Enhancements
- 3D airflow rainbow: particles tint along the path from AC supply → cold aisle → hot aisle → return (blue–green–yellow–red). Missing hot-aisle sensors interpolate until those probes are placed. Vents/returns use live supply/return color.
- 3D active/standby from SNMP: CRAC labels and a green/amber LED follow Unity system state (On = active, Off/Standby = standby) instead of only the manual role field.
- NOC cooling pane: live supply/return, aisle averages, SNMP active/standby, per-unit S/R/RH, and a 24h temperature history chart (supply, cold aisle, hot aisle, return). Poll writes
cooling_readingsfor the graph.
Bug fixes
- Liebert “sun surface” temps: Unity returns Integer32/Unsigned32 max (
2147483647/4294967295) when a sensor is not equipped. Those were stored as chilled-water 214748364.7° and compressor temps. Poll now drops SNMP not-available sentinels instead of converting them.