Building energy

extensions/energy/ simulates the heat balance of the thermal zones of a building, step by step. It gives the air temperature of each zone and the ideal heating and cooling power that holds its setpoints. extensions/building/views/thermal.mojo makes the zone model from a Building.

The rooms of an office floor warm and cool through a summer day

Modules

Module What it gives
energy/ids ZoneId, SurfaceId, WindowId and BoundaryKind (EXTERIOR, INTERZONE, GROUND)
energy/weather read_epw, parse_epw, design_day, ashrae_clear_sky, Weather, WeatherRecord and WeatherLocation
energy/solar sun_position, sun_angles, declination, equation_of_time, orientation, incidence_cosine and tilted_irradiance
energy/conduction LayeredWall, the finite-difference mesh of a Construction, and FaceCondition
energy/zone ZoneModel, Zone, Surface, Window, InternalGains, typical_gains, gain_fraction and the film coefficients
energy/simulation simulate, SimulationOptions, default_options, SimulationResult and ideal_loads
building/views/thermal thermal_view, ThermalView, ThermalViewOptions and default_thermal_options

Run a simulation

Make the zone model with thermal_view. Read the weather with read_epw, or make a clear day with design_day. Then call simulate.

var view = thermal_view(building, default_thermal_options(), List[ZoneId]())
var weather = read_epw("site.epw")
var options = default_options()
var result = simulate(view.model, weather, options)
var heating = result.heating_energy(ZoneId(0)).to(KILOWATT_HOUR)
var air = result.air_temperature(12, ZoneId(0)).to(CELSIUS)

An empty grouping gives one zone per space. Give one ZoneId per space to group spaces into zones. The zone ids must start at 0 and have no gap. Spaces in one group must use the same daily gain profile. The view refuses a group that mixes profiles; it cannot apply one profile to another use.

view.dropped lists what the view leaves out. view.space_zone, view.surface_face and view.window_opening map the model back to the building.

You can edit the zone model before the simulation. For example, set a zone's furniture capacity or turn off its heating with a heating setpoint of 0 K. simulate checks the model again.

Units

Every quantity at an API boundary carries a unit type.

Quantity Type Unit inside
Temperature Temperature64 K
Power, energy Power64, Energy64 W, J
Irradiance, gain per floor area HeatFlux64 W/m²
U-value, film coefficient ThermalTransmittance64 W/(m² K)
Infiltration Frequency64, with AIR_CHANGE_PER_HOUR 1/s
Time step, time zone, time of day Duration64 s
Latitude, longitude, slope, azimuth Angle64 rad

A Vec3d normal is in model coordinates: x east, y north and z up, turned by Site.north.

The physical model

Weather

An EPW file has 8 header lines and one record per line. The reader keeps the date, the hour, the air temperatures, the humidity and the pressure. It also keeps the three irradiation fields and the wind. It refuses a short header, a missing field, a field that is not a number and a value outside the ranges of the format. A missing value in the file, such as 99.9 for the dry-bulb, is out of range.

An irradiation in Wh/m² over an interval is the mean irradiance over that interval. The record holds over its interval, and the sun is placed at its middle.

design_day makes a clear day. The dry-bulb temperature is low + (high - low) (1 + cos(2π (t - 15) / 24)) / 2, with t in hours. The low is at 03:00 and the high at 15:00. The irradiance is the clear-sky model of the ASHRAE Handbook of Fundamentals (1985 to 2005 editions):

  • I_DN = CN A exp(-B / cos θz), with the monthly A, B and C of the handbook table.
  • I_d = C I_DN on the horizontal.
  • I = I_DN cos θz + I_d.

The relative humidity follows from the dew point by the Magnus form of Alduchov and Eskridge (1996). The pressure is that of the standard atmosphere, 101.325 (1 - 2.25577e-5 Z)^5.2559 kPa.

