Repository navigation
Supported controllers
The integration supports the SAMSON TROVIS 557x controller family as well as several compatible OEM controllers based on the same platforms.
Which devices and entities appear in Home Assistant depends not only on the controller model, but also on the hydronic system (aka system code number, Anlagenkennziffer) and the functions configured in the controller.
Note
Support means that the controller model and its documented hydronic configurations are known to the integration.
Not every supported model has already been tested on real hardware. The currently available test hardware is listed below.
| Controller | Rk1–Rk3 control circuits | Rk4 / DHW | Documented hydronic systems | Test status |
|---|---|---|---|---|
| SAMSON TROVIS 5573 | 2 | ✓ | 29 | Supported |
| SAMSON TROVIS 5573-1 | 2 | ✓ | 29 | Supported |
| SAMSON TROVIS 5575 | 2 | ✓ | 33 | Supported |
| SAMSON TROVIS 5576 | 2 | ✓ | 52 | ✅ Live tested |
| SAMSON TROVIS 5578 | 3 | ✓ | 90 | ✅ Live tested |
| SAMSON TROVIS 5578-E | 3 | ✓ | 95 | Supported |
| SAMSON TROVIS 5579 | 3 | ✓ | 85 | ✅ Live tested |
Rk is the abbreviation used by SAMSON for a control circuit
(Regelkreis).
Rk1, Rk2 and Rk3 are technical controller slots. Depending on the selected hydronic system, they can be used as heating circuits, pre-control circuits or, in some configurations, as a buffer-tank circuit. Solar is handled separately.
Rk4 is reserved for domestic hot water (DHW). It is only shown in Home Assistant when the configured hydronic system actually uses it.
The number in the table therefore describes what the controller hardware can support - it does not mean that every installation will show all of these circuits.
➡️ Learn more about Rk1–Rk4 and your TROVIS configuration
A number of controllers sold by other manufacturers have the same technical platform as the SAMSON TROVIS and use the same underlying controller technology. Currently these OEM models are known:
| Controller | TROVIS profile | Rk1–Rk3 | Rk4 / DHW | Documented system configurations | Notes |
|---|---|---|---|---|---|
| SAUTER EQJW126F001 | TROVIS 5573 | 1 | - | 1 | Rk1 and system 1.0 only |
| SAUTER EQJW146F001 | TROVIS 5573 | 2 | ✓ | 29 | |
| SAUTER EQJW146F002 | TROVIS 5573-1 | 2 | ✓ | 29 | |
| SAUTER EQJW246F002 | TROVIS 5578 | 3 | ✓ | 90 | |
| SAUTER EQJW246F003 | TROVIS 5578-E | 3 | ✓ | 95 | |
| YADOS YADO|MATIC 01 | TROVIS 5575 | 2 | ✓ | 33 | |
| YADOS YADO|MATIC 01-0003 | TROVIS 5575 | 2 | ✓ | 33 | |
| YADOS YADO|MATIC 03 | TROVIS 5573 | 2 | ✓ | 29 | |
| YADOS YADO|MATIC 03-1003 | TROVIS 5573-1 | 2 | ✓ | 29 | |
| YADOS YADO|MATIC 08 | TROVIS 5578 | 3 | ✓ | 90 | TROVIS 5578-1114 platform |
| PEWO PCR06 | TROVIS 5575 | 2 | ✓ | 33 |
Important
The OEM models above are supported based on the currently available technical documentation, but have not yet been verified on real hardware. If you own one of these controllers, your feedback would be especially useful!
➡️ Help us test another controller
There may be additional OEM controllers on the market that are based on a supported TROVIS platform.
If your controller is not listed here, please do not simply select another model because it looks similar. Open a discussion and provide:
- manufacturer and exact model name,
- a photo of the controller or type label if possible,
- the available technical manual,
- information about its Modbus interface.
We can then check whether it maps safely to one of the supported TROVIS profiles.
Disclaimer: Any information on this wiki is informal advice only. It is not supported nor endorsed by Samson, Sauter, YADOS, Pewo or any other equipment maker or OEM. There is no warranty expressed or implied: you take sole responsibility for everything you do with your heating controller.
-
Wozu dieses Projekt?
What is this project about?
-
Wie funktioniert das?
How does it work?
- Was wird benötigt? Kosten?
What's required? Costs?
- Supported controllers
- Connecting your TROVIS
- Installation and setup
- Current limits and migration
- Troubleshooting
- Architecture and internals
- Connections and transports
- Config flow and reconfiguration
- Coordinator and runtime updates
- Devices and entities
- Writing and write access
- Development and testing
- LAN/WLAN
USR-TCP232-T2, USR-TCP232-410S, USR-K7, USR-DR301 (Hutschiene), Elfin-EE10 (WLAN) - USB
AZDelivery FT232RL, Waveshare USB 2 RS232/485/TTL - ESP
ESP-01, Wemos D1 - SPS
S7 1200, Wago 750-889 - KNX
Masifi Modbus Gateway
- Edomi
- espHome/HomeAssitant
- FHEM
- HomeAssistant
- ioBroker
- KNX
- Loxone
- NodeRed
- openHAB
- SIMATIC Step7
- smarthomeNG
- Tasmota/MQTT
- Wago CODESYS
Wiki - Start