Shutdown mechanisms: SSH push vs. native NUT

Every enrolled machine (monitored_machines[], see Configuration) carries exactly one effective shutdown_method: none, native, serial, or ssh. native wraps NUT's own primary/secondary model (below); serial and ssh are the orchestrator's own push transports — it reaches out to the machine over a console cable or an SSH connection and sends the shutdown command itself. (The legacy per-UPS shutdown_targets[] array, described in Shutdown Targets, predates the per-machine model and is kept only for back-compat; its remote/serial/local kinds map onto shutdown_method ssh/serial/(the local host, which has no monitored_machines entry at all).) The SSH push path is the convenient one, and it is also the one with the most failure modes. This page describes that pathology honestly and asks whether NUT's own distributed-shutdown model is a better fit.

Ordering: serial before ssh, and per-machine push vs. per-UPS native

When more than one push-managed machine is due on the same UPS, serial fires before ssh: serial is network-independent (a console cable, not a route through the switch), while ssh dies with the network the same outage may be killing. The sort is stable, so declared order still holds within each transport.

This is also the point where native and a push method are structurally different kinds of authority, not two options on a spectrum: native is a per-UPS mechanism — the remote secondary's own upsmon reacts to the primary's NUT-level FSD flag for that UPS, with no orchestrator involvement at fire time at all — while serial/ssh are per-machine decisions the orchestrator itself makes and executes, one machine at a time, on each poll. A native machine is therefore never projected onto a push attempt (doing so would shut it down twice); only serial/ssh machines are.

"UPS is close to empty" means two different things for the two authorities. For a serial/ssh push, "close to empty" is the orchestrator's own configured shutdown.external group thresholds (battery_below / runtime_below) evaluated against the current snapshot — an operator-tunable gate. For native, the trigger is NUT's own low-battery (LB) condition on the primary, which is an entirely separate mechanism with its own thresholds configured in NUT itself, not in this orchestrator's config at all.

The push is NOT driven by NUT's LB flag — read this before relying on it

The paragraph above is easy to read as "both authorities fire at low battery, just with different thresholds". They do not share a mechanism, and the difference decides whether a push happens at all:

  • native fires from NUT. The primary raises FSD on its own LB condition and the remote secondary's upsmon halts the box. Nothing in this repo is involved, and nothing in this repo can stop it.
  • A serial/ssh push fires from this orchestrator's watch poll loop, and from nowhere else. UpsSnapshot.low_battery — the parsed LB flag — has zero consumers in the shutdown gate. It is read only by status, report, selftest and the web UI, all of which merely display it. deploy/nut/upssched.conf.snippet does map AT LOWBATT * EXECUTE lowbatt and deploy/upssched-cmd.sh does forward it, but handle_lowbatt writes a lowbatt event and sends one notification, then returns. It never reaches the shutdown path.

Three consequences follow, and none is obvious from the requirement text:

  1. If the watch unit is not running, no push ever fires. NUT will still deliver its LOWBATT notification and a native secondary will still halt itself, so the outage looks handled — while every serial/ssh machine silently rides the battery to the floor. systemctl --user status ups-orchestrator-watch is therefore a shutdown-path check, not just a monitoring one.
  2. Both shutdown.external thresholds must be crossed, not either. When battery_below and runtime_below are both set, _close_to_empty ANDs them. A UPS at 5% charge that still reports 20 minutes of runtime does not open the gate. Only when one of the two is left unset does the other decide alone.
  3. A UPS that raises LB without reporting charge or runtime never opens the gate at all. With both readings unknown, _close_to_empty returns False — deliberately, and pinned by test_an_undefined_close_to_empty_condition_never_fires. This is the shape a dying UPS actually produces (upsc stops reporting battery.charge and battery.runtime while ups.status still says OB), and firing on it would power off every box on that UPS on a bad read. The cost is the mirror image: such a UPS is one where native still halts its secondaries on FSD while no push ever fires, no matter how the thresholds are set. If you have a unit that reports LB and nothing else, native is the only authority that works on it.

This split is deliberate — native at NUT's LB, push at operator-tunable thresholds crossed earlier — but it means the two authorities can fire minutes apart, and it means the push has a liveness dependency that native does not.

