Behaviour FG_02
Published from
_docs/reference/fg-02-behaviour.md— edit it there, not here. Changes made in the wiki are overwritten on the next sync.
Optical inspection. Written from the shipped ST; the PLC is master for behaviour.
Source: Beckhoff/TwinCAT_1/PLC/PLC_1/Modules/12 FG_02/FG_02.TcPOU.
One: P_Camera : FB_AbstractCamera, twin device Y_Camera (LinkByte). Nothing in this group moves.
The twin side is FB_Camera in SIM_1. Both halves have to agree on the bit layout and nothing
checks it for you.
Two signals out, four back. This is a real protocol, not a status bit echoing a trigger.
| Out | Back | Meaning |
|---|---|---|
Enable |
Ready |
permission to trigger |
Trigger |
DeviceBusy |
the shot is running |
ResultValid |
a verdict is on the wire, and stays there until the trigger is released | |
ResultOK |
the verdict |
What that buys is diagnosis: the station can tell "the camera never answered" from "the shot never completed" from "the part is bad". The previous interface had one status bit wired straight from the trigger and could report none of the three — which is why the old sequence was a fixed 1 s dwell that could not fail.
The twin does not evaluate anything. It echoes enable and trigger and hands over the datum it
read; Ready, DeviceBusy, ResultValid and ResultOK are all synthesised in SIM_1's
FB_Camera, which compares the datum against an expected value set in that group's Mapping
action. Change the expectation there, not in the control PLC.
| Station | Payload key read | Expected | Written by |
|---|---|---|---|
| FG_01 | SerialNumber |
60 | the part itself (Assembly Part 1) |
| FG_02 | LaserMark |
240 | the FG_01 laser |
| FG_05 | CapsID |
810 | the part itself |
FG_02 is the station that verifies the mark, not FG_01. FG_01 fires the laser and then reads
SerialNumber — it never checks its own work. An unmarked part reads LaserMark = 0 here and
fails.
Execute, mode Production.
| Step | Action | Advances on | Timeout |
|---|---|---|---|
| 0 | P_Camera.Disable |
— | |
| 10 | Enable |
Ready |
ReadyTimer 2 s → fault 2
|
| 20 | Trigger |
DeviceBusy or ResultValid
|
ShotTimer 3 s → fault 3
|
| 30 | read verdict, latch _LastResultOK
|
ResultOK — else fault 1
|
ShotTimer → fault 3
|
| 40 |
Disable (clears the trigger first) |
— | |
| 50 | ChangeState(Complete) |
— |
ResultValid counts as an acknowledgement at step 20. A fast camera can raise and drop
DeviceBusy inside one scan, so waiting only on DeviceBusy would hang on exactly the device that
answered quickest.
ShotTimer deliberately spans steps 20 and 30: the split between acknowledged and answered
is the station's business, but the camera's total response time is one number and is what an
operator would be told. Same budgets as FG_01 — it is the same device.
Maintenance and Manual run no group sequence; the camera stays reachable through
FB_AbstractCamera.HMICommunication whenever HMIPermissions has granted control.
ST_FG_02_Inspection_Status, published as HMI.Inspection.FaultCode.
| Code | Meaning |
|---|---|
| 1 | the part is bad (ResultOK false) |
| 2 | the camera never became Ready
|
| 3 | the shot never completed |
A NOK aborts the group. Index02 never receives OperationDone and raises its own fault 3 on
the operation timeout, exactly as FG_04 does on B_NIO. There is no reject station on this line, so
a bad part stops the pallet where it is and asks for a human.
No Safety section is authored for this group in the twin, and no permissive is written in the
PLC. That is a gap in the twin, not permission to invent one. The station has no moving parts and
no hazardous output; the cell-level chain (Machine.SafetyOk → AbortImmediate) still applies.
Every one of Aborting, Stopping, Resetting is the same two steps: P_Camera.Disable(), then
complete. Disable() drops the trigger before the enable, so a shot is never left armed on a device
that is losing power on the next line.
Home position for this group is nothing energised. There is no mechanism to bring back to a known
place, so Resetting terminates on its own call and on nothing else — the rule from
transport-behaviour.md §4.
Clearing sets _FaultCode := 0 first, then waits for P_Camera.Reset(). The fault clears by the
act of clearing: a bad part is still a bad part after the camera has stopped reporting it, and the
operator has to have taken it out.
-
fg-01-behaviour.md— the same camera protocol, one station back -
transport-behaviour.md— the Index↔group handshake and the reset rule
Generated from DT_PSA_OPCV by _workflow/tools/build_wiki.py — 39 pages. Edit the source there; changes made here are overwritten.
Getting started
- Home
- Setup
- Using-The-Application
- How-It-Works
- PLC-Connectivity
- Engineering-Workflow
- Machine-Description
- Glossary
The machine
- Machine
- Machine-PLC-Symbols
- Machine-Provenance
- Machine-FG_01
- Machine-FG_02
- Machine-FG_03
- Machine-FG_04
- Machine-FG_05
- Machine-FG_System
- Machine-FG_Transport
Behaviour
- Behaviour-FG_01
- Behaviour-FG_02
- Behaviour-FG_03
- Behaviour-FG_04
- Behaviour-FG_05
- Behaviour-FG_System-Safety
- Behaviour-Gripper-Station-Reset
- Behaviour-State-Lamp
- Behaviour-Transport
Device types
- Device-Button
- Device-ControlBunker
- Device-Cylinder
- Device-DataReader
- Device-DrivePosition
- Device-DriveSimple
- Device-Lamp
- Device-LinkByte
- Device-Lock
- Device-PanelSampler
- Device-SensorBinary
- Device-SignalBinary
Control platforms
- Beckhoff TwinCAT 3
- Siemens TIA Portal — no wiki yet