The orchestrator gets installed to a system location because NUT's nut user
runs the event path and can't read a 0700 home directory. The repo can live
in your home for development; the deployed copy lives under /opt, /etc, and
/var/lib.
sudo deploy/install.sh
sudo "$EDITOR" /etc/ups-orchestrator.env # set your real webhookThis creates a venv at /opt/ups-orchestrator/venv (symlinked to
/usr/local/bin/ups-orchestrator), installs the config/env/state under /etc
and /var/lib, drops the upssched-cmd.sh dispatcher in /usr/local/bin, sets
ACLs so the run user can read the config and write state, and adds a sudoers.d
rule for local shutdown targets. Orchestrator-managed shutdowns remain disabled
unless the top-level shutdown policy is explicitly enabled.
Apply the snippets in deploy/nut/ (review them first; set your UPS names and
USB ids):
-
ups.conf: one section per UPS. -
upssched.conf: pointsCMDSCRIPTat/usr/local/bin/upssched-cmd.shand maps the events.ONBATTis debounced via a 15 sSTART-TIMERso brief utility dips don't page — only a sustained outage forwardsonbatt, and the restore alert only follows a real (non-debounced) outage.LOWBATTis never debounced. -
upsmon.conf: aMONITORline per UPS plus theNOTIFYFLAG/NOTIFYCMDwiring.
MONITOR <ups>@<host> <powervalue> <user> <pass> <primary|secondary> decides
who shuts down and when, so get these right:
-
@<host>must name the host runningupsd— the one physically cabled to the UPS. Use@localhostonly there; a host watching over the network names theupsdhost instead. A wrong host means upsmon never reaches the UPS and every event silently no-ops. -
powervalueis1for a UPS that actually powers this host (counts towardMINSUPPLIES) and0for a notify-only UPS, so an unrelated UPS's battery can't trigger this host's shutdown. -
primaryruns the shutdown sequence (exactly one per UPS);secondaryonly observes and powers itself off. A USB-cabled debug/observer host would list the same UPSes assecondary.The role is per UPS, and a host that owns the USB cable for all of them does not have to be
primaryfor all of them. On the reference deployment eulerpi5 isprimaryfor exactly one UPS andsecondaryat powervalue0for the other two, withMINSUPPLIES 0— deliberately, becauseprimaryplus a reachableMINSUPPLIESis what lets upsmon'sforceshutdown()halt this host, and this host is the one that must survive an outage to bring the others back. Read the live file rather than assuming;grep -E '^MONITOR|^MINSUPPLIES' /etc/nut/upsmon.conf.
Every NOTIFYFLAG … EXEC must map to an event the orchestrator handles
(onbatt, online, lowbatt, commbad, commok) and vice versa — a flag with
no handler is dead config; a handler with no flag never fires. The orchestrator
only observes and notifies here; upsmon's SHUTDOWNCMD does the real shutdown.
sudo systemctl restart nut-driver-enumerator nut-server nut-monitor
upsc -l # your UPSes should be listedFor multiple USB UPSes with the same vendor/product id, pin each section with a
serial = ... line. nut-scanner -U is the quickest way to list those serials.
monitor add --method {none|native|serial|ssh} (default native, matching
pre-Phase-2 invocations that omit --method) is the one enrollment command for
every shutdown authority. serial/ssh/none are record-only: they
write a monitored_machines entry and touch nothing else — no
upsd.users/LISTEN, no firewall, no remote NUT install. Only native runs
the privileged NUT-secondary bootstrap described below, and it runs on the
primary (eulerpi5) as root:
# native — network-reachable, nut-capable box: bootstraps a real NUT secondary
sudo ups-orchestrator monitor add mt --method native --ssh mt --ups cyberpower --os arch --powervalue 1
# serial — network-independent push over a console cable; no --ssh needed
sudo ups-orchestrator monitor add mt --method serial \
--serial-device /dev/serial/by-id/usb-FTDI_FT232R_USB_UART-if00-port0 \
--serial-baud 9600 --ups cyberpower
# ssh — push transport, no NUT enrollment
sudo ups-orchestrator monitor add somebox --method ssh --ssh somebox --ups cyberpowerYou cannot switch a native record to serial/ssh/none in place —
monitor add refuses that transition and tells you to monitor remove <name>
first, because that is the only command that runs the real remote NUT
teardown. Skipping it would leave the old secondary's upsmon armed while also
activating a push — two live shutdown authorities on one machine.
