Configuration

github-actions[bot] edited this page Aug 28, 2026 · 1 revision

Configuration

ModBridge stores its configuration in the config.json file by default.

Configuration can be done via the web interface (recommended) or by directly editing config.json in headless mode.

Headless operation (without WebUI)

ModBridge can be operated entirely without a graphical interface. This is ideal for resource-efficient servers, edge devices (such as Raspberry Pi), or automation via configuration management tools (Ansible, Puppet, etc.).

Create the configuration file

If no config.json exists yet, ModBridge automatically creates a default configuration on first start.

# Start ModBridge briefly once to generate config.json
./modbridge-linux-amd64-headless &
sleep 2
kill $!

Edit the configuration

Edit the file with the text editor of your choice:

# e.g. vi config.json

Example configuration

A typical config.json for headless operation with two configured proxies:

{
  "web_port": ":8080",
  "admin_pass_hash": "$2a$10$xyz...",
  "force_password_change": false,
  "session_timeout": 24,

  "proxies": [
    {
      "id": "proxy-1-solar",
      "name": "Solar Inverter",
      "listen_addr": ":5020",
      "target_addr": "192.168.1.100:502",
      "enabled": true,
      "paused": false,
      "connection_timeout": 5,
      "read_timeout": 5,
      "max_retries": 3,
      "description": "Rooftop solar system",
      "max_read_size": 0,
      "tags": ["solar", "roof"]
    },
    {
      "id": "proxy-2-hvac",
      "name": "Air Conditioner",
      "listen_addr": ":5021",
      "target_addr": "192.168.1.101:502",
      "enabled": true,
      "paused": false,
      "connection_timeout": 10,
      "read_timeout": 10,
      "max_retries": 1,
      "description": "Climate control building A",
      "max_read_size": 256,
      "tags": ["hvac", "building-a"]
    }
  ],

  "log_level": "INFO",
  "log_max_size": 100,
  "log_max_files": 10,
  "log_max_age_days": 30,

  "metrics_enabled": true,
  "metrics_port": ":9090",

  "debug_mode": false,
  "max_connections": 1000
}

Headless configuration options

Important settings for server operation:

Field Description Recommendation for headless
log_level Log verbosity (DEBUG, INFO, WARN, ERROR) INFO for production, WARN for minimal logs
metrics_enabled Enables the Prometheus metrics endpoint true (very useful for server monitoring)
metrics_port Port for the /metrics endpoint :9090 (default)
max_connections Maximum number of concurrent TCP connections Adjust to server capacity (e.g. 5000)

Proxy configuration (headless)

To add a new proxy in headless mode, extend the proxies array in config.json.

Important:

  • Every proxy needs a unique id (can be any string, UUID recommended).
  • listen_addr must be unique and have the format :PORT or IP:PORT.
  • Set "enabled": true so the proxy is loaded automatically at startup.

Restart the service after configuration changes

For changes to config.json to take effect, the ModBridge process must be restarted:

With systemd:

sudo systemctl restart modbridge

Docker:

docker restart modbridge

Check service status and logs

To make sure your headless configuration was loaded correctly:

# Check systemd status
sudo systemctl status modbridge

# Check logs for errors
sudo journalctl -u modbridge -f

Proxy fields (reference)

Field Type Description
id string UUID (assigned automatically)
name string Display name in the web interface
listen_addr string Local port, e.g. :5020
target_addr string Target address, e.g. 192.168.1.100:502
enabled bool Proxy enabled/disabled
paused bool Proxy paused (connections are rejected)
connection_timeout int Connection timeout in seconds
read_timeout int Read timeout in seconds
max_retries int Maximum retry attempts on error
max_read_size int Max. Modbus read size (0 = unlimited)
connect_delay_ms int Pause after the TCP connect before the first request (ms, 0 = off). For slow devices like Huawei inverters/sDongles
max_target_conns int Max. concurrent connections to the target device (0 = default 10). Use 1 for devices with a single Modbus session, e.g. SolarEdge/SunSpec
min_request_gap_ms int Minimum gap between two requests to the target device (ms, 0 = off)
request_timeout_ms int Hard time budget for a client request including retries (ms, 0 = derived automatically from read_timeout and max_retries)
calibrated_at string Time of the last measurement (RFC3339). Informative — shows how old the configured values are
device_profile string Last applied device profile. Informative only — remembers which preset the values came from; behavior follows the individual fields
cache_enabled bool Serve repeated reads from a cache (default: off)
cache_ttl_ms int Validity of a cache entry (ms, 0 = 5000)
poll_interval_ms int Refresh polled registers in the background (ms, 0 = off). Requires cache_enabled
protocol string tcp (default) or rtu-tcp for serial adapters that expect raw RTU frames
description string Optional description
tags array Optional tags for categorization

Cache and background polling

Some devices cannot be sped up: a SolarEdge leader fetches follower registers across the RS485 chain first, a heating controller simply takes seconds. When the client (e.g. Home Assistant with a 3 s timeout) gives up faster than the device answers, no amount of timeout tuning helps.

