Packet Frame
Same for host and thermostat:
| Field | Size | Description |
|---|---|---|
| REV | 1 | Protocol revision (1–255; examples use 0x01) |
| SEQ | 1 | Sequence number (see ranges) |
| CNT | 2 | Payload length, big-endian |
| PAYLOAD | CNT | Action + domain + attribute + data (or NACK form) |
| CRC | 1 | 8-bit CRC over REV ‖ SEQ ‖ CNT ‖ PAYLOAD
|
Byte: 0 1 2 3 4 ............... 4+CNT-1 4+CNT
Field: REV SEQ CNT_H CNT_L [ PAYLOAD ] CRC
| Source | Range |
|---|---|
| Home automation / cloud | 0–127 |
| Thermostat | 128–255 |
| Read Response | Same SEQ as initiating Read Request |
| Retries | Same SEQ as original packet |
- High byte first: length
512(0x0200) → bytes0x02 0x00. - For normal messages:
CNT = 3 + data_length(Action + Domain + Attribute + data). - For NACK:
CNT = 2(Action + Status only).
- Computed over REV, SEQ, CNT, and entire PAYLOAD.
- Implementation in this project: lookup-table CRC in
AprilaireClient.ts.
Some diagrams in the guide label the trailer as Reserved
0xFF— the guide's examples show0xFFbecause they don't compute the CRC, and its prose says the byte's return value "will vary (it is a development function)". The formal frame definition (guide note 5) defines it as an 8-bit CRC over REV+SEQ+CNT+PAYLOAD, and all real traffic uses the CRC. Implementations must compute it.
| Field | Size | Description |
|---|---|---|
| Action | 1 | Write / Read / COS / … |
| Functional domain | 1 | Attribute group |
| Attribute | 1 | Attribute within domain |
| Data | 0…N | Attribute-specific |
Write Control / Setpoint & Mode: Null mode, Fan On, Heat 21.0 °C, Cool 26.5 °C:
01 00 00 07 01 02 01 00 01 15 5A [CRC]
│ │ └───┘ │ │ │ │ │ │ └── cool 26.5°C = 0x5A
│ │ CNT=7 │ │ │ │ │ └──── heat 21.0°C = 0x15
│ │ │ │ │ │ └─────── fan On = 0x01
│ │ │ │ │ └────────── mode Null = 0x00
│ │ │ │ └────────────── attribute 0x01
│ │ │ └───────────────── domain Control 0x02
│ │ └──────────────────── action Write 0x01
│ └────────────────────────────── sequence 0x00
└───────────────────────────────── revision 0x01
When a multi-field attribute is written, a data sub-field of 0 / Null means do not modify that sub-field. For temperature fields, Null also uses positive sign and .0 fraction bits cleared (value magnitude 0).
Protocol reference for scrypted-aprilaire · Validate codecs with npm test