The rest of this section describes the native bootstrap. What it does, in order:
-
Bootstrap the primary. Append the LAN
LISTENto/etc/nut/upsd.conf, add the[upsmon_secondary]account to/etc/nut/upsd.users, then run a fullsystemctl restart nut-server. Areloadis a no-op forLISTEN—upsdonly binds its sockets at start, so a reload leaves it on localhost and the secondary never connects. This is why the flow restarts rather than reloads. -
Firewall. Splice a marked, reversible
tcp dport 3493 ip saddr { … } acceptrule into the operator's own input base chain (the one carryinghook input/policy drop, in/etc/nftables.d/main.nft), reload the top-level/etc/nftables.conf, then restart the crowdsec bouncer (see the warning below). The rule must live in that base chain: nftables evaluates every base chain on theinputhook, and anacceptin a self-containedpolicy accepttable at negative priority is terminal only for its own chain — the packet still reaches thepolicy dropbase chain and is dropped, so the port never opens (the symptom is aupsctimeout, not a refusal). The marked block makes the edit idempotent andmonitor removereverses it cleanly./etc/nftables.d/main.nftmust already exist and contain the input base chain — enrollment errors clearly if it does not, rather than writing a rule that lands nowhere. -
Remote install/config. Over the
sshalias: install the NUT client for the box's distro (nuton Arch,nut-clienton Ubuntu/Debian), write a secondaryupsmon.conf(powervalue 1,MINSUPPLIES 1,DEADTIME 30, and noPOWERDOWNFLAG/killpower— a secondary has no UPS to power off), and enablenut-monitor. -
Verify. Confirm the secondary reads its UPS off the primary's
upsd.
The secondary's NUT password comes from UPS_NUT_SECONDARY_PASSWORD in
/etc/ups-orchestrator.env and must match the [upsmon_secondary] entry on the
primary. It is never written to config.json.
Address resolution. Two addresses matter and both are auto-detected, but a WAN/NAT SSH path can fool the defaults — override explicitly when in doubt:
-
The secondary's source IP (the nftables
saddr, and whatupsdsees). It is resolved by runningip -o route get <primary>on the secondary and taking thesrc— the real address the box sources packets from toward the primary.$SSH_CONNECTIONis only a fallback, because over a WAN/NAT hop its client field is the gateway, not the machine's LAN IP. Pass--ip <addr>to override. -
The primary's LAN IP (the
MONITORline and theLISTENthe secondary dials). It is taken from the first non-loopbacknut_server.listenentry, else auto-detected via a localip route gettoward the secondary. If neither yields a LAN address, enrollment errors (rather than silently bindingupsdto localhost and failing at verify) — pass--primary-ip <addr>or add a LAN address tonut_server.listen.
!!! danger "Mandatory: restart crowdsec after every nft -f"
Debian's /etc/nftables.conf opens with flush ruleset, which wipes
crowdsec's crowdsec/crowdsec6 tables. The bouncer does not recreate
them on a plain reload — only a restart does. So every nftables reload
must be followed by:
```bash
sudo nft -f /etc/nftables.conf
sudo systemctl restart crowdsec-firewall-bouncer
```
`monitor add` does this for you. To make the guard permanent across *future*
reloads, install the shipped `PartOf=nftables.service` drop-in
(`deploy/nftables/crowdsec-partof.conf`):
```bash
sudo systemctl edit crowdsec-firewall-bouncer # paste the [Unit] stanza
sudo systemctl daemon-reload
```
Warning sign that the guard is missing: `nft list tables` shows no `crowdsec`
table after an enrollment or reload.
