Understanding your TROVIS
TROVIS controllers can look complicated at first because one controller can be used for many different heating and district-heating systems. The good news is that the integration already reads most of that structure for you.
This page explains the terms you will see in Home Assistant without diving into register addresses or controller internals.
A TROVIS installation is mainly shaped by:
- Controller model - for example TROVIS 5576, 5578 or 5579.
- System code / Anlagenkennziffer - the hydronic system selected in the TROVIS.
- Functions and connected inputs - which sensors and optional functions are actually configured.
The integration probes these automatically and creates only the Home Assistant devices and entities that make sense for the detected installation.
The Anlagenkennziffer (system code) tells the TROVIS what kind of hydronic system it is controlling.
Examples can describe systems with:
- one or more heating circuits,
- a primary/pre-control circuit,
- domestic hot water,
- a buffer tank,
- solar support,
- combinations of these functions.
Two identical TROVIS 5578 controllers can therefore look quite different in Home Assistant when they use different system codes.
You normally do not need to enter this number in Home Assistant. The integration reads it from the controller.
Rk is the TROVIS technical control-circuit slot.
The important point is that an Rk number is an identity, not automatically a heating-circuit number.
| Technical slot | Possible meaning |
|---|---|
| Rk1 | heating circuit, primary/pre-control circuit, buffer-tank circuit, or unused |
| Rk2 | heating circuit, primary/pre-control circuit, or unused |
| Rk3 | heating circuit, primary/pre-control circuit, or unused |
| Rk4 | domestic hot water, when the selected hydronic system includes it |
Home Assistant keeps the Rk number stable and uses the detected role to decide the visible name and useful entity set.
So a device named Rk1 - Pre-control circuit is not a renamed heating circuit. It really is the controller's Rk1 slot operating in a different hydronic role.
A heating-circuit Rk controls a flow temperature for a room-heating circuit.
The integration currently understands three basic ways the TROVIS can calculate that target:
The controller uses outdoor temperature together with room setpoint, gradient and level to calculate the required flow temperature.
This is the normal weather-compensated mode and is the mode used by the Home Assistant climate convenience entity.
The controller uses fixed flow temperatures for day and night operation instead of calculating them from outdoor temperature.
Four outdoor-temperature points define the heating curve explicitly. Separate day and night flow temperatures can be configured, together with the corresponding return-temperature limits.
Only one of these three basic modes is active for a heating circuit at a time.
Return-temperature limitation is not a fourth heating mode.
It is an additional limit applied on top of the selected heating-circuit mode. If the return temperature becomes too high, the TROVIS can reduce the flow-temperature demand and close the control valve further.
This is particularly important in many district-heating systems where a maximum return temperature is required.
The integration distinguishes between:
- the immediate, circuit-specific Outdoor temp cutoff active state, and
- the controller's broader summer-operation behavior.
The outdoor-temperature cutoff belongs to an individual Rk and reacts to its effective outdoor-temperature shutdown threshold. It should not be confused with a multi-day or controller-wide summer mode.
When the selected hydronic system contains domestic hot water, the integration creates Rk4 - Domestic hot water.
Rk4 can contain supported values and controls for the DHW function, and a water_heater convenience entity can be added where the available TROVIS data maps cleanly to Home Assistant.
If your hydronic system has no DHW function, Rk4 is not created.
In actual buffer-tank systems, the buffer-tank circuit uses Rk1.
The integration therefore does not create a second duplicate buffer device. Instead, Rk1 keeps its technical identity and receives the additional buffer-tank values that are valid for the detected controller and system code.
Solar is not Rk1 through Rk4.
When the hydronic configuration contains a supported solar circuit, Home Assistant creates a separate Solar device.
The solar circuit may interact with domestic hot water or a buffer tank, but it remains its own functional part of the integration.
Physical sensor inputs are kept together under the Measurements device.
Common TROVIS abbreviations include:
| Abbreviation | Meaning |
|---|---|
| AF | outdoor temperature sensor |
| VF | flow temperature sensor |
| RüF | return temperature sensor |
| RF | room temperature sensor |
| SF | storage temperature sensor |
| FG | remote sensor / remote setpoint input |
| IMP | pulse-rate input |
The number identifies the physical/logical input, for example VF1, VF2 or SF2.
Why keep these under Measurements instead of moving every sensor into an Rk device? Because the same physical input can have a different role depending on model, wiring, system code and enabled functions. Keeping the sensor identity stable avoids confusing entity changes when the controller configuration changes.
The integration intentionally avoids exposing every possible TROVIS datapoint on every controller.
An entity can depend on:
- controller model,
- system code,
- Rk role,
- configured functions,
- detected sensor inputs,
- active heating-circuit mode,
- whether the datapoint is safe and useful to expose in Home Assistant.
That is why two users with the same controller model can still see different devices and entities.
Normal polling updates values, but it does not rebuild the Home Assistant device structure every minute.
If you change something on the TROVIS that affects the system structure - for example the hydronic system, sensor assignments or important function settings - run Reconfigure on the integration so that the controller is probed again.
➡️ Config-flow-and-reconfiguration
This Wiki stays focused on the Home Assistant integration. Register/coil definitions, hydronic matrices, sensor resolvers and controller-side rules are maintained in the trovis-modbus documentation so that the same information does not need to be maintained twice.
Disclaimer: Any information on this wiki is informal advice only. It is not supported nor endorsed by Samson, Sauter, YADOS, Pewo or any other equipment maker or OEM. There is no warranty expressed or implied: you take sole responsibility for everything you do with your heating controller.
-
Wozu dieses Projekt?
What is this project about?
-
Wie funktioniert das?
How does it work?
- Was wird benötigt? Kosten?
What's required? Costs?
- Supported controllers
- Connecting your TROVIS
- Installation and setup
- Current limits and migration
- Troubleshooting
- Architecture and internals
- Connections and transports
- Config flow and reconfiguration
- Coordinator and runtime updates
- Devices and entities
- Writing and write access
- Development and testing
- LAN/WLAN
USR-TCP232-T2, USR-TCP232-410S, USR-K7, USR-DR301 (Hutschiene), Elfin-EE10 (WLAN) - USB
AZDelivery FT232RL, Waveshare USB 2 RS232/485/TTL - ESP
ESP-01, Wemos D1 - SPS
S7 1200, Wago 750-889 - KNX
Masifi Modbus Gateway
- Edomi
- espHome/HomeAssitant
- FHEM
- HomeAssistant
- ioBroker
- KNX
- Loxone
- NodeRed
- openHAB
- SIMATIC Step7
- smarthomeNG
- Tasmota/MQTT
- Wago CODESYS
Wiki - Start