Every topic on the Copper Canyon broker. The single source of truth is
common/namespace.py;
the generated, tested list of every concrete topic is
inventory/topics.csv
(see Interface reference). Both trees written out in full, with the
dam's and the vendor's view explained: Example Unified Namespace.
Broker: mqtt://localhost:1884 from the host, mosquitto:1883 inside the compose network.
Anonymous, no TLS. All topics start with the version v1.0/.
Prefix v1.0/DRWPA/CopperCanyon/. Published by the dam simulator every second, retained.
| Area / module | Tags |
|---|---|
Reservoir |
Level (m a.s.l.), Inflow (m³/s), Volume (hm³ above 380 m) |
River |
TailwaterLevel (m a.s.l.), Flow (m³/s) |
Plant |
GrossHead (m), TotalMW, MWSetpoint (MW, incl. AGC), MWSetpointReachable, AGCEnabled, GridFrequency (Hz) |
Intake |
GatePosition (%), TrashRackDP (m), RakerRunning
|
Penstock |
Pressure (bar), Flow (m³/s) |
Spillway/Gate01, /Gate02
|
Position (%), Flow (m³/s), Mode (AUTO/MAN) |
BottomOutlet |
ValvePosition (%), Flow (m³/s), Mode (AUTO/MAN) |
Powerhouse/Unit1…Unit3
|
State, BreakerClosed, ControlMode (PLANT/LOCAL), MWSetpoint, MW, MVAr, GatePosition (%), GateSetpoint (%), Speed (rpm), Flow (m³/s), NetHead (m), InletValveOpen, ActiveAlarms (list of codes) |
Powerhouse/Unit1…Unit3 (hardwired) |
ThrustBearingTemp, UpperGuideBearingTemp, LowerGuideBearingTemp, TurbineGuideBearingTemp (°C), CoolingWaterFlow (L/s), GovernorOilPressure (bar) |
82 topics. State is one of Stopped, Starting, SpeedNoLoad, Synchronising, Generating,
Stopping, Tripped; the ActiveAlarms codes are listed on Copper Canyon Dam.
Payload (the Sweet Harmony format):
{"value": 36.65, "unit": "MW", "timestamp": "2026-10-20T12:00:00.000Z"}Booleans are true/false, states and modes strings, ActiveAlarms a JSON list, e.g.
{"value": ["TRIP_BEARING_TEMP", "BEARING_TEMP_HIGH"], "unit": "", ...}.
Events v1.0/DRWPA/CopperCanyon/Plant/Events (not retained): commands accepted or refused,
state changes, trips, raker starts.
{"timestamp": "2026-10-20T12:00:01.200Z", "source": "Unit1", "kind": "refused",
"text": "Unit1: start refused, governor oil pressure below 55.0 bar"}kind is command, refused, state, trip or info.
A Cmd branch next to the measured values. The dam simulator subscribes; the result shows up on
the measured topics. Payload: a bare value (42, true, PLANT) or JSON {"value": ...}
(optionally with "source"). For a trigger any payload works. Never retain a command: a
retained Start would replay on every simulator restart.
| Topic (after the prefix) | Value |
|---|---|
Plant/Cmd/MWSetpoint |
0–130 MW (the grid operator) |
Plant/Cmd/AGC |
true / false
|
Intake/Cmd/GatePosition |
0–100 %; closing is refused while a unit is not stopped |
Spillway/Gate01/Cmd/Mode, Gate02/Cmd/Mode
|
AUTO / MAN
|
Spillway/Gate01/Cmd/Position, Gate02/Cmd/Position
|
0–100 % (switches the gate to MAN) |
BottomOutlet/Cmd/Mode |
AUTO / MAN
|
BottomOutlet/Cmd/Position |
0–100 % (switches to MAN) |
Powerhouse/<unit>/Cmd/Start |
trigger |
Powerhouse/<unit>/Cmd/Stop |
trigger |
Powerhouse/<unit>/Cmd/EmergencyStop |
trigger |
Powerhouse/<unit>/Cmd/Reset |
trigger (at standstill) |
Powerhouse/<unit>/Cmd/ControlMode |
PLANT / LOCAL
|
Powerhouse/<unit>/Cmd/MWSetpoint |
0–42 MW (switches the unit to LOCAL) |
mosquitto_pub -h localhost -p 1884 -t 'v1.0/DRWPA/CopperCanyon/Plant/Cmd/MWSetpoint' -m '{"value": 90}'v1.0/CH/Fleet/<CustomerId>/<SiteId>/<AssetSerial>/<Subsystem>/<Component>/<Metric>, here
v1.0/CH/Fleet/DRWPA/CopperCanyon/CH-FR-1987-0042/... (Unit1), CH-FR-1987-0043 (Unit2),
CH-FR-1989-0051 (Unit3). The component level is left out where there is only one.