Also apply the nut-monitor network-online drop-in
(deploy/nut/nut-monitor-network-online.conf) on each secondary so upsmon
starts after the network is actually up, not merely configured — otherwise it
logs a spurious comm-loss on boot until DHCP settles.
Operator-only actions on the far-end machine (e.g. mt) — the orchestrator
never touches another host's /etc; this is reference guidance for whoever
administers that box.
!!! warning "The 'code only' scope no longer applies"
An earlier revision of this page said Phase 2 shipped code only and that
shutdown.enabled stays false in production. That scope was lifted by the
operator and both statements are now false on the reference deployment. Never
infer a deployment's armed state from this page — run
ups-orchestrator remote-shutdown --dry-run and read the gate verdict.
Before any of the far-end setup below matters, the primary must be able to
open the serial device at all. deploy/install.sh adds the run user to
dialout, which is the group Debian puts /dev/ttyUSB* and /dev/ttyS* in:
id -nG "$USER" | tr ' ' '\n' | grep -qx dialout || echo "NOT in dialout"
# group membership only takes effect on a new login session:
sudo usermod -aG dialout "$USER" && echo "log out and back in"Without it every serial push and every ups-orchestrator shutdown rehearse
fails with PermissionError on the device open — the watch loop runs as your
user under systemd --user, not as root. Group changes do not apply to an
already-running session or an already-started user service, so after a fresh
install: re-login, then systemctl --user restart ups-orchestrator-watch.
The nut user is deliberately not in dialout, and does not need to be.
The upssched dispatcher runs as nut, but the shipped
deploy/nut/upssched.conf.snippet only wires ONBATT, ONLINE, LOWBATT,
COMMBAD and COMMOK — none of which reach the push gate (see
Shutdown-Mechanisms). The serial push is not
reachable from the NUT event path at all; it fires from the poll loop, which
runs as your user. If you add an AT ... EXECUTE remote_shutdown rule to
upssched.conf, you must add nut to dialout too — otherwise that rule
fails with PermissionError at the one moment it exists to work.
A serial push writes a shutdown command into a passwordless/auto-login getty
on the target's console tty. Three prerequisites, scoped to that one serial
tty only — none of this should loosen SSH or the physical console login:
-
Auto-login getty on the serial console, at the SAME baud the primary uses. On a systemd host, override the console-getty unit for the specific serial tty (name unverified for any given box — commonly
ttyS0/ttyS1; the operator confirms it against that machine's actual wiring):sudo systemctl edit serial-getty@ttyS0.service
[Service] ExecStart= ExecStart=-/sbin/agetty --autologin youruser -L %I 9600 $TERM # 9600 = EXAMPLE
(The exact flags depend on your distro's
agettyversion — treat this as a starting point to verify againstman agettyon the target, not a drop-in guarantee.) The baud given here (9600is only an EXAMPLE — this deployment's Dell console actually runs at 115200) must match what the primary declares asserial_baudfor this machine — see the baud call-out in Configuration. A mismatch here is exactly the silent failure mode described there: the write still "succeeds" (rc 0) and nothing happens. -
NOPASSWD for shutdown/poweroff, if the auto-login user above is not root — the pushed command (
shutdown_cmd, see Configuration → per-transport shutdown_cmd) must be able to run without a password prompt, or it will sit on the console waiting for input that a push over a 3-wire cable can never provide:youruser ALL=(root) NOPASSWD: /sbin/shutdown, /sbin/poweroff -
BIOS/SOL must not steal the tty from the OS getty post-boot. On a Dell PowerEdge (or similar server BMC), Serial-Over-LAN can redirect the same physical UART to the BMC console after boot, in which case the pushed bytes reach the BMC, not the running Linux getty, and the "shutdown" never happens. Confirm SOL is disabled for the tty you're wiring to, or that it hands the port back to the OS before this path is relied on.
The native secondary model has one irreducible hole. Secondaries monitor upsd
on the primary over TCP. If the primary (eulerpi5) or the network switch
between them dies on an otherwise healthy grid, the secondaries are left
last-known-OL and blind: upsmon treats prolonged comm-loss as a warning
(NOCOMM), not a shutdown, by design. They stay up but unprotected against a
subsequent outage until the feed returns.
