FAQ & Troubleshooting
English · Русский
After the first flash, the web interface is available at http://192.168.4.1 through the ESP32 access point. Wi-Fi can be configured there. Once the ESP32 joins your home network, the web interface is available at the address assigned by your router. The Ethernet setup instructions describe a wired connection.
If an update leaves pages loading only partly or controls behaving incorrectly, the images are worth checking. The firmware and filesystem must be for the same version and board. A browser reload is needed after uploading both images.
The compatibility table lists the build name and GPIO map for each board. For example, a Wemos S3 mini uses s3_mini. The firmware and filesystem need that build name and must come from the same release. The first installation instructions list the files and flash offsets.
Ethernet requires a supported build: s3_mini or esp32_c6_ethernet. The standard esp32_c6 build has Bluetooth support instead. The board table lists interface support; the firmware and filesystem images must match.
No. Ethernet mode disables Wi-Fi and the ESP32 access point. Loss of the cable connection or IP address leaves Ethernet selected. Restoring access requires a working wired connection with correct DHCP or static address settings.
OTGateway switches to Wi-Fi only when Ethernet cannot start, for example because its configuration is incomplete or driver initialization fails. More detail is available under switching and connection failures.
One Master controls the Slave device on an OpenTherm bus. When you connect OTGateway, the ESP32 takes that role. The original OpenTherm thermostat must be disconnected from the bus.
An on/off thermostat can signal demand through the Cascade control input. The documentation for your adapter describes the input and wiring.
- On the Dashboard, check OpenTherm connection. Network and MQTT connections have separate indicators.
- Make sure the Slave device supports OpenTherm and the adapter is connected to its OpenTherm terminals.
- Compare the adapter wiring and board GPIOs with In GPIO and Out GPIO in OTGateway settings.
Important
On the project's adapter boards through revision 1.3, the printed input and output labels are reversed.
If the link works and only one reading is missing, the sensor checks describe the next steps.
- On the Dashboard, compare Heating target temp, Heating setpoint temp and Heating enabled. The selected mode determines whether you set indoor or heating fluid temperature.
- If OTGateway blocks heating, check hysteresis, overheat protection and the cascade control input.
- Check Heating active and Flame, which the Slave device reports. The appliance may take some time to respond after a setting is accepted.
- If OTGateway requests heating and the Slave device stays idle, check limits on its panel and the settings for your model. It may require a particular Master member ID, summer/winter mode or CH2 configuration.
Some appliances continue to display their local panel setting during external control. Heating activity and measured flow temperature on the OTGateway Dashboard show the Slave device's response.
The meaning of the target depends on the selected mode. With PID, Equitherm or the Slave device's native weather compensation, the heating target is indoor temperature. In direct control it is heating fluid temperature. DHW has its own target.
The value is constrained by the circuit limits shown on the Dashboard. If receiving minimum and maximum temperatures over OpenTherm is enabled, OTGateway updates the range using Slave device data. Some models, such as the Ideal Heat2, also enforce a limit set on the appliance's panel.
For Equitherm, comparing indoor temperatures on mild and cold days at the same target helps assess the curve. If the indoor temperature drops as the weather gets colder, the slope is worth checking. The steps are described under tuning the heating curve.
For PID, gains are adjusted with Equitherm and hysteresis disabled, taking flow temperature limits and the deadband into account. With the default settings, the integral correction builds more slowly near the target. Both the flow setpoint and indoor temperature matter when tuning PID.
The Dashboard shows Heating enabled, Heating active, DHW active and Flame for checking circuit state. The pump may be in overrun, and the burner may be supplying DHW. Freeze protection can re-enable heating.
If the Slave device is still providing central heating, the disabling signal needs to match your model's requirements. It is selected under OpenTherm settings → Circuit disabling action.
DHW support can be turned off in OpenTherm settings.
The relevant checks are DHW support in OpenTherm settings, the DHW enable switch, target temperature and overheat indicator.
If DHW works while heating is on, the heating circuit's disabling action and the settings for your Slave device model are worth checking, including DHW blocking and CH2.
With the flame on, 0% relative modulation means the burner is running at its minimum output. Flame shows the burner status reported by the Slave device.
OpenTherm does not provide direct control of the burner or its current modulation level. The boiler controls these itself to maintain the target flow temperature.
OTGateway can only limit the maximum modulation level using Max modulation level under Heating settings in the web interface. Not all boilers support this limit.
The Power sensor shows estimated thermal output in kW. The calculation uses relative modulation and the configured minimum and maximum output. These limits need to match the appliance specifications.
Measuring gas consumption requires gas meter readings.
Emergency mode depends on the sensors required by your controller. Equitherm needs outdoor temperature. PID without Equitherm and the Slave device's native weather compensation need indoor temperature.
