IS3 Export

hacs Validate

English · Česky

UNOFFICIAL Home Assistant integration for iNELS central units (ELKO EP) over their ASCII interface — primarily the older CU3-01M and CU3-02M. It talks to the unit directly and needs no Connection Server.

The "IS3" in the name is iNELS3 — the .is3 export format the integration is based on.

It downloads the device list from the export the unit serves itself. It tracks state live: the unit pushes changes on its own, so nothing is polled.

Status: experimental. The protocol is verified against a live unit, the parser against exports from seven installations (17 to 1125 items, IDM3 03-03-34 through 03-05-03). Blinds on a real drive remain unverified — see Limitations.

❗ First enable the protocol in IDM3

Without this nothing works — the unit isn't listening on the ASCII port.

In iNELS IDM3Central unit configurationThird part setting:

Item What to do
Port Pick a free port. There's no default, so write it down.
Separator Must match the integration's setting. [32] is a space.
Number base Must match the integration's setting.
Mode Remote control + IDM

On the right, tick the events the unit should send. Whatever you don't tick, the integration will never learn about, and the entity stays stuck at its last value:

  • Digital_OUT_SwitchOn / SwitchOff — relays (without them you won't catch a switch flip)
  • Analog_OUT_ValueChanged, Analog_OUT_SwitchOn / SwitchOff — dimmers
  • Analog_IN_ValueChange, Sensor_Change — temperatures, humidities, analog inputs
  • Digital_IN_SwitchOn / SwitchOff — inputs and buttons
  • SysInt_Change, Program_ValueSwitchOn / Off — system variables

Finally, Save to CU.

How fast state shows up in Home Assistant depends on these checkboxes. The unit is also driven by switches on the walls, so a change need not come from HA — and it's only detected from an event. What has its own event updates within a second or so; what doesn't, only on the periodic re-read (30 s). The variability with changes from the wall (instant vs. 2–3 s) is the unit's own delay before it sends the change over ASCII, not the integration's.

Commands from HA itself show up immediately, and the integration then verifies them by reading back — if the output didn't take, or a switch on the wall flipped it in the meantime, the state corrects itself to reality instead of leaving the icon stuck in the wrong state.

Installation

Add repository to HACS

Then Download, restart Home Assistant, and:

Add integration

Manually: copy custom_components/is3_export into config/custom_components/.

Configuration

Field Description Default
Host The unit's IP address
ASCII port from IDM3 (default 1111) 1111
Export file path leave empty, it downloads from the unit empty
Separator from IDM3, offers all 27 options space [32]
Number base from IDM3 hexadecimal

The integration's name is taken from the export header.

No password is entered. The unit's web server serves the export as a static file with no login, so the iNELS project password has no effect on its availability. (If some unit blocks the download anyway, enter the path to a locally downloaded export.)

If entities report an estimated state, your separator or number base is wrong — Home Assistant raises a repair issue to say so. You can correct it without removing the integration: Settings → Devices & services → IS3 Export → ⋮ → Reconfigure.

Removing the integration

Settings → Devices & services → IS3 Export → ⋮ → Delete. This closes the connection and removes every entity and device the integration created. Nothing is left behind on the central unit — the integration only ever talked to it over the network — and no files are written outside custom_components/is3_export.

Which addresses become entities

The second byte of the address determines the type:

Address Meaning Entity Write
0x0102 relay switch
0x0104 dimmer (with % unit) light 0–100 %
0x0203 SYSTEMBIT switch
0x0202 SYSTEMINTEGER number
address pair blind cover
controller channels heating zone climate
0x0101 inputs, buttons, controller status outputs binary_sensor
0x0107 module faults binary_sensor (problem)
0x0105 temperature / humidity sensor
0x0108 analog input sensor
0x0103, 0x0111, 0x0112 controller channels sensor
0x0206 water meters, electricity meters sensor (total)
0x0501, 0x0204, 0x0209, 0x0003 plans, groups, schedules

Writes happen only where a write is documented. Never to inputs, thermostat channels, or plans.

The hardware ID decides, not the name: anything starting with Controller_ is controller internals and is not written to — a window sensor sits in the same range as a relay. Conversely, an unnamed relay (_ SA3-04M_RE2_…) is still a relay.

Names refine the entity type

The address says what the output is; the name says what it's for. A pulse and a lamp are the same as far as the address is concerned.

In the name Entity Icon
imp button
sv light light bulb
lamp light floor lamp
zrc light mirror
LED light LED strip
vent switch fan
zas switch socket
TL (or DIN input) event (press + long_press)

sv, imp, vent, zas, and TL must match as a whole token (otherwise Svod_vody would be a light and Zastineni a socket); lamp, zrc, and LED are enough as a prefix.

