Shutdown Targets (LEGACY, back-compat only)

!!! warning "This per-UPS shutdown_targets[] array is LEGACY" New enrollments use the per-machine monitored_machines[].shutdown_method model (none/native/serial/ssh, via monitor add --method ...) — see Configuration. shutdown_targets[] is still parsed so pre-existing config files keep loading, but a new entry should not be written here. kind: "serial" maps onto shutdown_method: "serial"; kind: "remote" maps onto shutdown_method: "ssh"; kind: "local" has no monitored_machines equivalent — the watcher host is never enrolled as a machine, so a local target stays the only way to describe its own shutdown.

A shutdown target is a machine the orchestrator knows how to power down. Each UPS can have any number, and target entries are only transports: they say how to reach a device. The top-level shutdown policy decides whether any target command is allowed to run. That policy is disabled by default.

The host running the daemon is protected separately by NUT's own upsmon SHUTDOWNCMD; orchestrator targets are optional extra actions for the devices a UPS feeds.

!!! note "SSH is the fallback, not the primary path" Native NUT (upsmon secondary, enrolled via monitor add) is the primary graceful-shutdown mechanism; the remote (SSH) / serial targets here are a configurable, default-off backup. See SSH vs. native NUT for the full analysis, the failure modes, and when each path applies.

Deferred: a native-plus-deadman regime, where a legacy target fired only as a last resort strictly below a native secondary's own LB point, was scoped for this phase and dropped — it may return in a future phase. (It was also never actually implemented: battery_below/runtime_below on a target are parsed but not consulted at runtime — see Triggers, below.)

Chosen defaults for the open questions

These were live-environment unknowns resolved to defaults, not blockers:

  • DEADTIME 30 on secondaries (the ≥3×POLLFREQ floor for POLLFREQ 5).
  • Per-host nft scope — each secondary's source IP added to the dedicated table inet ups_orchestrator set, not a broad allow.
  • Serial-cable presence unknown → legacy target kind defaults to remote; switch to serial where a console cable exists (network-independent, survives a dark switch).
  • nut group present → snippet/secret files at 0640 root:nut, with a 0600 root:root fallback where the group is unavailable.

Kinds

  • serial: send the command over a serial console (device + baud) into a passwordless or auto-login getty. This needs no network, so it keeps working during an outage when the router/switch is also dark. It's the best primary path for a server you can reach over a console cable.
  • remote: run the command over SSH. host can be a real hostname or an ssh_config Host alias; leave user empty to connect as just ssh <alias>, which keeps the real hostname/port/key in ~/.ssh/config.
  • local: the host the daemon runs on. Local targets run after every enabled serial/remote target on the same UPS, so the watcher dies last.

Triggers

Auto-shutdown is controlled from one top-level surface:

  • shutdown.enabled must be true.
  • The relevant group must be enabled:
    • shutdown.external.enabled for serial and remote.
    • shutdown.internal.enabled for local.
  • The UPS must be on battery when require_power_outage is true.
  • The UPS must have been on battery for at least min_on_battery_seconds.
  • The UPS must be close to empty by the group's central battery_below and runtime_below thresholds.

If battery percent and runtime are both available, both must be at or below the group threshold. This prevents a shutdown at, for example, 50% battery while the UPS still reports 30 minutes of runtime. If one reading is unavailable, the available threshold is used.

An explicit remote_shutdown event still respects this policy; it does not bypass disabled groups or the close-to-empty gate.

Example

!!! danger "Match your console's ACTUAL baud — a wrong value is silent" Read the real rate off the far end: systemctl cat serial-getty@<tty>.service on that machine. stty only configures the local tty and returns success at essentially any recognised rate on the same physical line, so a wrong baud here sends garbage down the wire and the orchestrator reports success (rc 0) anyway — it cannot detect a far-end speed mismatch, only a rejected local line configuration. Declare the real speed of the console you are wiring to, not a value copied from an example.

{
  "name": "bigserver",
  "kind": "serial",
  "enabled": true,
  "device": "/dev/serial/by-id/usb-FTDI_FT232R_USB_UART-if00-port0",
  "baud": 9600,
  "cmd": "sudo /sbin/shutdown -h now"
}

What each kind needs on the far end

  • serial: an auto-login getty on the target's serial port. Scope the auto-login to that serial tty only; don't loosen SSH or the physical console.
  • remote: key-based SSH (BatchMode) and a passwordless shutdown for the SSH user.
  • local: a sudoers.d rule for passwordless shutdown/poweroff, which deploy/install.sh writes for the run user.