Option A (shipped mitigation). Each secondary runs powervalue 1 +
MINSUPPLIES 1 + DEADTIME 30. This covers every path where the grid is really
down: a genuine on-battery outage still triggers shutdown, and if the primary
dies mid-outage (everything already OB), each secondary's local
DEADTIME-on-OB timer declares the UPS dead and shuts down (dead-UPS
inference, Path B2). What Option A does not cover is the healthy-grid
crash: primary or switch dies while everything is OL, so there is no OB
state to infer from — NOCOMM warnings only, no shutdown.
Do not claim the SSH/serial backup closes this hole. The default-off backup runs on eulerpi5 — it dies with the primary (mode b) and cannot cross a dark switch (mode c). Stating otherwise would be a documentation correctness bug.
Option B (the designated future fix, not implemented here): a second,
independent upsd (e.g. on the rpi4, in a separate power + network domain) that
the secondaries also monitor. That gives a surviving monitor when the primary is
gone. It is a topology change, deferred to a future phase.
Wiring recommendation (mitigation D): put the network switch and eulerpi5 on the longest-runtime UPS. It does not close the b2/c-OL hole, but it shrinks the window in which the coordinator or its network path goes dark before the secondaries.
loginctl enable-linger "$USER"
deploy/install-user-service.shThis installs:
-
ups-orchestrator-watch.service: continuous poll loop for the opt-in shutdown policy and on-battery countdowns. It re-reads the config when the file changes, so an edit to/etc/ups-orchestrator/config.jsontakes effect within one poll interval — no restart needed. A reload that fails to parse keeps the previously loaded policy and logs an error rather than exiting, because a half-written file must not disarm a running shutdown controller.This matters most for
monitor remove: before the reload existed, a disarm persisted to disk and the running daemon carried on with its startup snapshot until somebody restarted the unit.The loop also closes a
COMMUNICATION LOSTalert itself once the UPS reads again, and opens one after three consecutive unreadable polls. NUT cannot be relied on for either:upsmonfiresCOMMOKonly on a lost→ok transition it observed, so restartingnut-monitor(which anut-serverrestart does) leaves the alarm permanently open — andupsmonreachingupsdis a different code path from this program reachingupsd, so there are states where upsmon is content and every reading here is blank. The same backstop exists for LOW BATTERY, for the same reason.It is also watchdogged. The unit is
Type=notifywithWatchdogSec=120, and the ping is sent after each completed sweep of every UPS — not on a timer, because a timer would keep reporting healthy while the loop was wedged in a blocking serial read. Before this, systemd could see the process exit but never see it hang, and a hung loop polls nothing while still showingactive (running).
ups-orchestrator-alert@.service is an OnFailure= handler that posts straight to
the Discord webhook. It reads the webhook from the env file and shells out to curl
— no venv, no package import, no config read — because the config is the most likely
thing to be broken when it runs.
It exists because the orchestrator cannot report its own death: an unloadable config makes the watch loop and every NUT event handler exit before a notifier is ever constructed, so a crash-loop is otherwise completely silent and the next real outage produces no alerts and no shutdowns.
StartLimitIntervalSec=300 / StartLimitBurst=5 are what make that reachable. They
live in [Unit], not [Service] — systemd silently ignores them in [Service] and
keeps its 10s default, which at RestartSec=5 can never trip, so the unit would loop
in activating forever and OnFailure= would never fire.
One page per unit per hour; the journal line is written every time regardless.