TL_ (button) makes an event button on any module. A DIN input is a button on wall controllers and on the central unit itself (In-Out); on other modules (e.g. the IM3 input module) DIN is a plain binary_sensor (a maintained contact) until you name it TL_. A wired button distinguishes both press and long_press (see Wall switches).

A button (imp) sends a pulse on press — the bit to 1 and straight back to 0. The idle state is always 0, so every next press is again a clean rising edge that the iNELS program reacts to. (Holding 1 would work only once; the unit doesn't zero the bit itself.) It splits on _ and -, and case doesn't matter. The more specific one wins: imp_sv_chodba is a button.

The light and switch conventions (sv, lamp, zrc, LED, vent, imp) apply only to physical relays/dimmers and never turn anything into a writable entity — an input named Sv_okno stays a binary_sensor, and the system bit blok_noc_lamp stays a switch. Conversely, TL/DIN apply only to digital inputs (they won't make a button out of a relay).

There are deliberately no more rules. If something comes out differently, override the entity type or icon manually in Home Assistant.

Blinds

They combine several addresses into one cover entity, from two possible sources:

  1. System bits of the blind program — up, down, stop, tilt. The program in the unit drives the contacts itself. It takes priority.
  2. A pair of JA3 relays — only up and down, stop by releasing both. Used only when there's no program in the export.

Addresses taken by a blind no longer appear as switches.

Heating zones

A heating controller is a set of channels with the same serial suffix plus a named root <name> Controller_<serial>. Together they form one climate entity:

Channel
current temperature Actual-Therm-AOUT
target temperature Required-Therm-AOUT (heating) / Required-Cool-Therm-AOUT (cooling)
heats / cools Required-Heat-DOUT / Required-Cool-DOUT
preset Control-Manual-IN — 0 Schedule, 1–4 Preset 1–4, 7 Manual
heating / cooling Control-HC-IN — 0 heating, 1 cooling
on / off Control-IN — 0 off, 1 on

The Cool mode is offered for a zone only when it actually has a cooling output wired. The cooling channels (Control-HC-IN, Required-Cool-*) are carried by every zone, so their presence isn't enough — the capability is only recognized from the controller's root row: a heating zone has flags 0x05 with empty cooling schedule slots, a zone with cooling 0x3F with filled ones (verified on the unit). Where Cool is available, it's switched via Control-HC-IN, and cooling has its own setpoints: Required-Cool-Therm-AOUT (in effect) and Manual-Cool-Therm-AIN (manual).

Setting the temperature switches the zone into Manual and writes Manual-Therm-AIN (heating), or Manual-Cool-Therm-AIN (cooling). Preset values 1–4 and the weekly plan behind Schedule (HEATCOOL_WEEK) are set on the unit.

Watch out for one pitfall (handled): writing the setpoint immediately after switching into Manual corrupts it — the value drops below frost protection (~0.1 °C), and the heating relay with it, and the zone stops heating. So after switching, the integration waits, then writes the setpoint and verifies it by reading back, repeating the write if needed. Manual is value 7, not 5 — a five drops the zone to frost protection.

Each zone also has a select plan — Normal / Vacation / Holiday (Control-Plan-IN 0 / 64 / 128, all verified on a live unit). Holiday is a daily program (HEATCOOL_DAY) and must be configured on the unit; where it isn't, the switch doesn't take and the read-back squares the plan back in the UI.

Wall switches (WSB3)

A single switch breaks down into one entity per channel — nothing is special-cased, it follows from the address type:

Type Breakdown into entities
WSB3-20 8 — 2 buttons (up/down) + 2 LEDs (green/red) + 2 temperatures + 2 digital inputs
WSB3-40 12 — 4 buttons + 4 LEDs + 2 temperatures + 2 digital inputs
WSB3-*-Hum +2 — humidity (%, device_class humidity) and dew point (°C)

The indicator LEDs (roles Green/Red) are switches with a G/R icon — it's recognized from the role, so even unnamed ones (_) get it.

Buttons (Up/Down/DIN) are an event entity. Wired switches (WSB) distinguish a short press and long_press; the buttons of an RF controller report only press.

The same recognition applies to the whole family of wall controllers — besides WSB3, also the glass/touch GSB3, GSP3, MSB3, GBP3, GRT3, the card readers GMR3/GCR3/GHR3/GCH3, the info panels GDB3, WMR3, and the room controller IDRT3 (all wired → press+long_press). The RFKEY remote is all buttons (only press). IBWL (RF input module) is different — each of its inputs mirrors a paired RF device (a button, but also a door/motion sensor), which we can't tell from the export, so it's a binary_sensor by default; to make a particular input a press, name it TL_. A proximity sensor and a card reader are not treated as buttons.