- Check the required sensor's connection. If its readings arrive over the network, check that feed too.
- For a MANUAL sensor, find out when its last update arrived. The sensor goes offline after 10 minutes without an update.
- Restore the feed. OTGateway leaves emergency mode once the required sensors have been available for the configured delay.
Until recovery, OTGateway uses the temperature in Emergency mode settings.
An OpenTherm connection means that the Slave device answers status requests. Support for each reading depends on the model and control board.
For pressure and DHW flow readings, the sensor must be enabled and connected. A working flow sensor can read 0 with the tap closed.
For faults and diagnostics, the Dashboard has separate indicators. The Slave device manual explains the reported code.
The Sensors settings include its enable switch, Type/source and Purpose. The sensor must be enabled and its settings need to match the connection and intended use.
- For a wired sensor, the relevant setting is the GPIO; for Dallas, its address matters too.
- For a Bluetooth thermometer, the address and advertising format matter.
- For MANUAL, the relevant details are the last update time and the address receiving the reading — the MQTT slug or REST ID.
Yes, several probes can share a Dallas bus. Each needs separate configuration, with a shared GPIO and its own 8-byte address. After enabling the sensors, their readings are available for checking.
Tip
If you leave an address unset, OTGateway can assign the first unclaimed probe on the bus. The saved addresses help identify the sensor in each location.
3 conditions are needed.
- The board and build support BLE.
- A Bluetooth sensor is enabled and the thermometer's address is set.
- The thermometer advertises a supported format — ATC1441, PVVX or unencrypted BTHome v2.
The sensor's connection status is available for checking after the next broadcast.
Each sensor is configured separately. Sensors used for regulation have the Indoor temperature purpose. Heating settings offers a choice of average, minimum or maximum reading. Temperature is suitable for sensors used only for display.
Note
These readings feed one controller with a shared indoor target. Zones with separate schedules and valves require zone control.
You can send a Zigbee sensor or weather reading from Home Assistant to a MANUAL sensor. The reading needs to be refreshed within 10 minutes, even if the value stays the same.
For Home Assistant, OTGateway and the MQTT integration need to connect to the same broker, with Home Assistant Discovery enabled in the device's MQTT settings. The Home Assistant integration instructions describe the remaining setup.
Your own MQTT client needs the prefix configured on OTGateway.
- The heating target is available at
<prefix>/settings/heating/target. - A new temperature is sent as a plain number to
<prefix>/settings/heating/target/setwith retain off. - OTGateway publishes the accepted value at
<prefix>/settings/heating/target. - Actual heating activity is available at
<prefix>/state/slave/heating/active.
The example for following a heating request shows the exchange in detail.
When you upgrade from an older OTGateway firmware to the latest release, Home Assistant may keep entities from the previous version. They appear as unavailable on the device page.
- In Home Assistant, open Settings → Devices & services → MQTT and select the OTGateway device you upgraded.
- Open the menu on that device's page, select Delete and confirm.
- Restart the ESP32 running OTGateway. With Home Assistant Discovery enabled in MQTT settings, OTGateway republishes the current entity configurations when it reconnects to the broker.
- Reopen the device in Home Assistant and check its entities. If the ID of an entity you use has changed, select it again in your dashboards and automations.
- Open the OTGateway device page in Home Assistant.
- Expand the hidden entities and select the sensor or setting.
- Enable the entity in its settings.
Automations need the entity's actual ID.
The choice of entity in a Home Assistant automation depends on the purpose. Heating enabled shows whether OTGateway allows the circuit to run. Heating active shows actual activity reported by the Slave device.
External pump settings are available for a pump wired to the ESP32 output. OTGateway controls that output according to its own heating request. Post-circulation keeps the pump running for the configured time after heating stops. The anti-stuck cycle runs it after a long idle period.
The web interface's main page shows Uptime and Last reset reason under System. The same information is available in system.uptime and system.reset_reason through GET /api/info.
- If uptime keeps increasing, the Wi-Fi or Ethernet connection and the broker connection are relevant to diagnosis.
- If uptime started over, diagnosis needs the reset reason, firmware version and board.
Analysis after an exception or panic requires the available core dump and the ELF for that build.
The WebSerial log is available on the Logs page of the web interface. WebSerial can be enabled in System settings. Verbose provides a detailed trace; the usual log level can be restored afterwards.
The page filter only changes which messages are displayed. Viewing logs over USB requires serial output to be enabled and the connection to use its configured baud rate.
For an OpenTherm ID using signed f8.8 temperature, the 16-bit field is interpreted as a signed integer and divided by 256. For example, 0x1580 represents 21.5 °C and 0xFF80 represents −0.5 °C. The data type depends on the particular ID.
Temperatures in the web interface, MQTT and REST are already decoded and use the units selected in OTGateway.