Local-last, and what that costs during an outage (D-7). The watcher host's own local target — its own poweroff — is always held until every enabled remote/serial/push target on the same UPS has been attempted (not necessarily succeeded — see below). So each enrolled push machine on that UPS adds its own transport timeout to the delay before the watcher host powers itself off: the serial path's stty call plus a settle delay, or the ssh path's connect timeout, each running in turn. A push that fails does not block the local target — only a push that has not yet been attempted does — so a hung or unreachable machine slows the watcher's own shutdown by its timeout, but can never prevent it.

A failed shutdown is retried

A transport that returns non-zero is not treated as a completed shutdown. Each target gets up to three attempts per outage, and only a return code of 0 marks it done.

This distinction is load-bearing. The ledger that releases the local-target hold means ATTEMPTED — it exists so a dead remote cannot strand the host running this program. Using that same ledger as the fire-once key gave every machine exactly one attempt per outage: for an ssh target that is a single ~20 s window (ConnectTimeout=10), and on a deployment where the LAN runs off the shortest-runtime UPS, that is precisely the window most likely to fail transiently. Failing it once meant the machine stayed up for the whole outage while still drawing from the battery.

The budget is what keeps the original intent — a box that cannot be reached must not be hammered on every poll for the rest of the outage.

A failure always pages, regardless of shutdown_policy.notify. That flag silences routine attempt and success messages; "we tried to shut this machine down and it did not work" is the one outcome on this path that always needs a human.

What the SSH path actually does

_default_ssh_shutdown runs, per target:

ssh -o BatchMode=yes -o ConnectTimeout=10 -- <user@host> <the record's shutdown_cmd>
# `--` terminates option parsing (BL-01): without it a host or user beginning
# with '-' is read by ssh as an option such as -oProxyCommand=... and executed.

The orchestrator pushes a shutdown command into each box over SSH when its per-group policy (battery_below / runtime_below) trips.

flowchart LR
    subgraph orch["orchestrator host"]
      P[policy gate] -->|ssh sudo shutdown| K1
      P -->|ssh sudo shutdown| K2
    end
    K1["box A (sshd + sudo)"]
    K2["box B (sshd + sudo)"]
    NET{{"network switch / router<br/>⚠ often on the same failing power"}}
    P -.->|every command traverses| NET
    NET -.-> K1
    NET -.-> K2
Loading

The pathology

  1. Network dependency in the exact failure window. A grid outage is when you need the shutdown, and it is also when the switch/router/AP between the orchestrator and the target is most likely dark (unprotected, or on another draining UPS). SSH then times out (ConnectTimeout=10) and the box never shuts down gracefully — it hard-drops when its UPS empties. Serial exists precisely because it sidesteps this; SSH does not.
  2. It reimplements NUT's distributed shutdown — with more moving parts. NUT already solves "shut down every machine on a dying UPS" with the primary/secondary model (below). The SSH path rebuilds a slice of that as an outbound command channel that needs sshd, a login, a shell, and a passwordless sudo shutdown on every target.
  3. Credential/trust inversion. SSH shutdown means the orchestrator holds keys that can run sudo shutdown on every box — a lateral-movement liability that points the wrong way (one host able to halt the fleet). NUT's model inverts this: each box pulls state from the primary and shuts itself down.
  4. No coordination with NUT's own state. The SSH decision runs on the orchestrator's thresholds, independent of NUT's LOWBATT/FSD. Two shutdown authorities on one UPS with no shared sequencing; the "local dies last" ordering is a hand-rolled fragment of what NUT sequences natively.
  5. Fire-and-forget correctness gaps. A box mid-shutdown may drop the SSH connection, so a successful shutdown can return non-zero and page a false failure.

The native NUT model (primary / secondary + FSD)

In NUT, one host is the primary (runs upsd, owns the UPS). Every other UPS-fed host runs upsmon as a secondary, monitoring that upsd over TCP. No SSH, no keys pushed around, no reverse command channel — the secondary shuts itself down. There are two ways it decides to, and which one applies depends on the primary's powervalue for that UPS:

  • Primary-driven FSD — if the primary declares powervalue ≥ 1 for the UPS (i.e. it is itself fed by it), then when the primary hits low-battery it raises the FSD (forced-shutdown) flag; every secondary polls it off upsd (ups.status → OB LB FSD) within one POLLFREQALERT and runs SHUTDOWNCMD.
  • Secondary self-trigger — if the primary is powervalue 0 for that UPS (monitors it but isn't powered by it — this is exactly eulerpi5's case for the Rack and Third UPSes), the primary never raises FSD for it. The secondary must therefore reach the decision itself: with powervalue 1 + MINSUPPLIES 1 it shuts down the moment it reads its own UPS as OB LB (or after DEADTIME if the UPS was last seen OB and then goes silent).