| Subsystem | Tags |
|---|---|
Context (copied from the customer tree) |
MW, MVAr, GatePosition_pct, NetHead_m, Speed_rpm, UnitState, TailwaterLevel_m
|
Bearings/Thrust |
PadTemp01..06, OilBathTemp, OilLevel (%), HPLiftPressure (bar) |
Bearings/UGB, /LGB, /TGB
|
PadTemp01..04, OilTemp, OilLevel (%) |
Cooling |
WaterInletTemp, WaterFlow_TB, WaterFlow_GB, WaterFlow_AirCoolers (L/s), OilCoolerOutletTemp
|
Governor/HPU |
AccumulatorPressure (bar), SumpLevel (%), OilTemp, Pump1Running, Pump2Running, PumpStartsPerHour, FilterDP (bar), ServoPositionA, ServoPositionB, GateSetpoint (%) |
Turbine |
SpiralCasePressure, HeadcoverPressure, DraftTubePressure (bar, gauge, 1 s mean), ShaftSealWaterFlow (L/min), HeadcoverSumpPumpStarts (counter), ShearPinStatus (OK/BROKEN), WicketGateBreakawayAlarm
|
Vibration/UGB, /LGB, /TGB
|
ShaftX/Overall_um_pp, ShaftY/Overall_um_pp (µm peak-to-peak) |
Vibration/Headcover |
Vel_mm_s_rms (mm/s) |
Generator |
StatorTemp01..06, AirGapMin_mm
|
Counters |
Starts, RunHours, EmergencyStops, LoadRejections (kept in data/ch_plc_counters.json) |
74 topics per turbine. Payload:
{"value": 61.4, "unit": "°C", "timestamp": "2026-10-20T12:00:00.000Z", "quality": "GOOD", "seq": 128734}-
qualityisGOOD,UNCERTAINorBAD. Only the context values use the other two (stale or never received customer data). A failing sensor (scenario G) staysGOOD: the PLC doesn't know. -
seqis one counter per PLC over every message it sends (process, waveform, events), so gaps are detectable. The CH asset viewer counts them.
The PLC does no spectral analysis. It publishes raw blocks so edge devices can run FFT, orbit and envelope analysis themselves.
| Topic (after the serial) | Unit | Rate | Block | Every | Size |
|---|---|---|---|---|---|
Vibration/UGB/ShaftX/Waveform, ShaftY, same for LGB, TGB (6 channels) |
µm | 1 kS/s | 4 s = 4,000 samples | 30 s | ~25 KB each |
Vibration/DraftTube/Pressure/Waveform |
bar (gauge) | 100 S/s | 10 s = 1,000 samples | 30 s | ~8 KB |
Vibration/Headcover/Accel/Waveform |
m/s² | 10 kS/s | 0.5 s = 5,000 samples | 5 min | ~35 KB |
Plus every block of the turbine right away when a vibration or shear-pin alarm is raised (at most once per 30 s). Interval, length and the number of detailed turbines are environment variables (see Configuration).
{"timestamp": "2026-10-20T09:24:00.000Z", "seq": 22197, "sampleRate": 1000, "samples": 4000,
"unit": "µm", "speedRpm": 300.2, "keyphasorIdx": [13, 213, 413], "trigger": "periodic",
"values": [12.4, 13.1, ...]}-
timestampis the time of the first sample; sample i is attimestamp + i / sampleRate. -
keyphasorIdxlists the sample index of each shaft revolution mark, so orbits and phase work without a separate channel. Empty when the shaft stands still. -
triggerisperiodic,alarmormanual. - Rounding: shaft displacement 1 decimal (µm), draft-tube pressure 3 decimals (bar), accelerometer 2 decimals (m/s²). The design basis says 1 decimal; bar and m/s² need more.
| Topic (after the serial) | Retained | Content |
|---|---|---|
Events/Alarm |
no | One message per PLC alarm raised or cleared |
Events/ActiveAlarms |
yes | The list of active PLC alarm ids, after every change |
_meta/Nameplate |
yes | The digital nameplate |
_meta/Status |
yes |
ONLINE, or OFFLINE (MQTT last will) — a plain string, not JSON |
{"timestamp": "2026-10-20T12:14:03.000Z", "seq": 130211, "serial": "CH-FR-1987-0042",
"alarmId": "TGB_PAD03_H", "state": "ACTIVE", "severity": "WARNING",
"tag": "Bearings/TGB/PadTemp03", "value": 75.12, "limit": 75.0, "text": "TGB pad 3 temperature high"}state is ACTIVE or CLEARED, severity WARNING or CRITICAL. The alarm ids and limits are
on Failure modes.
The nameplate carries the serial, manufacturer, product line, model CH-FR-V40-100, rated power,
head, flow and speed, runner blades and wicket gates, the commissioning year, the PLC retrofit year
and firmware, the data model version, the customer (id, name, site, unitName, unitTag)
and the list of waveform channels with their rate, samples and interval.
About 18 KB/s per turbine with the defaults (~74 messages/s): ~12 KB/s of process values (the long topics count) and ~6 KB/s of waveforms. The customer tree adds ~7 KB/s. The live figures per turbine are in the CH asset viewer, or:
curl -s localhost:8122/api/assets | python3 -m json.tool | grep -E '"(kbytes|msgs)_per_s"'mosquitto_sub -h localhost -p 1884 -t 'v1.0/CH/#' -v # the CH tree (busy)
mosquitto_sub -h localhost -p 1884 -t 'v1.0/DRWPA/CopperCanyon/Plant/#' -v # plant values + events
mosquitto_sub -h localhost -p 1884 -t 'v1.0/CH/Fleet/+/+/+/Events/Alarm' -v # every CH alarmPython (paho-mqtt 2.x):
import json, paho.mqtt.client as mqtt
def on_message(client, userdata, msg):
p = json.loads(msg.payload)
print(msg.topic, p["value"], p.get("quality"), p.get("seq"))
c = mqtt.Client(mqtt.CallbackAPIVersion.VERSION2, client_id="my-edge-device")
c.on_message = on_message
c.connect("localhost", 1884)
c.subscribe("v1.0/CH/Fleet/DRWPA/CopperCanyon/CH-FR-1987-0042/Bearings/#")
c.loop_forever()Inside the compose network use host mosquitto, port 1883.
Start
Understand
- Copper Canyon Dam
- Architecture
- Customer data vs. machine-builder data
- Example Unified Namespace
- Failure modes
- RCA demo walkthrough
- RCA with Claude: a guide for engineers
Use
- Dam SCADA
- CH asset viewer
- Instructor station
- Node-RED and MQTT Explorer
- Namespace
- Interface reference
- Configuration
For vendors
Contribute