Domain Scheduling
| COS | Yes |
| Access | R/W |
| Data length | 1 byte |
| Byte | Field | Values |
|---|---|---|
| 0 | Program type | 0 Programmable (default), 1 Non-programmable |
Disabling the program keeps current setpoints until changed via protocol or UI.
| COS | Yes |
| Access | R/W |
| Data length | 3 bytes |
| Byte | Field | Values |
|---|---|---|
| 0 | Away fan | 1 On, 2 Auto, 3 Circ |
| 1 | Away heat index | 0→15.5 °C … 5→18.5 °C (see table) |
| 2 | Away cool index | 0→26.5 °C … 5→29.5 °C |
| Index | °C | approx °F |
|---|---|---|
| 0 | 15.5 | 60 |
| 1 | 16 | 61 |
| 2 | 16.5 | 62 |
| 3 | 17 | 63 |
| 4 | 17.5 | 64 |
| 5 | 18.5 | 65 |
| Index | °C | approx °F |
|---|---|---|
| 0 | 26.5 | 80 |
| 1 | 27 | 81 |
| 2 | 27.5 | 82 |
| 3 | 28.5 | 83 |
| 4 | 29 | 84 |
| 5 | 29.5 | 85 |
Defaults (guide bold): Fan 2 Auto, Heat index 2 (62 °F), Cool index 5 (85 °F).
Guide oddity: the heat index map jumps from 4 → 17.5 °C to 5 → 18.5 °C, skipping 18.0 °C. This matches the conversion table (64 °F → 17.5 °C, 65 °F → 18.5 °C by the first-entry rule) but means 18.0 °C is not representable here. See Guide Errata.
| COS | Yes |
| Access | R/W |
| Data length | 21 bytes |
| Read selector |
Required — day index as Read Request data: 0–6 = Sunday–Saturday |
Programs the four daily events (Wake, Leave, Return, Sleep). Events are ordered by start time, not event name. Deadband violations on write are rejected with a NACK (out of range) when the thermostat is in Auto — unlike Setpoint & Mode 2.1, which auto-corrects.
| Field | Byte | Values |
|---|---|---|
| Day | Byte 0 | 0: Sunday 1: Monday 2: Tuesday 3: Wednesday 4: Thursday 5: Friday 6: Saturday 7: Week days (value is not valid during a read request) 8: Weekend days (value is not valid during a read request) 9: All Days (7) (value is not valid during a read request) 10-255: Reserved |
| Wake Start Minute | Byte 1 | 0 – 59: Minute60-255: Reserved |
| Wake Start Hour | Byte 2 | 0-23: Hour24-255: Reserved |
| Wake Fan | Byte 3 | 0: Reserved 1: On 2: Auto 3: Circ 4-255: Reserved |
| Wake Heat Setpoint | Byte 4 | bits 7: Heat Setpoint Sign 0: Positive 1: Negative bits 6: Heat Setpoint ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Heat Setpoint in Celsius (refer to appendix on for C / F conversion) 0-3: Reserved (out of range)4-32: Heat Setpoint 32-63: Reserved (out of range) |
| Wake Cool Setpoint | Byte 5 | bits 7: Cool Setpoint Sign 0: Positive 1: Negative bits 6: Cool Setpoint ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Cool Setpoint in Celsius (refer to appendix on for C / F conversion) 0-9: Reserved (out of range)10-37: Cool Setpoint 38-63: Reserved (out of range) |
| Leave Start Minute | Byte 6 | 0 – 59: Minute 60-255: Reserved |
| Leave Start Hour | Byte 7 | 0-23: Hour24-255: Reserved |
| Leave Fan | Byte 8 | 0: Reserved 1: On 2: Auto 3: Circ 4-255: Reserved |
| Leave Heat Setpoint | Byte 9 | bits 7: Heat Setpoint Sign 0: Positive 1: Negative bits 6: Heat Setpoint ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Heat Setpoint in Celsius (refer to appendix on for C / F conversion) 0-3: Reserved (out of range)4-32: Heat Setpoint 32-63: Reserved (out of range) |
| Leave Cool Setpoint | Byte 10 | bits 7: Cool Setpoint Sign 0: Positive 1: Negative bits 6: Cool Setpoint ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Cool Setpoint in Celsius (refer to appendix on for C / F conversion) 0-9: Reserved (out of range)10-37: Cool Setpoint 38-63: Reserved (out of range) |
