Domain: Sensors (0x05)

Temperature / humidity status enums (common)

Temperature sensor status

Value Meaning
0 No error
1 Out of range low
2 Out of range high
3 Not installed (5.2 only — in 5.1 the guide marks value 3 as Reserved)
4 Open / error open
5 Short / error short

Humidity sensor status

Value Meaning
0 No error
3 Not installed
4 Error

5.1 Sensor Values & Status

COS No
Access R
Data length 16 bytes

Full array of installed sensor status/value pairs for monitoring. Prefer 5.2 Controlling Sensors for the sensors that actually control the thermostat.

Field Byte Values
Built in Temperature Sensor Status Byte 0 0: No Error 1: Out of Range Low 2: Out of Range High 3: Reserved 4: Open 5: Short 6-255 Reserved
Built In Temperature Sensor Value Byte 1 bits 7: Built-in Sensor Sign 0: Positive 1: Reserved bits 6: Built-in Sensor ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Built-in Sensor value in Celsius 0-40: Value (refer to appendix 1 for C / F conversion) 40-63: Reserved (out of range)
Wired Remote Temperature Sensor Status Byte 2 0: No Error 1: Out of Range Low 2: Out of Range High 3: Reserved 4: Open 5: Short 6-255 Reserved
Wired Remote Temperature Sensor Value Byte 3 bits 7: Wired Remote Sensor Sign 0: Positive 1: Reserved bits 6: Wired Sensor ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Built-in Sensor value in Celsius 0-40: Value (refer to appendix 1 for C / F conversion) 41: Reserved 42-63: Reserved (out of range)
Wired Outdoor Temperature Sensor Status Byte 4 0: No Error 1: Out of Range Low 2: Out of Range High 3: Reserved 4: Open 5: Short 6-255 Reserved Note: This status is for wired and wireless sensor values only
Wired Outdoor Temperature Sensor Value Byte 5 bits 7 Outdoor Sensor Sign 0: Positive 1: Negative bits 6 Outdoor Sensor ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Outdoor Sensor Value 0-55: Value (refer to appendix 1 for C / F conversion) 56-63 : Reserved (out of range) Note: This value is for wired and wireless sensor values only
Built in Humidity Sensor Status (except 8810) Byte 6 0: No Error 1: Reserved 2: Reserved 3: Not Installed 4: Error 5-255: Reserved
Built in Humidity Sensor Value (except 8810) Byte 7 0: Reserved 1-99: %RH 100-255: Reserved
RAT Sensor Status (except 8810,8820) Byte 8 0: No Error 1: Out of Range Low 2: Out of Range High 3: Reserved 4: Open 5: Short 6-255 Reserved
RAT Sensor Value (except 8810,8820) Byte 9 bits 7 RAT Sensor 0: Positive 1: Negative bits 6 Outdoor Sensor ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Outdoor Sensor Value 0-55: Value (refer to appendix 1 for C / F conversion) 56-63 : Reserved (out of range)
LAT Sensor Status (except 8810,8820) Byte 10 0: No Error 1: Out of Range Low 2: Out of Range High 3: Reserved 4: Open 5: Short 6-255 Reserved
LAT Sensor Value (except 8810,8820) Byte 11 bits 7 LAT Sensor 0: Positive 1: Negative bits 6 Outdoor Sensor ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Outdoor Sensor Value 0-55: Value (refer to appendix 1 for C / F conversion) 56-63 : Reserved (out of range)
Wireless Outdoor Temperature Sensor Status (except 8810,8820) Byte 12 0: No Error 1: Out of Range Low 2: Out of Range High 3: Reserved 4: Open 5: Short 6-255 Reserved Note: This status is for wired and wireless sensor values only
Wireless Outdoor Temperature Sensor Value (except 8810,8820) Byte 13 bits 7 Outdoor Sensor Sign 0: Positive 1: Negative bits 6 Outdoor Sensor ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Outdoor Sensor Value 0-55: Value (refer to appendix 1 for C / F conversion) 56-63 : Reserved (out of range) Note: This value is for wired and wireless sensor values only
Wireless Outdoor Humidity Sensor Status (except 8810,8820) Byte 14 0: No Error 1: Reserved 2: Reserved 3: Not Installed 4: Error 5-255: Reserved
Wireless Outdoor Humidity Sensor Value (except 8810,8820) Byte 15 0: Reserved 1-99: %RH 100-255: Reserved

Temperature values use the packed Celsius byte (see Temperature Encoding). Humidity values are percent RH.

Guide typo: Byte 1 lists "0-40: Value 40-63: Reserved" — overlapping at 40; presumed intent is 41–63 reserved (Byte 3 states 41+ reserved for the same encoding). See Guide Errata.

5.2 Controlling Sensors Status and Value

COS Yes
Access R
Data length 8 bytes

The sensors actually selected for indoor/outdoor temperature and humidity control.

Byte Field
0 Indoor temperature status
1 Indoor temperature value (packed °C)
2 Outdoor temperature status
3 Outdoor temperature value
4 Indoor humidity status
5 Indoor humidity %
6 Outdoor humidity status
7 Outdoor humidity %

COS causes: controlling sensor status or value changes.

5.3 Support Modules

COS Yes
Access R
Data length 8 bytes
Read selector Module index as Read Request data: 0–3 = Support Module 1–4
Models Except 8810; up to 4 modules (8081 temp / 8082 temp+RH)
Field Byte Values
Module Address Byte 0 0: Reserved 1:1 2:2 3:3 4:4 5-255: Reserved
Sensor 1 Status Byte 1 0: Normal 1-2: Reserved 3: Not Installed 4: Error 3-255: Reserved
Sensor 1 Mode Byte 2 0: Control 1: Monitor 2: Absent 3-255: Reserved
Sensor 1 Temp Value Byte 3 bits 7: Sensor 1 Temp 0: Positive 1: Reserved bits 6: Wired Sensor ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Built-in Sensor value in Celsius 0-40: Value (refer to appendix 1 for C / F conversion) 41-63: Reserved (out of range)
Sensor 2 Status Byte 4 0: Normal 1-2: Reserved 3: Not Installed 4: Error 3-255: Reserved
Sensor 2 Mode Byte 5 0: Control 1: Monitor 2: Absent 3-255: Reserved
Sensor 2 Temp Value Byte 6 bits 7: Sensor 2 Temp 0: Positive 1: Reserved bits 6: Wired Sensor ½ Celsius Indicator 0: “.0” Celsius 1: “.5” Celsius bits 5-0: Built-in Sensor value in Celsius 0-40: Value (refer to appendix 1 for C / F conversion) 41-63: Reserved (out of range)
Sensor 2 RH Value Byte 7 0: Reserved 1-99: %RH 100-255: Reserved

Modules can be configured as Control, Monitor, or Absent. Controlling module counts also appear in Setup / Installer Settings.

5.4 Written Outdoor Temperature Value

COS Yes (status → Timed Out)
Access R/W
Data length 2 bytes
Constraint For Automation outdoor-sensor mode only
Byte Field Notes
0 Outdoor sensor status Read/COS only. 0 No error; 4 Timed Out. Writes must send 0 (does not overwrite real status).
1 Temperature Packed °C. Writes do not generate COS. Negatives limited per guide.

Staleness: if no successful update for 10 minutes, value is invalid / timed out. Host should refresh more often than every 10 minutes when sharing one outdoor sensor across multiple thermostats.