Pitfalls hit while developing the extended commands, kept around for reference when adding new commands later, or revisiting these conclusions.
The original idea was to mirror the "numbered" approach getpreg/
getjpreg use, letting getalarm:nnn specify which historical alarm
to read (ERR_DATA's first parameter formally looks like an input
sequence number). Real-hardware testing disproved this: parsing the
sequence number itself worked fine (echoed back during debugging,
1, 2, 5, 8, 9 all matched exactly what was sent), but no matter what
number was given, ERR_DATA returned the same entry every time.
Cross-checking against the TP's alarm history screen, entries 5, 8,
and 9 were "reset", SRVO-003, and SYST-039 respectively, which
didn't match the PROG-048 read back at all. Testing with these
values, this parameter to ERR_DATA doesn't look like it selects a
history index; what it's actually for isn't clear. The TP clearly uses
a different mechanism to page through alarm history, and this driver
hasn't found an equivalent access method yet, not ruling out that it's
just not found rather than confirmed impossible. This approach has
since been removed; anyone continuing to try, this is the known
sticking point. For full alarm history, go directly to the TP's
報警 → 履歷 screen for now.
A real pitfall hit along the way: ERR_DATA's first parameter
formally looks like an input, but after the call it gets rewritten by
ERR_DATA itself (observed becoming something like an internal alarm
count, e.g. 1447). Early on, a FOR loop variable was passed directly
as this parameter; after one call the loop variable was corrupted,
ending the loop after a single iteration and throwing in a stray
semicolon that shouldn't have been there. The fix was to copy the loop
variable into a separate variable each iteration and pass that copy to
ERR_DATA, letting it mutate the copy while the loop variable itself
stays untouched.
This pitfall isn't specific to ERR_DATA: any KAREL built-in
function's parameter, unless verified to be pure input, shouldn't be
passed a control-flow variable (a loop counter and the like) directly.
This lesson still holds even though ERR_DATA itself turned out to be
a dead end for now, kept here for the next time a different built-in
function is used.
The first version hung outright during real-hardware testing (no
response received). Comparing against the already-verified
GET_CURJPOS (mappdk_cmd.kl) found the cause: GET_CURJPOS calls
CNV_JPOS_REL(jpos, joint_vals, status) with the generic JOINTPOS
type, where the third parameter is a status code, not an axis count.
The first version wrongly declared it as JOINTPOS6 and treated the
third parameter as an axis count, both wrong. After matching
GET_CURJPOS's approach exactly (JOINTPOS, the status semantics,
using UNINIT() to tell which array entries are real axes),
real-hardware verification across multiple position-register values
read and wrote correctly, round-tripped consistently, and never hung
again. setjpreg uses the reverse conversion (CNV_REL_JPOS), and its
approach matched MOVEJ/CHECK_JOINT from the start, so it never had
a problem.