| Return Start Minute | Byte 11 | 0 – 59: Minute 60-255: Reserved |
| Return Start Hour | Byte 12 | 0-23: Hour24-255: Reserved |
| Return Fan | Byte 13 | 0: Reserved 1: On 2: Auto 3: Circ 4-255: Reserved |
| Return Heat Setpoint | Byte 14 | bits 7: Heat Setpoint Sign 0: Positive 1: Negative bits 6: Heat Setpoint ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Heat Setpoint in Celsius (refer to appendix on for C / F conversion) 0-3: Reserved (out of range)4-32: Heat Setpoint 32-63: Reserved (out of range) |
| Return Cool Setpoint | Byte 15 | bits 7: Cool Setpoint Sign 0: Positive 1: Negative bits 6: Cool Setpoint ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Cool Setpoint in Celsius (refer to appendix on for C / F conversion) 0-9: Reserved (out of range)10-37: Cool Setpoint 38-63: Reserved (out of range) |
| Sleep Start Minute | Byte 16 | 0 – 59: Minute 60-255: Reserved |
| Sleep Start Hour | Byte 17 | 0-23: Hour24-255: Reserved |
| Sleep Fan | Byte 18 | 0: Reserved 1: On 2: Auto 3: Circ 4-255: Reserved |
| Sleep Heat Setpoint | Byte 19 | bits 7: Heat Setpoint Sign 0: Positive 1: Negative bits 6: Heat Setpoint ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Heat Setpoint in Celsius (refer to appendix on for C / F conversion) 0-3: Reserved (out of range)4-32: Heat Setpoint 32-63: Reserved (out of range) |
| Sleep Cool Setpoint | Byte 20 | bits 7: Cool Setpoint Sign 0: Positive 1: Negative bits 6: Cool Setpoint ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Cool Setpoint in Celsius (refer to appendix on for C / F conversion) 0-9: Reserved (out of range)10-37: Cool Setpoint 38-63: Reserved (out of range) |
| Value | Meaning |
|---|---|
| 0–6 | Sunday–Saturday |
| 7 | Weekdays (write only; not valid on read) |
| 8 | Weekend (write only; not valid on read) |
| 9 | All days (write only; not valid on read) |
Each of Wake / Leave / Return / Sleep uses five bytes:
- Start minute (0–59)
- Start hour (0–23)
- Fan (1 On, 2 Auto, 3 Circ)
- Heat setpoint (packed temperature byte)
- Cool setpoint (packed temperature byte)
See Temperature Encoding for setpoint bits.
Guide typo: heat setpoint ranges read "4-32: Heat Setpoint 32-63: Reserved" — overlapping at 32; presumed intent is 33–63 reserved. See Guide Errata.
| COS | Yes |
| Access | R/W |
| Data length | 10 bytes |
| Byte | Field | Values |
|---|---|---|
| 0 | Hold | 0 Disabled, 1 Temporary, 2 Permanent, 3 Away, 4 Vacation |
| 1 | Fan | 1 On, 2 Auto, 3 Circ |
| 2 | Heat SP | Packed temp (or Null when disabled) |
| 3 | Cool SP | Packed temp |
| 4 | DEH vacation | 0 Off; 50–70 %RH when used |
| 5 | End minute | 0–59 |
| 6 | End hour | 0–23 |
| 7 | End date | 1–31 (day of month) |
| 8 | End month | 1–12 |
| 9 | End year | Year − 2000 (0 = 2000) |
Cancel hold: Hold = Disabled; all other fields Null.
COS causes: hold expire; timed lockout; user hold change; incremental SP; setpoint/mode write; lockout change cancelling hold.
NACK if DEH written when dehumidification not installed / wrong vacation config, or deadband violation.
| COS | Yes |
| Access | R/W |
| Data length | 1 byte |
| Byte | Field |
|---|---|
| 0 | 0 Off, 1 On |
Raises room temperature by installer offset (default 3 °), then returns to normal setpoint. NACK if room already too warm (over 85 °F). Cancel via Heat Blast off, cancel hold, or new hold.
Protocol reference for scrypted-aprilaire · Validate codecs with npm test