Sun and irradiance

The solar equations are those of Duffie and Beckman, "Solar Engineering of Thermal Processes", 4th edition, 2013:

Quantity Equation Source
Day angle B = 360 (n - 1) / 365 eq. 1.4.2
Equation of time E = 229.2 (0.000075 + 0.001868 cos B - 0.032077 sin B - 0.014615 cos 2B - 0.04089 sin 2B) min eq. 1.5.3, Spencer (1971)
Declination Spencer's Fourier series eq. 1.6.1b
Solar time standard time + 4 min/degree (longitude - 15 × time zone) + E eq. 1.5.2
Zenith angle cos θz = cos φ cos δ cos ω + sin φ sin δ eq. 1.6.5
Solar azimuth γs = sign(ω) arccos((cos θz sin φ - sin δ) / (sin θz cos φ)) eq. 1.6.6
Incidence cos θ = cos θz cos β + sin θz sin β cos(γs - γ) eq. 1.6.3
Irradiance on a surface I_T = I_bn max(cos θ, 0) + I_d (1 + cos β) / 2 + I ρg (1 - cos β) / 2 eq. 2.15.1, isotropic sky

An azimuth is measured from south, west positive. A longitude and a time zone are east positive.

Conduction

LayeredWall cuts each layer of a construction into equal elements, with a node at each element boundary. Each element is small enough that its Fourier number α Δt / Δx² is at least fourier. A layer gets at most 64 elements. The energy balance of node i is the implicit (backward Euler) form, Incropera section 5.10:

C_i (T_i' - T_i) / Δt = K_(i-1) (T_(i-1)' - T_i') + K_i (T_(i+1)' - T_i')

A face node also gains h (T_env - T') + q. Here h is the film coefficient and q is the absorbed radiation. The system is tridiagonal, and solve_tridiagonal solves it.

Zones

A zone is well-mixed air. Its balance in each step is:

C (T' - T) / Δt = Σ h A (T_s' - T') + (Σ U A + ρ c_p V n) (T_out - T')
                  + G + Σ SHGC A I + Q
Term Meaning Value
C Air and furniture heat capacity ρ c_p V + Zone.furniture
ρ c_p Air at 20 °C and 101.325 kPa 1.204 kg/m³ × 1006 J/(kg K), ASHRAE Handbook of Fundamentals chapter 1
h A (T_s' - T') Heat from each surface's inside face The film coefficient times the net area
U A Each window The glazing U-value, films included
n Infiltration Air changes per second
G Internal gains typical_gains(use) × floor area × gain_fraction(use, hour)
SHGC A I Solar gain of each window The irradiance on the window's plane
Q Ideal heating (positive) or cooling (negative) power Found by the step

A surface's node temperatures are linear in the zone temperatures. The step solves each wall three times: once with the known conditions, and once for a unit temperature on each face. The zone balances then form one small linear system.

A zone floats freely while its air stays between its setpoints. A zone that would leave its band is held at the setpoint it would cross. An active-set loop finds which zones are held. It frees a held zone whose power has the wrong sign, and it repeats until nothing changes.

Film coefficients

The film coefficients combine convection and long-wave radiation:

Face Coefficient Source
Inside, wall 1/0.13 = 7.69 W/(m² K) ISO 6946
Inside, ceiling or roof (heat flows up) 1/0.10 = 10 W/(m² K) ISO 6946
Inside, floor (heat flows down) 1/0.17 = 5.88 W/(m² K) ISO 6946
Outside, default 1/0.04 = 25 W/(m² K) ISO 6946
Outside, with wind_film 4 + 4 v + 4 ε σ T³ ISO 6946 Annex C

With the ISO 6946 films, a surface's U-value equals Construction.u_value.

Ground

A ground-contact surface sees the ground temperature of SimulationOptions through its outside film. This is a simplification of ISO 13370: the model has no soil layer.

Internal gains

typical_gains gives these peak gains in W/m² of floor. They are typical values of the order of the ASHRAE Handbook of Fundamentals chapter 18 and ISO 17772-1. They are not design values. A project must use its own values.

