Troubleshooting
Connection refused. modbus-sim serve listens on 127.0.0.1:5020 by
default. A master on another machine, in a VM or in a Docker container needs
--host 0.0.0.0 (and the right port: 5020, not 502). Check with
modbus-sim list on the simulator's machine.
Connected, but every request times out.
- Wrong framing: a master that sends RTU frames over TCP (many gateways and
some SCADA drivers call it "RTU over TCP" or "encapsulated") needs
--rtu-over-tcp; a plain Modbus TCP master needs the default. - On RTU, an unknown unit ID gets no answer at all — exactly as on a real bus.
modbus-sim listshows the unit IDs. - A fault is still active:
modbus-sim listshows the faults per device,modbus-sim clear <device>removes them.
Exception 0x0B (gateway target failed to respond). On Modbus TCP, a unit ID
that no device has answers 0x0B, like a gateway. Check the unit ID (pymodbus:
device_id=, older versions slave=).
-
Off by one. Manuals often give 1-based register numbers (30001, 40001);
the frame carries the 0-based address. Register 30071 is
input 70(0x46), 40001 isholding 0.modbus-sim map <profile>prints both columns. - Wrong table. Input registers (function 04) and holding registers (function 03) are separate. The SDM630's measurements are input registers; the E5CC and the SunSpec map use holding registers only.
-
A gap in the map. Profiles with
gaps: error(the default, andsunspec-inverter) answer 02 for unmapped addresses, so a block read across a gap fails.eastron-sdm630andomron-e5ccread gaps as 0. - Read-only. Writing a read-only point answers 02, like many real devices.
- Half a value. A write that would change only one register of a 32- or 64-bit value answers 02.
- The value is outside the point's
min/max(modbus-sim mapshows the limits), or the request quantity is out of range (more than 125 registers in one read, 123 in one write). - E5CC: a wrong operation command code or related information.
Communications writing is off. Write 0x0001 to address 0x0000 (function
06) first. See Real-device profiles.
Huge or tiny floats (1.65e+24, 1.6e-23). Word order. The same four
bytes, decoded with the 16-bit words swapped. The SDM630 sends ABCD (most
significant register first); many other meters send CDAB. Try
modbus-sim read … -t float32 -o CDAB against the device's profile to see
both.
An integer that is ten or a hundred times too big. Scale. The E5CC sends
tenths of a degree (1500 = 150.0 °C), SunSpec values need their scale
factor register (A × 10^A_SF). --scale 0.1 in the CLI, or your client's
equivalent.
65535 / -32768 / 0xFFFFFFFF on a SunSpec device. That is SunSpec's "not implemented" value, not a reading. Treat it as missing.
3276.7 on a temperature. 0x7FFF — the controller's way of saying "input error" (sensor break). The E5CC also sets bit 6 in its status word.
A negative power factor on the SDM630. Correct per Eastron's protocol: negative for inductive loads.
- Models run on the real clock. A controller with a time constant of minutes
heats for minutes;
model_params: {time_scale: 10}speeds it up. - The SunSpec inverter sleeps at night (simulated 20:00–6:00; it starts at
noon). With
time_scale: 120a day passes in 12 minutes. - A
freezefault stops all values;modbus-sim listshows it.
-
--ptyprints the device to open (/dev/pts/N) and only works on Linux and macOS; the name changes on every start. - Over a pty, baud rate and parity are not simulated: any setting of the master
works. On a real serial port (
--serial) they must match. - Windows: use a virtual null-modem pair (com0com) and
--serial COMx. - Unit 0 on RTU is a broadcast: writes reach every device, nobody answers.
Run the request with the CLI to see the raw registers ([4366 1741]), compare
with the profile (modbus-sim map), and if the simulator seems wrong, open an
issue with the command, the
output and the profile.