How short/long works: telling them apart needs the hold duration = the gap between the close (=1) and the open (=0). On a wired switch this gap is clean and consistent — taps fall under ~100 ms, deliberate holds over ~1.5 s, with a wide empty gap in between. So on the close the integration starts a timer: if the open arrives first, it's a short press; when the timer (1.5 s, the same as long-press in iNELS) runs out and the button is still held, it's a long_press — it fires right at that moment, without waiting for release, so the long-press action kicks in on time. A lost open won't stick the button — a safety timer releases it.

⚠️ A condition for reliable short/long: no running Connection Server. Its periodic polling freezes the unit for a few seconds and smears the hold duration (see the Connection Server slows the response section below). That originally made this look like a dead end; under clean conditions the timing is reliable.

RF controllers stay on press only — their open is lost too often, and the hold duration there isn't reliable. For them press fires on every close event; buttons are meanwhile not deduplicated (the integration normally wakes an entity only on a value change) so that a lost open doesn't hide the next press — otherwise the next press would be "no change" and get discarded (hence the earlier "I have to press 3×"). A short debounce (~0.5 s) swallows only an immediate double-send of the same press.

Sensors, by contrast, are throttled (max ~1 notification/s) so that a chatty analog input of the CU doesn't flood the loop — the value keeps being stored, only the state isn't written constantly. This keeps button handling snappy.

The RF controller's battery status is a plain binary_sensor (battery), not a button.

Split into devices

Every physical module (by the serial number in the hardware ID) is its own device in HA, nested under the central unit. So the channels of one switch, relay board, or dimmer stay together — you can tell which Green1 belongs to which switch. System things (bits, integers, buttons) have no module and remain directly on the central unit.

Hidden by default

Large installations export hundreds of panel internals — button contacts, indicator LEDs, fault flags. Entities are created from them, but they are disabled by default. You enable them in the integration settings. Unnamed ones get their name from the role in the hardware ID (e.g. Up, Green), not from the whole ID.

Also disabled are the SW status inputs of relays and the fault/alert flags (OUF-Alert, type 0x0107) — even when they're named, because hardly anyone watches them. An alert has device_class problem and is diagnostic.

RF devices

A device on an RF module (e.g. RFKEY — remotes) appears as its own device with buttons (binary_sensor), and the Battery_LOW battery status gets device_class battery.

What's in the export

The export is not a list of everything — in IDM3 you choose what goes into it. If something's missing in Home Assistant, add it there. The integration checks once every 30 minutes whether the list has changed and reloads itself. Reload does it immediately.

Values

Temperatures and humidities come in multiplied by a hundred — 2550 means 25.50 °C. Dimmers are already in percent. SYSTEMINTEGER is a raw value that isn't converted in any way; what it means is up to the program that uses it.

⚠️ Security

The ASCII port has no authentication — and the password on the unit won't change that; it only protects the web server. Anyone who reaches that TCP port can control the entire installation.

Keep the unit on a separate VLAN, or at least firewall it off from untrusted devices and from the internet.

Limitations

  • Blinds are not verified on a real drive. For the relay variant, it's assumed that 1 starts the motor and 0 stops it; the pause when reversing direction is a guess.
  • Scenes can't be triggered — a GET on them returns N, and writing is unverified.
  • The binary .otc / .cld formats are not read. They additionally contain named scenes.
  • Both the HTTP and ASCII ports run without encryption.

⚠️ Connection Server slows the response

If the same central unit is also served by the iNELS Connection Server, expect an occasional delay. The Connection Server reaches into the unit for the complete state roughly every 40–60 s, and during that the unit freezes the entire ASCII output for ~2–4 s — it stops sending events and stops executing commands. Every so often a press or a toggle falls into this window and then reacts those 2–4 s later — and that for all clients at once, including the Connection Server itself (so it delays even itself).

  • If you don't need the Connection Server, turn it off — the integration's response is then smooth (the unit answers in ~180 ms).
  • If you do need it, slow down / lighten the periodic state polling in its configuration (how often and how much it reads from the unit).

Verified in isolation: the integration itself causes no freezing — it arises only when the Connection Server is also connected.

The number of clients isn't related either: the central unit has a limited number of ASCII connections. Don't point a lot of clients at the ASCII port at once — when the slots run out, the unit will accept the connection but stop serving it (the HTTP export keeps running), and only a CU restart helps.

Diagnostics

When something's off, this script finds out what the unit can do — it's read-only until you add --write:

python tools/probe_is3.py <ip> <port> 0x0102000A

Development

pip install -r requirements-test.txt
pytest

The unit also speaks other protocols the integration doesn't work with: ELKONET (binary, port 9999) and XML-RPC on the Connection Server (port 7801) — for that route there's InelsForHass.

License

MIT