Every enrolled machine (monitored_machines[], see
Configuration) carries exactly one effective
shutdown_method: none, native, serial, or ssh. native wraps NUT's
own primary/secondary model (below); serial and ssh are the orchestrator's
own push transports — it reaches out to the machine over a console cable or
an SSH connection and sends the shutdown command itself. (The legacy
per-UPS shutdown_targets[] array, described in
Shutdown Targets, predates the per-machine model and is
kept only for back-compat; its remote/serial/local kinds map onto
shutdown_method ssh/serial/(the local host, which has no
monitored_machines entry at all).) The SSH push path is the convenient one,
and it is also the one with the most failure modes. This page describes that
pathology honestly and asks whether NUT's own distributed-shutdown model is a
better fit.
When more than one push-managed machine is due on the same UPS, serial fires before ssh: serial is network-independent (a console cable, not a route through the switch), while ssh dies with the network the same outage may be killing. The sort is stable, so declared order still holds within each transport.
This is also the point where native and a push method are structurally
different kinds of authority, not two options on a spectrum: native is a
per-UPS mechanism — the remote secondary's own upsmon reacts to the
primary's NUT-level FSD flag for that UPS, with no orchestrator involvement
at fire time at all — while serial/ssh are per-machine decisions the
orchestrator itself makes and executes, one machine at a time, on each poll.
A native machine is therefore never projected onto a push attempt (doing
so would shut it down twice); only serial/ssh machines are.
"UPS is close to empty" means two different things for the two authorities.
For a serial/ssh push, "close to empty" is the orchestrator's own
configured shutdown.external group thresholds (battery_below /
runtime_below) evaluated against the current snapshot — an operator-tunable
gate. For native, the trigger is NUT's own low-battery (LB) condition on
the primary, which is an entirely separate mechanism with its own thresholds
configured in NUT itself, not in this orchestrator's config at all.
The paragraph above is easy to read as "both authorities fire at low battery, just with different thresholds". They do not share a mechanism, and the difference decides whether a push happens at all:
-
nativefires from NUT. The primary raises FSD on its ownLBcondition and the remote secondary'supsmonhalts the box. Nothing in this repo is involved, and nothing in this repo can stop it. -
A
serial/sshpush fires from this orchestrator'swatchpoll loop, and from nowhere else.UpsSnapshot.low_battery— the parsedLBflag — has zero consumers in the shutdown gate. It is read only bystatus,report,selftestand the web UI, all of which merely display it.deploy/nut/upssched.conf.snippetdoes mapAT LOWBATT * EXECUTE lowbattanddeploy/upssched-cmd.shdoes forward it, buthandle_lowbattwrites alowbattevent and sends one notification, then returns. It never reaches the shutdown path.
Three consequences follow, and none is obvious from the requirement text:
-
If the
watchunit is not running, no push ever fires. NUT will still deliver its LOWBATT notification and anativesecondary will still halt itself, so the outage looks handled — while everyserial/sshmachine silently rides the battery to the floor.systemctl --user status ups-orchestrator-watchis therefore a shutdown-path check, not just a monitoring one. -
Both
shutdown.externalthresholds must be crossed, not either. Whenbattery_belowandruntime_beloware both set,_close_to_emptyANDs them. A UPS at 5% charge that still reports 20 minutes of runtime does not open the gate. Only when one of the two is left unset does the other decide alone. -
A UPS that raises
LBwithout reporting charge or runtime never opens the gate at all. With both readings unknown,_close_to_emptyreturnsFalse— deliberately, and pinned bytest_an_undefined_close_to_empty_condition_never_fires. This is the shape a dying UPS actually produces (upscstops reportingbattery.chargeandbattery.runtimewhileups.statusstill saysOB), and firing on it would power off every box on that UPS on a bad read. The cost is the mirror image: such a UPS is one wherenativestill halts its secondaries on FSD while no push ever fires, no matter how the thresholds are set. If you have a unit that reportsLBand nothing else,nativeis the only authority that works on it.
This split is deliberate — native at NUT's LB, push at operator-tunable
thresholds crossed earlier — but it means the two authorities can fire minutes
apart, and it means the push has a liveness dependency that native does not.
