Real devices and networks fail in a handful of typical ways. Each recipe below shows the failure, the modbus-sim fault that reproduces it, and a pytest test for the code that has to cope. They use pymodbus as the master (tested with 3.16) and the devices of the Browser demo; all of them run as they are against modbus-sim 0.2.0.

import time

import pytest
from pymodbus.client import ModbusTcpClient
from pymodbus.exceptions import ConnectionException, ModbusIOException

BENCH = {"devices": [
    {"profile": "eastron-sdm630", "unit": 1, "name": "meter"},
    {"profile": "omron-e5cc", "unit": 2, "name": "controller"},
    {"profile": "sunspec-inverter", "unit": 3, "name": "inverter"},
]}


@pytest.fixture
def bench(modbus_bench_factory):
    return modbus_bench_factory(BENCH)


@pytest.fixture
def client(bench):
    c = ModbusTcpClient("127.0.0.1", port=bench.port, timeout=0.5, retries=0)
    c.connect()
    yield c
    c.close()


def read_voltage(client):
    r = client.read_input_registers(0, count=2, device_id=1)
    return client.convert_from_registers(r.registers, client.DATATYPE.FLOAT32)

Faults are switched with bench.inject(device, kind, **params) in tests, or modbus-sim inject <device> <kind> name=value … against a running server. The complete list with parameters is in the README. Faults with a count wear off after that many requests; the others stay until cleared.

The device does not answer

Real life: a meter with a loose RS-485 wire, a gateway that lost the slave, a device rebooting. pymodbus raises ModbusIOException after its timeout; code that does not catch it stops polling everything else.

def read_voltage_or_none(client):
    try:
        return read_voltage(client)
    except ModbusIOException:
        return None


def test_meter_silent(bench, client):
    bench.inject("meter", "no_response")               # count=1
    assert read_voltage_or_none(client) is None
    assert read_voltage_or_none(client) > 200          # the next one answers

no_response with count=null keeps the device silent until you clear it; delay seconds=1.5 answers late instead — useful to find the timeout your code really uses.

The device is busy, or answers an exception

Real life: a device answers exception 06 (server device busy) while it writes its flash, or 04 (server device failure) when something inside broke. The request did not fail at the transport level — isError() is the check.

def test_busy(bench, client):
    bench.inject("meter", "busy")
    r = client.read_input_registers(0, count=2, device_id=1)
    assert r.isError() and r.exception_code == 6


def test_exception_on_one_function(bench, client):
    bench.inject("controller", "exception", code=4, function=3, count=3)
    r = client.read_holding_registers(0x2000, count=1, device_id=2)
    assert r.isError() and r.exception_code == 4

function=3 limits the fault to one function code, so writes still work — good for testing that a read failure does not stop the control loop.

The connection drops

Real life: a gateway closes idle connections, a switch restarts, a firewall drops the session. pymodbus raises ConnectionException; the client must reconnect.

def test_reconnect(bench, client):
    bench.inject("meter", "drop_connection")
    with pytest.raises(ConnectionException):
        read_voltage(client)
    client.close()
    client.connect()
    assert read_voltage(client) > 200

A value runs away

Real life: a drifting sensor, a bad current transformer, a wrong scale factor in a configuration. Your plausibility checks and alarms should catch it.

def test_drift(bench, client):
    bench.inject("meter", "drift", point="voltage_l1", per_second=20)
    time.sleep(1.5)
    assert read_voltage(client) > 253          # +10 %: your over-voltage alarm should fire

freeze is the opposite: values stop changing, as when a device hangs but its Modbus stack still answers. Watchdogs that look for changing values should catch that.

The process itself fails

Device faults change what the model reports — the registers stay valid, the values say something is wrong.

def test_phase_loss(bench, client):
    bench.inject("meter", "phase_loss", phase=2)
    r = client.read_input_registers(0, count=6, device_id=1)
    v = client.convert_from_registers(r.registers, client.DATATYPE.FLOAT32)
    assert v[1] == 0.0 and v[0] > 200


def test_sensor_break(bench, client):
    bench.inject("controller", "sensor_break")
    r = client.read_holding_registers(0x2000, count=2, device_id=2)
    assert r.registers[0] == 0x7FFF and r.registers[1] & 1 << 6    # PV, input error bit


def test_grid_loss(bench, client):
    bench.inject("inverter", "grid_loss")
    r = client.read_holding_registers(40108, count=4, device_id=3)
    state, _vendor, evt_hi, evt_lo = r.registers
    assert state == 7 and (evt_hi << 16 | evt_lo) & 1 << 4         # fault, grid disconnect

The device refuses a write

Real life: not a fault but a rule of the device — and a classic first-day bug. The E5CC answers exception 04 to every write while communications writing is off (see Real-device profiles). A driver should handle it once, explicitly:

def set_point(client, celsius, unit=2):
    r = client.write_register(0x2103, round(celsius * 10), device_id=unit)
    if r.isError() and r.exception_code == 4:              # communications writing off
        client.write_register(0x0000, 0x0001, device_id=unit)
        r = client.write_register(0x2103, round(celsius * 10), device_id=unit)
    return not r.isError()


def test_set_point_enables_writing(client):
    assert set_point(client, 150)
    r = client.read_holding_registers(0x2002, count=1, device_id=2)
    assert r.registers == [1500]

Transport-level faults

For code that parses frames itself (gateways, protocol stacks, your own master):

Fault What happens
bad_crc RTU: the answer has a wrong CRC — a correct master discards it and times out
wrong_transaction TCP: the answer carries another transaction ID — a correct master must not accept it as the answer to its request
wrong_unit the answer comes from another unit ID
truncate bytes=N the answer is cut short by N bytes