-
ups-orchestrator-recorder.service: one-second UPS telemetry samples for power-loss forensics. It retains twenty 50 MB historical segments plus the active file (roughly two weeks at the live three-UPS record size) and records self-test, output-shutdown timer, and alarm fields alongside load/voltage. -
ups-orchestrator-boot-audit.service: one-shot post-boot alert when the host recovered from abrupt power loss. -
ups-orchestrator-report.timer: daily Discord report of battery, estimated time to 0%, load, and voltage for every configured UPS. On Mondays it also posts the power dashboard image (per-UPS cards, a draw-over-time chart, and daily-kWh usage bars for the week) — no separate timer. This needsmatplotlibin the install venv; add it once withsudo /opt/ups-orchestrator/venv/bin/pip install matplotlib(orpip install ups-orchestrator[dashboard]). Without it the report still sends; the image is skipped with a logged warning. -
ups-orchestrator-selftest.timer/.service: weekly NUT battery self-test with a Discord alert on failure. Installed but not enabled — the test discharges the pack, and it needs a NUT admin account (instcmdsin/etc/nut/upsd.users) exported asUPS_NUT_ADMIN_USER/UPS_NUT_ADMIN_PASSWORDin/etc/ups-orchestrator.env. Arming it is your call:systemctl --user enable --now ups-orchestrator-selftest.timer.
You can test the report path immediately:
ups-orchestrator report --print # terminal preview
ups-orchestrator report # send Discord webhook
ups-orchestrator notify-test # send test embed and print delivery result
ups-orchestrator audit # boot/UPS/state/shutdown evidence report
ups-orchestrator logs events # tail durable local UPS event JSONL
ups-orchestrator logs notificationsups-orchestrator maintenance begin --hours 2 --reason "recabling the rack"
ups-orchestrator maintenance status
ups-orchestrator maintenance endDeclare one before you pull a plug on purpose.
The reason is that a deliberate cut and a real outage are indistinguishable from
this host. Both leave every UPS reporting OL right up to the instant the host
dies — there is no in-band signal that says "a human did this". The boot audit
therefore falls back to filesystem-recovery evidence in the boot journal, which
fires on plenty of ordinary boots. Powering everything down on purpose to redo
cabling produced three critical Discord alerts in one evening. Only the operator
knows which it was, so the operator gets to say so in advance.
While a window is open, ups-orchestrator boot-audit suppresses its critical
power-loss alert and records why. It is the last of three suppression gates,
which matters for what a window is actually for:
- the boot was already audited (the per-boot marker),
- the previous boot logged systemd's own shutdown sequence — a clean
poweroff/reboot, and no amount of fsck noise makes that an outage, - an operator-declared maintenance window is open.
Gate 2 already covers an orderly sudo poweroff. A window is what you need for
the case gate 2 cannot see: the cut that leaves the journal stopping mid-line,
because you really did pull the plug.
| Flag | Default | Meaning |
|---|---|---|
--hours |
4 |
Window length for begin. Must be greater than zero (rc 2 otherwise) |
--reason |
"" |
Free text, echoed into the suppression record so a silent boot audit still says who silenced it and why |
begin overwrites any open window rather than extending it, so re-running it is
how you lengthen one. end prints no window was open and still exits 0 if
there was nothing to clear — ending a window you are unsure about is always
safe. status prints no window open — power-loss alerts are ARMED when
nothing is set.
!!! warning "The expiry is the safety feature — do not wish it away" A window is time-bounded on purpose. A boolean "maintenance mode" flag that an operator forgets to clear silences outage alerting forever, and that failure is invisible precisely because nothing gets delivered: a silenced monitor and a quiet month look identical from the outside. An expiry makes the armed state the default one — the system re-arms itself whether or not anyone remembers. Prefer a short window you re-open over a long one you intend to close.
The marker is /var/lib/ups-orchestrator/maintenance.json (override with
$UPS_ORCH_MAINTENANCE_STATE), holding just the expiry and the reason. Anything
unreadable — missing, truncated, not JSON, no until — is treated as no
window, so a corrupt marker fails toward alerting rather than toward silence.
Deleting the file by hand is equivalent to maintenance end.