Either way the secondary runs plain shutdown -h now — a secondary must never run killpower/POWERDOWNFLAG (it has no UPS to power off; doing so is a known foot-gun).

flowchart RL
    UPSD["upsd on primary<br/>(sets FSD when critical)"]
    S1["secondary upsmon<br/>box A → local shutdown"]
    S2["secondary upsmon<br/>box B → local shutdown"]
    S1 -->|MONITOR pulls status| UPSD
    S2 -->|MONITOR pulls status| UPSD
    UPSD -.->|FSD flag| S1
    UPSD -.->|FSD flag| S2
Loading

This is the credential-minimal, coordinated, pull-based design NUT is built for. It removes pathologies 2–5 outright — but it introduces one new gap of its own:

!!! warning "The primary-dies-first hole" Secondaries monitor upsd on the primary. If the primary's own UPS dies first, the primary powers off, upsd vanishes, and the secondaries lose their monitor for their UPS. During a real outage (everything already OB) each secondary's local DEADTIME-on-OB timer still fires, so they shut down safely. But if the primary (or the network switch) dies on an otherwise healthy grid, the secondaries are left up-but-blind until the feed returns. upsmon treats prolonged comm-loss as a warning, not a shutdown — by design. The durable fix is a second, independent upsd the secondaries also monitor (Option B, deferred). A serial/ssh push machine on the same box does not cover this hole either: it still runs on the primary, so it dies with the primary and can't cross a dark switch — and in any case a machine cannot be both native and a push authority at once (see Configuration → mutual exclusion). See Deployment → Known limitation: primary-dies-first for the full covered/uncovered breakdown and the shipped Option A mitigation.

The honest trade-off

SSH push (current) Native NUT (secondary + FSD) Serial
Survives a dead network ❌ ❌ (upsd is over TCP) ✅
Credential surface keys + sudo on every box read MONITOR creds only none (getty)
Coordinated with NUT no yes (native) no
Per-box threshold on one UPS ✅ ❌ (FSD is per-UPS) ✅
Works on non-NUT appliances ✅ ❌ (needs nut-client) ✅ (any console)
Agent required on target sshd + sudo nut-client auto-login getty

Native NUT does not fix the network pathology — upsd is reached over TCP, so a secondary is as blind as SSH when the switch is dark. Only serial is network-independent. What native NUT fixes is the credential inversion, the coordination gap, and the reimplementation — for boxes that can run nut-client.

Recommended shape

Keep the orchestrator as the policy brain, but prefer wrapping NUT over pushing SSH:

  • Network-reachable, nut-capable boxes → enroll them as NUT secondaries with ups-orchestrator monitor add (see Deployment → Enroll NUT secondaries). The CLI writes each secondary with powervalue 1 + MINSUPPLIES 1 + DEADTIME 30 so it self-triggers on its own OB LB (the primary here is powervalue 0 for those UPSes and won't raise FSD for them). Credential-minimal, coordinated, no SSH fan-out.
  • Serial → keep as the network-independent shutdown_method for the boxes that matter most, enrolled with monitor add --method serial. This is the only path that survives the outage-network case, so it is not replaceable by either ssh or native.
  • serial / ssh as a machine's shutdown_method → default-off (the central shutdown.enabled gate), and mutually exclusive with native on the same machine — a machine takes exactly one shutdown authority, never both. A native-plus-deadman regime (a push firing only as a last resort strictly below a native secondary's own LB point) was considered for this phase and dropped; it is deferred to a possible future phase. Neither serial nor ssh covers the primary-dies-first hole (it dies with the primary) — that's what the future redundant upsd is for.

The per-box thresholds the current policy layer offers are the one thing plain FSD can't express; if that granularity is actually needed, it belongs at the primary's decision logic (the orchestrator) driving FSD, not in an SSH fan-out.