Use People Lighting Equipment Profile
office 7 8 10 work
corridor 1 5 0 work
core 0 3 0 work
lobby 3 8 1 work
retail 6 12 3 shop
living 3 5 4 home
bedroom 2 4 1 home
kitchen 3 7 25 home
bathroom 1 6 2 home
storage 0 4 0 work
mechanical 0 5 10 always
meeting 20 10 5 work
Profile Share of the peak
work 1 from 08:00 to 18:00, 0.1 otherwise
shop 1 from 09:00 to 21:00, 0.1 otherwise
home 1 from 18:00 to 23:00, 0.5 from 23:00 to 07:00, 0.3 otherwise
always 1

The thermal view

thermal_view makes one surface for each face of each wall, slab and roof:

Face Surface
A space on both sides INTERZONE, between the two zones
The outside below a floor at level 0 GROUND
The outside on any other side EXTERIOR

A window in an exterior wall becomes a Window. Its area leaves the area of the wall's surface. The view records these simplifications in dropped:

  • A door stays part of its wall's construction.
  • A window in an interior wall stays part of the wall.
  • A wall that a window fills has no opaque surface.
  • Columns and beams carry no heat.
  • The model has no furniture. Set Zone.furniture to add it.
  • A window is one plane in its wall, with no frame and no reveal.

Validation

Each row is a test. The reference is in the test docstring.

Test Reference Reference value Measured
Steady load of a room Σ U A ΔT + ρ c_p V n ΔT, U from Construction.u_value 1102.126 W Relative error 7e-8
Steady wall ISO 6946 series resistance q = U ΔT Error under 1e-9 W/m²
Semi-infinite solid, 6 h after a 100 K step Incropera eq. 5.57, the error function T(x, t) Largest error 0.039 K
Slab, 2 h after a 100 K step, Δt = 900 to 112.5 s Carslaw and Jaeger section 3.3, the Fourier series T(L/2, t) 2.04, 1.05, 0.53, 0.27 K: first order
Lumped zone cooling, τ = 10.8 h, Δt = 60 s Incropera section 5.2: exp(-t/τ) 2.160 °C after 24 h 0.17%; 1.5e-13 K from (1 + Δt/τ)^-n
Two zones in series Conductance divider T_B Error under 1e-6 K
Equation of time, February 3 Duffie and Beckman Example 1.5.1 -13.5 min, solar time 10:19 -13.49 min
Incidence on a tilted surface Duffie and Beckman Example 1.6.1 cos θ = 0.817 0.8174
Zenith and azimuth Duffie and Beckman Example 1.6.2 66.5°, -40.0°; 79.6°, 112.0° 66.55°, -40.08°; 79.64°, 112.02°
Declination Duffie and Beckman Table 1.6.1 12 monthly values Largest error 0.050°
Declination at the equinoxes and the solstice The obliquity, 23.44° Sign change on March 20 to 21 and September 23 to 24 23.45° on June 21
EPW fixture assets/energy/fixture.epw The values of each field Exact
EPW refusals The ranges of the EPW format Each malformed header and record in the tests Each refused
Thermal view The faces of the cell complex Surface areas equal face areas less windows Error under 1e-9 m²

Limits

  • The model has no humidity balance. It computes sensible heat only.
  • It has no HVAC system model. The loads are ideal, with no capacity limit.
  • The interior films combine convection and radiation. The model has no long-wave exchange between surfaces, and no sky temperature below the air temperature.
  • All internal and solar gains go to the zone air at once. The sun through a window does not heat the floor first.
  • The solar heat gain coefficient of a window does not change with the angle of incidence. The model has no shading by overhangs or by other buildings.
  • Gain profiles are the same every day, with no weekends or holidays.
  • The ground is at one fixed temperature, with no soil layer.
  • Conduction is one-dimensional. The model has no thermal bridges.

References

  • Duffie and Beckman, "Solar Engineering of Thermal Processes", 4th edition, 2013, chapters 1 and 2.
  • Incropera, DeWitt, Bergman and Lavine, "Fundamentals of Heat and Mass Transfer", 6th edition, 2007, chapter 5.
  • Carslaw and Jaeger, "Conduction of Heat in Solids", 2nd edition, 1959, chapter 3.
  • ASHRAE Handbook of Fundamentals, chapters 1, 14, 16 and 18.
  • ISO 6946, "Building components and building elements — Thermal resistance and thermal transmittance".
  • ISO 13370, "Thermal performance of buildings — Heat transfer via the ground".
  • ISO 17772-1, "Energy performance of buildings — Indoor environmental quality".
  • Alduchov and Eskridge, "Improved Magnus form approximation of saturation vapor pressure", 1996.
  • Liu and Jordan, "The interrelationship and characteristic distribution of direct, diffuse and total solar radiation", 1960.