Several targets exist for the times something looks wrong. Run the read-only ones first.
make nut-driver-cpu is worth knowing about before you need it. It samples each
usbhid-ups process over five seconds of wall clock, because ps reports a
lifetime average — which is how a driver spinning at 64% of a core went unnoticed
here for two days. The UPS answered upsc in 15 ms throughout, so nothing was "down"
and nothing alerted; it simply ate a fifth of the machine. If one driver is pegged
while its siblings sit at 0%, sudo make nut-repair-driver-spin UPS=<name> adds NUT's
pollonly to that one device and restarts only its driver.
make nut-status # read-only, NO sudo
sudo make nut-repair-listen # restore upsd's loopback LISTEN
sudo make install-config CONFIG=/path/to.json # validate, then install into /etcRead-only and unprivileged — it changes nothing, so it is always safe to run first and it will not mask the fault by restarting something. It prints, in one screen:
-
is-activefornut-server,nut-monitorandnut-driver.target, plus the--userunitsups-orchestrator-recorderandups-orchestrator-watch; - the active (uncommented)
LISTENlines in/etc/nut/upsd.conf; - whether a bare
upsc -lis answered — printingREFUSED (run: sudo make nut-repair-listen)when it is not; - the most recent recorder sample, as a timestamp and each UPS's status, so you can tell "no data" apart from "bad data".
Guarantees /etc/nut/upsd.conf keeps a loopback LISTEN, restarts
nut-server, and verifies a bare upsc -l works before it exits non-zero.
It exists because of a genuinely nasty default. upsd listens on localhost only
when upsd.conf has no LISTEN line at all, and Debian ships the file with
every LISTEN commented out. Writing the first explicit LISTEN — as LAN
enrollment must — silently replaces that implicit default instead of adding to
it. That broke this host twice:
- every bare
upscwas refused for two days, taking the local tooling with it; - then a boot where
eth0had no DHCP lease yet leftupsdwith no bindable address, so it exited, and systemd's restart limit killednut-serveroutright.
Idempotent: if loopback is already listed it says so, skips the restart, and
removes the backup it took. When it does rewrite, it backs the file up to
upsd.conf.bak-<epoch> first and edits in place so the inode keeps its
mode, owner and ACL. It reuses whatever LAN address is already configured, and
the rewrite goes through the same tested function the daemon uses
(nutclient.upsert_upsd_listen), so there is one implementation of the rule and
no second one to drift. Needs the venv (make venv).
Never hand-copy a config into /etc. This target:
- Validates that the file actually LOADS before touching the live one, and prints every load-time degrade notice it raises;
- prints the topology the file implies — for each UPS, what it shuts down and
what it also powers (the
devicesinventory above), so a recabling typo is visible as the wrong blast radius rather than discovered during an outage; - backs the live config up to
config.json.bak-<epoch>if one exists; - installs it
0640 root:nutwith au:<user>:rACL, then prints the resulting mode and ACL.
The validation is in front of the install, not after it, because a config that
fails to parse is a monitoring-topology outage that looks healthy: watch would
poll zero UPSes and report no problem. The user granted the read ACL is
$SUDO_USER.
| Path | What |
|---|---|
/usr/local/bin/ups-orchestrator |
the orchestrator |
/usr/local/bin/upssched-cmd.sh |
NUT dispatcher |
/etc/ups-orchestrator/config.json |
per-UPS config (no secret) |
/etc/ups-orchestrator.env |
webhook + paths |
/var/lib/ups-orchestrator/state.json |
per-UPS state |
/var/lib/ups-orchestrator/samples.jsonl |
high-frequency UPS samples |
/var/lib/ups-orchestrator/events.jsonl |
UPS event/decision log |
/var/lib/ups-orchestrator/notifications.jsonl |
Discord delivery outcomes |
/var/lib/ups-orchestrator/maintenance.json |
open maintenance window (absent = alerts armed) |
/var/lib/ups-orchestrator/boot-audit.json |
per-boot marker, so one boot alerts once |
~/.config/systemd/user/ups-orchestrator-watch.service |
the poll loop |
~/.config/systemd/user/ups-orchestrator-recorder.service |
telemetry recorder |
~/.config/systemd/user/ups-orchestrator-report.timer |
daily UPS load report |
~/.config/systemd/user/ups-orchestrator-selftest.timer |
weekly battery self-test (installed, not enabled) |
Your real device ids, IPs, and the webhook stay on the machine under /etc;
none of that is in the repo.