Process-image symbols that are not linked, on purpose

Published from _docs/reference/plc-io-exceptions.md — edit it there, not here. Changes made in the wiki are overwritten on the next sync.

Hand-written. The I/O reconciliation reads the first column of the table below and treats those symbols as accounted for, reporting them as by design rather than as open work.

Everything else in the process image that has no terminal channel is a gap. A signal with no link compiles, runs, and does nothing — no compiler and no runtime will mention it. That is the whole reason this file is narrow: an entry here silences a real check, so it needs a reason someone can verify, not a reason someone assumed.

Before adding a row, establish the reason from the project — a declaration comment, a registration call, an HMI binding — and cite it. If the only argument is "it has never been linked", that is an open gap, not an exception.

Symbol Why it is not linked Owner
MAIN.ControlSource_HMI_Web.MainPMLControl_Simplified.StartPressed Written by the panel over ADS, not by a terminal. FB_ControlSource_HMI's declaration header states it: "The HMI binds straight to this block's inherited structs - there is no translation layer." The block is registered by MAIN.Initialize via Machine.RegisterExternalController(THIS^). HMI
MAIN.ControlSource_HMI_Web.MainPMLControl_Simplified.StopPressed Same block, same mechanism. HMI
MAIN.ControlSource_HMI_Web.MainPMLControl_Simplified.ResetPressed Same block, same mechanism. HMI

Polarity: the two emergency stops are normally closed, on both sides

Not a linking exception — both SS_EStop1.HardwareInput and SS_EStop2.HardwareInput are linked like any other input. This is a sense note, recorded here because it is invisible in the process image and dangerous to discover late.

A real emergency stop is wired normally closed and reads TRUE while healthy. Getting that the other way round has the worst failure mode available: a cut cable would read as "no emergency stop". So the NC sense is the one the control program is written against, and the twin was made to match it rather than the other way round.

The twin inverts, so PLC_1 does not branch on whether it is driven by the twin. The twin's OC.Interactions.Button sets _link.Status.SetBit(0, value) from _pressed, so bValue is TRUE while the mushroom is pressed — the opposite of the hardware. SIM_1's FG_System.Mapping carries the NOT that fixes it:

GVL_EtherCAT_1_SIM.FG_System_Panel_EL1809_1.bIn9	:= NOT SS_EStop1.bValue;
GVL_EtherCAT_1_SIM.FG_System_Panel_EL1809_1.bIn10	:= NOT SS_EStop2.bValue;

PLC_1 then reads NC in both worlds. FB_IlluminatedButton.Active is HardwareInput XOR _Inverted, and FG_System.Initialize sets the polarity once:

SS_EStop1.Inverted := TRUE;   // NC contact - TRUE while healthy
SS_EStop2.Inverted := TRUE;

FG_System.EmergencyStopActive is unchanged: it is written against Active, which is still TRUE while a mushroom is latched.

The two edits are one change. Dropping the NOT in SIM_1 without clearing Inverted in PLC_1, or the reverse, gives a machine that is emergency-stopped whenever nobody is pressing anything — or, far worse, one that never reports an emergency stop at all.

Two ordering traps, both closed in code

Neither is obvious from reading the assignment, and both turn an inverted input back into a spurious or a missed emergency stop.

The polarity is set in Initialize step 0, with the registrations — not in step 10 with the other parameters. Machine.EnforceSafety reads FG_System.EmergencyStopActive through a property getter that does not care whether FG_System has finished initialising. Every scan the polarity is still FALSE is a scan on which a healthy mushroom reads as latched and the machine aborts. Step 0 leaves no such scan.

FB_IlluminatedButton.Initialize seeds HMI.DeviceConfig.Inverted from _Inverted. HMICommunication runs _Inverted := HMI.DeviceConfig.Inverted whenever HMI control is available, and CyclicLogic publishes the other direction only after SUPER^.CyclicLogic() has already called it — so on the first executing scan the mirror is still the struct's zero default. Without the seed, selecting Manual could silently revert the polarity to FALSE.

With no process image, both mushrooms report active. SIM_1 not running, EtherCAT down or a cut cable all leave the bits at 0, which under NC means latched. That is the fail-safe direction and it is intended — a machine that will not leave Aborted right after startup is usually the twin not being connected yet, not a fault in FG_System.

Not exceptions

Recorded here so nobody adds them to the table by mistake.

  • MAIN.Machine.FG_02._CameraEnable, ._LightEnable, ._Trigger, ._ShotOk — open work, not exempt. FG_02's module exists and declares its I/O, but no FG_02* terminal exists on either master yet, so there is nothing to allocate against. The I/O tooling can propose the terminals to add. Once they exist, these four link like any others.