Local-last, and what that costs during an outage (D-7). The watcher host's
own local target — its own poweroff — is always held until every enabled
remote/serial/push target on the same UPS has been attempted (not
necessarily succeeded — see below). So each enrolled push machine on that UPS
adds its own transport timeout to the delay before the watcher host powers
itself off: the serial path's stty call plus a settle delay, or the ssh
path's connect timeout, each running in turn. A push that fails does not
block the local target — only a push that has not yet been attempted does —
so a hung or unreachable machine slows the watcher's own shutdown by its
timeout, but can never prevent it.
A transport that returns non-zero is not treated as a completed shutdown. Each target gets up to three attempts per outage, and only a return code of 0 marks it done.
This distinction is load-bearing. The ledger that releases the local-target hold means
ATTEMPTED — it exists so a dead remote cannot strand the host running this program.
Using that same ledger as the fire-once key gave every machine exactly one attempt per
outage: for an ssh target that is a single ~20 s window (ConnectTimeout=10), and on
a deployment where the LAN runs off the shortest-runtime UPS, that is precisely the
window most likely to fail transiently. Failing it once meant the machine stayed up for
the whole outage while still drawing from the battery.
The budget is what keeps the original intent — a box that cannot be reached must not be hammered on every poll for the rest of the outage.
A failure always pages, regardless of shutdown_policy.notify. That flag silences
routine attempt and success messages; "we tried to shut this machine down and it did not
work" is the one outcome on this path that always needs a human.
_default_ssh_shutdown runs, per target:
ssh -o BatchMode=yes -o ConnectTimeout=10 -- <user@host> <the record's shutdown_cmd>
# `--` terminates option parsing (BL-01): without it a host or user beginning
# with '-' is read by ssh as an option such as -oProxyCommand=... and executed.
The orchestrator pushes a shutdown command into each box over SSH when its
per-group policy (battery_below / runtime_below) trips.
flowchart LR
subgraph orch["orchestrator host"]
P[policy gate] -->|ssh sudo shutdown| K1
P -->|ssh sudo shutdown| K2
end
K1["box A (sshd + sudo)"]
K2["box B (sshd + sudo)"]
NET{{"network switch / router<br/>⚠ often on the same failing power"}}
P -.->|every command traverses| NET
NET -.-> K1
NET -.-> K2
-
Network dependency in the exact failure window. A grid outage is when you
need the shutdown, and it is also when the switch/router/AP between the
orchestrator and the target is most likely dark (unprotected, or on another
draining UPS). SSH then times out (
ConnectTimeout=10) and the box never shuts down gracefully — it hard-drops when its UPS empties. Serial exists precisely because it sidesteps this; SSH does not. -
It reimplements NUT's distributed shutdown — with more moving parts. NUT
already solves "shut down every machine on a dying UPS" with the primary/secondary
model (below). The SSH path rebuilds a slice of that as an outbound command
channel that needs
sshd, a login, a shell, and a passwordlesssudo shutdownon every target. -
Credential/trust inversion. SSH shutdown means the orchestrator holds keys
that can run
sudo shutdownon every box — a lateral-movement liability that points the wrong way (one host able to halt the fleet). NUT's model inverts this: each box pulls state from the primary and shuts itself down. -
No coordination with NUT's own state. The SSH decision runs on the
orchestrator's thresholds, independent of NUT's
LOWBATT/FSD. Two shutdown authorities on one UPS with no shared sequencing; the "local dies last" ordering is a hand-rolled fragment of what NUT sequences natively. - Fire-and-forget correctness gaps. A box mid-shutdown may drop the SSH connection, so a successful shutdown can return non-zero and page a false failure.
In NUT, one host is the primary (runs upsd, owns the UPS). Every other
UPS-fed host runs upsmon as a secondary, monitoring that upsd over TCP.
No SSH, no keys pushed around, no reverse command channel — the secondary shuts
itself down. There are two ways it decides to, and which one applies depends
on the primary's powervalue for that UPS:
-
Primary-driven FSD — if the primary declares
powervalue ≥ 1for the UPS (i.e. it is itself fed by it), then when the primary hits low-battery it raises the FSD (forced-shutdown) flag; every secondary polls it offupsd(ups.status→OB LB FSD) within onePOLLFREQALERTand runsSHUTDOWNCMD. -
Secondary self-trigger — if the primary is
powervalue 0for that UPS (monitors it but isn't powered by it — this is exactly eulerpi5's case for the Rack and Third UPSes), the primary never raises FSD for it. The secondary must therefore reach the decision itself: withpowervalue 1+MINSUPPLIES 1it shuts down the moment it reads its own UPS asOB LB(or afterDEADTIMEif the UPS was last seenOBand then goes silent).
