], p.get("quality"), p.get("seq"))

c = mqtt.Client(mqtt.CallbackAPIVersion.VERSION2, client_id="my-edge-device")
c.on_message = on_message
c.connect("localhost", 1884)
c.subscribe("v1.0/CH/Fleet/DRWPA/CopperCanyon/CH-FR-1987-0042/Bearings/#")
c.loop_forever()

Inside the compose network use host mosquitto, port 1883.