For this there are two related options:

  • cache_enabled — repeated reads are served from the cache instead of asking the device again.
  • poll_interval_ms — a background poller refreshes exactly the registers that clients actually query, on its own schedule. The client gets an immediate answer and never waits for the device.
"cache_enabled": true,
"cache_ttl_ms": 20000,
"poll_interval_ms": 5000

The poller bundles neighboring registers: if a client queries twenty small ranges that lie close together, ModBridge reads them as one block and then distributes the response across the individual entries. This reduces exactly the factor that dominates on slow devices — the number of round trips. Client requests themselves are never merged; a proxy that rewrites what a client asked for is no longer traceable.

TTL and interval belong together. cache_ttl_ms is an upper bound on the age of a value, not a refresh schedule — the poller keeps entries considerably fresher. If the validity is not multiple times the interval, entries expire between two rounds, the client falls through to the device again in that gap, and waits after all. ModBridge logs a warning at startup when the two values are in that ratio.

What you are accepting: a cached value is by definition not the live value — it is up to cache_ttl_ms old. For dashboards and energy data this is harmless; for control loops it is not. That is why the feature is off by default and must be enabled deliberately.

What the cache does not do:

  • Writes are never cached and always passed through.
  • After a write, all cache entries of that unit ID are discarded — a just-changed value would not merely be old, it would be wrong.
  • Modbus exceptions never land in the cache.
  • The poller only queries registers that a client has requested before, and forgets them again when nobody asks for them for a while.

The proxy status exposes cache_hits, cache_misses, cache_entries, and polled_requests for verification.

Measuring the device (calibration)

Profiles are educated guesses. Calibration replaces them with measurements on the real device: it lowers the gap step by step until the device starts discarding requests, increases the number of parallel sessions until it stops answering, and derives the read timeout from the measured latency.

Found in the proxy dialog under Measure device, or via POST /api/proxies/calibrate with {"id": "<proxy-id>"}.

What happens during the measurement: the proxy accepts no client connections. During that time nothing is queried and nothing is controlled through this proxy. That is why a run is hard-capped at 90 seconds; when the time expires, it returns what was measured so far instead of continuing.

What the run protects against:

  • Read accesses only. Never a write.
  • It repeats a register that a client is querying anyway — the proxy remembers the last read. Alternatively you specify a register.
  • It disconnects connected clients for the duration and holds back new ones: their traffic would falsify the measurement and vice versa. Nobody can pin a controller on demand for 90 seconds, so the proxy does it — a request that is already in flight still gets its answer, and the clients reconnect on their own afterwards.
  • It releases the pool connection beforehand and pauses the health check — a device with a single Modbus session cannot be measured otherwise, because the proxy itself holds that session.
  • It changes nothing. Applying the values is a separate click, and they are only saved when the proxy is saved.

A single error is not a measurement: each step is judged across a series, and the adopted gap keeps 1.5x distance from the fastest value that still ran cleanly. If the device does not answer reliably even at the most cautious gap, the run deliberately returns conservative values plus a clear note — instead of an error nobody can use.

calibrated_at records when the last measurement happened. If stale_responses or the error count rises noticeably later, a new measurement is worthwhile — devices behave differently after a firmware update.

Device profiles

In the proxy dialog of the web interface, a device profile fills the fields at the top with values that match the behavior of the target device. The selection is grouped by category and searchable.

Important for context: the profiles describe a behavior class, not a manufacturer specification. The values live in nine classes; the roughly 60 device entries only map which class a device falls into — how many Modbus sessions it serves, how much room it needs between requests, how long an answer may take, and whether it speaks Modbus TCP or raw RTU. Measured timing values per model they are explicitly not. A profile is a starting point that keeps a device stable — fine-tuning remains your job.

Behavior classes

Class Behavior Core setting
standard ModBridge defaults no limits
multiSession fast, many clients no limits, no gap
fewSessions some parallel sessions 2 connections, 50 ms gap
singleSession one Modbus session only 1 connection, 100 ms gap
singleSessionFast one session, client with a short timeout + budget 2.5 s, read timeout 2 s
singleSessionSlow one session, sluggish controller 250 ms gap, 10 s read timeout
connectDelay discards requests right after connect 3 s pause, 1 connection
serialGateway serial line behind TCP 1 connection, 50 ms gap, reads capped at 125 registers
rtuOverTcp raw RTU frames without MBAP header protocol rtu-tcp, 1 connection