Either way the secondary runs plain shutdown -h now — a secondary must never
run killpower/POWERDOWNFLAG (it has no UPS to power off; doing so is a known
foot-gun).
flowchart RL
UPSD["upsd on primary<br/>(sets FSD when critical)"]
S1["secondary upsmon<br/>box A → local shutdown"]
S2["secondary upsmon<br/>box B → local shutdown"]
S1 -->|MONITOR pulls status| UPSD
S2 -->|MONITOR pulls status| UPSD
UPSD -.->|FSD flag| S1
UPSD -.->|FSD flag| S2
This is the credential-minimal, coordinated, pull-based design NUT is built for. It removes pathologies 2–5 outright — but it introduces one new gap of its own:
!!! warning "The primary-dies-first hole"
Secondaries monitor upsd on the primary. If the primary's own UPS dies
first, the primary powers off, upsd vanishes, and the secondaries lose their
monitor for their UPS. During a real outage (everything already OB) each
secondary's local DEADTIME-on-OB timer still fires, so they shut down safely.
But if the primary (or the network switch) dies on an otherwise healthy grid,
the secondaries are left up-but-blind until the feed returns. upsmon treats
prolonged comm-loss as a warning, not a shutdown — by design. The durable fix
is a second, independent upsd the secondaries also monitor (Option B,
deferred). A serial/ssh push machine on the same box does not cover
this hole either: it still runs on the primary, so it dies with the primary
and can't cross a dark switch — and in any case a machine cannot be both
native and a push authority at once (see
Configuration → mutual exclusion). See
Deployment → Known limitation: primary-dies-first for the
full covered/uncovered breakdown and the shipped Option A mitigation.
| SSH push (current) | Native NUT (secondary + FSD) | Serial | |
|---|---|---|---|
| Survives a dead network | ❌ | ❌ (upsd is over TCP) | ✅ |
| Credential surface | keys + sudo on every box | read MONITOR creds only | none (getty) |
| Coordinated with NUT | no | yes (native) | no |
| Per-box threshold on one UPS | ✅ | ❌ (FSD is per-UPS) | ✅ |
| Works on non-NUT appliances | ✅ | ❌ (needs nut-client) | ✅ (any console) |
| Agent required on target | sshd + sudo | nut-client | auto-login getty |
Native NUT does not fix the network pathology — upsd is reached over TCP, so
a secondary is as blind as SSH when the switch is dark. Only serial is
network-independent. What native NUT fixes is the credential inversion, the
coordination gap, and the reimplementation — for boxes that can run nut-client.
Keep the orchestrator as the policy brain, but prefer wrapping NUT over pushing SSH:
-
Network-reachable, nut-capable boxes → enroll them as NUT secondaries
with
ups-orchestrator monitor add(see Deployment → Enroll NUT secondaries). The CLI writes each secondary withpowervalue 1+MINSUPPLIES 1+DEADTIME 30so it self-triggers on its ownOB LB(the primary here ispowervalue 0for those UPSes and won't raise FSD for them). Credential-minimal, coordinated, no SSH fan-out. -
Serial → keep as the network-independent
shutdown_methodfor the boxes that matter most, enrolled withmonitor add --method serial. This is the only path that survives the outage-network case, so it is not replaceable by eithersshornative. -
serial/sshas a machine's shutdown_method → default-off (the centralshutdown.enabledgate), and mutually exclusive withnativeon the same machine — a machine takes exactly one shutdown authority, never both. A native-plus-deadman regime (a push firing only as a last resort strictly below a native secondary's own LB point) was considered for this phase and dropped; it is deferred to a possible future phase. Neitherserialnorsshcovers the primary-dies-first hole (it dies with the primary) — that's what the future redundantupsdis for.
The per-box thresholds the current policy layer offers are the one thing plain FSD can't express; if that granularity is actually needed, it belongs at the primary's decision logic (the orchestrator) driving FSD, not in an SSH fan-out.