FG_02 — the behaviour contract

Published from _docs/reference/fg-02-behaviour.md — edit it there, not here. Changes made in the wiki are overwritten on the next sync.

Optical inspection. Written from the shipped ST; the PLC is master for behaviour.

Source: Beckhoff/TwinCAT_1/PLC/PLC_1/Modules/12 FG_02/FG_02.TcPOU.


Components

One: P_Camera : FB_AbstractCamera, twin device Y_Camera (LinkByte). Nothing in this group moves.

The twin side is FB_Camera in SIM_1. Both halves have to agree on the bit layout and nothing checks it for you.

The camera handshake

Two signals out, four back. This is a real protocol, not a status bit echoing a trigger.

Out Back Meaning
Enable Ready permission to trigger
Trigger DeviceBusy the shot is running
ResultValid a verdict is on the wire, and stays there until the trigger is released
ResultOK the verdict

What that buys is diagnosis: the station can tell "the camera never answered" from "the shot never completed" from "the part is bad". The previous interface had one status bit wired straight from the trigger and could report none of the three — which is why the old sequence was a fixed 1 s dwell that could not fail.

What is actually compared

The twin does not evaluate anything. It echoes enable and trigger and hands over the datum it read; Ready, DeviceBusy, ResultValid and ResultOK are all synthesised in SIM_1's FB_Camera, which compares the datum against an expected value set in that group's Mapping action. Change the expectation there, not in the control PLC.

Station Payload key read Expected Written by
FG_01 SerialNumber 60 the part itself (Assembly Part 1)
FG_02 LaserMark 240 the FG_01 laser
FG_05 CapsID 810 the part itself

FG_02 is the station that verifies the mark, not FG_01. FG_01 fires the laser and then reads SerialNumber — it never checks its own work. An unmarked part reads LaserMark = 0 here and fails.

Production cycle

Execute, mode Production.

Step Action Advances on Timeout
0 P_Camera.Disable —
10 Enable Ready ReadyTimer 2 s → fault 2
20 Trigger DeviceBusy or ResultValid ShotTimer 3 s → fault 3
30 read verdict, latch _LastResultOK ResultOK — else fault 1 ShotTimer → fault 3
40 Disable (clears the trigger first) —
50 ChangeState(Complete) —

ResultValid counts as an acknowledgement at step 20. A fast camera can raise and drop DeviceBusy inside one scan, so waiting only on DeviceBusy would hang on exactly the device that answered quickest.

ShotTimer deliberately spans steps 20 and 30: the split between acknowledged and answered is the station's business, but the camera's total response time is one number and is what an operator would be told. Same budgets as FG_01 — it is the same device.

Maintenance and Manual run no group sequence; the camera stays reachable through FB_AbstractCamera.HMICommunication whenever HMIPermissions has granted control.

Fault codes

ST_FG_02_Inspection_Status, published as HMI.Inspection.FaultCode.

Code Meaning
1 the part is bad (ResultOK false)
2 the camera never became Ready
3 the shot never completed

A NOK aborts the group. Index02 never receives OperationDone and raises its own fault 3 on the operation timeout, exactly as FG_04 does on B_NIO. There is no reject station on this line, so a bad part stops the pallet where it is and asks for a human.

Safety

No Safety section is authored for this group in the twin, and no permissive is written in the PLC. That is a gap in the twin, not permission to invent one. The station has no moving parts and no hazardous output; the cell-level chain (Machine.SafetyOk → AbortImmediate) still applies.

Non-production states

Every one of Aborting, Stopping, Resetting is the same two steps: P_Camera.Disable(), then complete. Disable() drops the trigger before the enable, so a shot is never left armed on a device that is losing power on the next line.

Home position for this group is nothing energised. There is no mechanism to bring back to a known place, so Resetting terminates on its own call and on nothing else — the rule from transport-behaviour.md §4.

Clearing sets _FaultCode := 0 first, then waits for P_Camera.Reset(). The fault clears by the act of clearing: a bad part is still a bad part after the camera has stopped reporting it, and the operator has to have taken it out.