Categories and devices

Category Devices
General Standard, PLC, Modbus-TCP→RTU gateway, serial adapter
Inverters / PV SolarEdge (single), SolarEdge Leader+Follower, SMA, Fronius, Kostal, Huawei, Sungrow, GoodWe, Growatt, SolaX, Deye/Sunsynk, Sofar, Delta, KACO, FIMER/ABB, E3/DC, Victron, generic SunSpec
Heat pumps / heating IDM (Navigator 2.0 / Navigator 10), Stiebel Eltron ISG, Tecalor ISG, NIBE S-series, NIBE MODBUS 40, Lambda, Waterkotte, Ochsner, Nilan, Daikin Altherma, Panasonic Aquarea, LG Therma V, Mitsubishi Ecodan
Ventilation / climate Helios KWL, Zehnder ComfoAir Q, Vallox, Pluggit, Wolf CWL
Energy meters Eastron SDM, Carlo Gavazzi EM24/EM340, Janitza UMG, Schneider iEM3000, Siemens SENTRON PAC, ABB B23/B24, Finder 7M, Iskra WM3, Shelly Pro EM
Battery storage BYD Battery-Box, Pylontech, VARTA
Wallboxes / charging KEBA, Alfen Eve, go-e, Wallbox Pulsar Plus, MENNEKES AMTRON, Webasto, ABL eMH, Heidelberg Energy Control

Devices that only reach Modbus through a separate adapter (e.g. NIBE MODBUS 40, LG PI485, many meters) are marked accordingly in the hint text — the values apply to the adapter there, not the device.

A new device is an entry in frontend/src/deviceProfiles.js with a label and a class; categories, class hints, and notes live in frontend/src/i18n.js under control.profiles.*.

Complete config.json (example with all options)

{
  "web_port": ":8080",
  "admin_pass_hash": "",
  "force_password_change": true,
  "session_timeout": 24,

  "proxies": [
    {
      "id": "21e71152-3866-43ac-891d-c5ec85fa1e98",
      "name": "SolarEdge Proxy",
      "listen_addr": ":5020",
      "target_addr": "192.168.1.100:502",
      "enabled": true,
      "paused": false,
      "connection_timeout": 10,
      "read_timeout": 10,
      "max_retries": 3,
      "description": "Connects to the SolarEdge plant",
      "max_read_size": 0,
      "connect_delay_ms": 0,
      "max_target_conns": 1,
      "min_request_gap_ms": 100,
      "request_timeout_ms": 2500,
      "tags": []
    }
  ],

  "log_level": "INFO",
  "log_max_size": 100,
  "log_max_files": 10,
  "log_max_age_days": 30,

  "tls_enabled": false,
  "tls_cert_file": "",
  "tls_key_file": "",

  "cors_allowed_origins": ["*"],
  "cors_allowed_methods": ["GET", "POST", "PUT", "DELETE", "OPTIONS"],
  "cors_allowed_headers": ["Content-Type", "Authorization"],

  "rate_limit_enabled": true,
  "rate_limit_requests": 60,
  "rate_limit_burst": 100,

  "ip_whitelist_enabled": false,
  "ip_whitelist": [],
  "ip_blacklist_enabled": false,
  "ip_blacklist": [],

  "metrics_enabled": true,
  "metrics_port": ":9090",

  "email_enabled": false,
  "email_smtp_server": "",
  "email_smtp_port": 587,
  "email_from": "",
  "email_to": "",
  "email_username": "",
  "email_password": "",
  "email_alert_on_error": true,
  "email_alert_on_warning": false,

  "backup_enabled": true,
  "backup_interval": "daily",
  "backup_retention": 7,
  "backup_path": "./backups",
  "backup_database": true,
  "backup_config": true,

  "debug_mode": false,
  "max_connections": 1000
}

Writes and flash wear

On an SD card or a cheap SSD, the question of what ModBridge actually writes to disk is fair.

Never touches the disk: the response cache, the background poller, statistics, latency percentiles, and calibration. All of that lives entirely in RAM and disappears on restart. Enabling the cache generates no additional writes.

Touches the disk:

What When
connection_history one row per client connection
devices updated per connection
audit_log per user action (rare)
log files per log line, with rotation
config.json only on configuration changes

The relevant item is the connection history. A client with one permanent connection generates almost nothing; a client in a reconnect loop generates one row per attempt.

Countermeasures:

  • WAL mode and synchronous=NORMAL are set. This removes the fsync on every commit — the difference on flash storage is substantial. The price: on a power failure the last transactions may be missing. The database is not corrupted by this.
  • The connection history is cleaned up automatically after 7 days.
  • log_level at WARN reduces the log volume considerably.

If you want to be absolutely safe, put the database and logs on different media (USB SSD, tmpfs for logs) — that is a question of installation, not configuration.